38AUQ

60 Hz Heat Pump Outdoor Unit Split System with Puronr (R---410A) Refrigerant 6 to 20 Nominal Tons Sizes: 07---25

Product Data

C10108

Fig. 1 -- 38AUQ -- 07--12 shown

Gemini split system heat pump systems save energy and provide outstanding heating and cooling all year with:

S All-season comfort in any climate

S High energy savings capability

S Suitability for new construction or replacement

FEATURES/BENEFITS

System indoor and outdoor sections offer outstanding performance in either the cooling or heating mode

Heat pump system energy savings opportunity

Electrical energy consumption is always a prime concern when selecting an air-conditioning system for a commercial application. An easy, effective way to save energy is to install a heat pump. When building plans call for a heat pump, consider a matched Carrier 38AUQ/40RUQ heat pump system. These systems not only offer highly efficient cooling, they also provide a clean, safe, efficient source of heat. In fact, they are capable of delivering more than 3 units of heat energy for each unit of electrical power consumed.

Heat pump uniqueness

The outstanding performance of these heat pump systems is due to the heat pump’s ability to absorb and transfer heat — from outdoors to indoors for heating, and from indoors to outdoors for cooling. System indoor and outdoor sections operate as evaporators or condensers, depending on whether heating or cooling is required. The heating cycle starts with the outdoor coil absorbing heat from the surrounding air (even outside air at extremely cold temperatures), and ends with the indoor coil releasing or rejecting heat to the air around it.

38AUQ application versatility

Whether for a new application or replacement, these Carrier split system heat pumps offer time-proven performance for year-round comfort in any climate. With matching 40RUQ air handler, the units standard cooling operation ranges up to 125_F (52_C) and down to 35_F (2_C) ambient temperatures. If lower ambient cooling temperatures are required, Carrier’s Motor Master controller will allow operation down to --20_F (--29_C) ambient temperatures.

FEATURES/BENEFITS (cont.)

Rugged long life compressor

The 38AUQ outdoor units are equipped with a scroll compressor for superior efficiency and long life. Crank case heaters are available where required and each circuit is further protected by a suction line accumulator to protect during the defrost cycles or unique applications plus provide important oil management, all resulting in higher reliability.

Controls for performance efficiency

These units offer the building owner operating controls and components designed for performance dependability.

The highly efficient hermetic scroll compressors are engineered for long life and durability. The compressor includes overload protection and compressor vibration isolation for further enhancement of quiet operation. The high-pressure switch protects the entire refrigeration system from abnormally high operating pressures. A loss-of-charge switch is also provided to protect the system against low charge conditions.

Each unit utilizes the the Comfort Alertt diagnostic and troubleshooting control system. This protects the units operation and provides valuable diagnostic information such as:

-- System Go LED indicator -- Fault LED indicator -- Compressor fault LED indicator -- Phase loss protection -- Phase reversal protection -- Anti short cycle protection

The 24-v--75VA control circuit transformer permits quick, easy wiring of standard and programmable 24-v thermostats.

The 24--v--75VA control circuit transformer also comes with a re--settable circuit breaker for extra protection.

Latest safety standards are assured through UL (Underwriters’ Laboratories), UL -- Canada and ETL (Electrical Testing Laboratories) approval .

The 38AUQ units utilize a reliable defrost board with field configurable timed defrost cycles. The defrost board may be easily configured for defrost cycles of 30 to 90 minutes, depending upon the application.

Motor failure due to electrical overload is prevented by temperature and current sensors. Coil quality and performance are enhanced by copper tubes and aluminum fins, which provide maximum heat transfer. The coil is circuited for subcooling. A large heat transfer surface offers additional efficiency.

Innovative Carrier 40RUQ indoor units are custom matched to 38AUQ outdoor units for superior system performance

The 40RUQ Heat Pump air handler has excellent fan performance, efficient direct-expansion (DX) coils, easy installation, and a unique combination of indoor air quality features. Its versatility and state-of-the-art features help to ensure that the heat pump system provides economical performance now and in the future.

Easy installation and service — The 40RUQ multi--position design and component layout helps to get the unit installed and running quickly. The direct-expansion (DX) coils have factory-installed thermostatic expansion valves (TXVs) with matching distributor nozzles. All 40RUQ units also include factory-installed check valves and piping for heat pump duty with matching 38AUQ units.

The 40RUQ units can be converted from horizontal to vertical operation simply by repositioning the unit. Drain pan connections are duplicated on both sides of the unit.

Fan motors and contactors are pre--wired. For easier service, the filters, motor, drive, TXVs, check valves, and coil connections are accessible by removing a single side panel.

Indoor-air quality (IAQ) features — The unique combination of IAQ features in the 40RUQ Series indoor units helps to make sure that only clean, fresh, conditioned air is delivered to the occupied space.

In the Cooling mode, direct-expansion (DX) cooling coils prevent the build-up of humidity in the room, even during part-load conditions.

Standard 2-in. disposable filters remove dust and airborne particles from the occupied space.

Thermal insulation contains an immobilized anti-microbial agent to inhibit the growth of bacteria and fungi. The anti-microbial agent is registered with the U.S.

Environmental Protection Agency (EPA).

The pitched corrosion-free drain pan can be adjusted for a right- or left-hand connection to provide positive drainage and to prevent standing condensate. Each unit contains two separate drain pans which are provided for either vertical or horizontal fan coil positions.

The 40RUQ accessory economizer can provide ventilation air to improve indoor air quality. When used in conjunction with Carrier Comfort System thermostats and CO2 sensors or PremierLink controller, the economizer admits fresh outdoor air to replace stale, recirculated indoor air.

Economy — The 40RUQ Series air handlers have low initial costs, and they continue to save money by providing reduced installation expense and energy-efficient performance.

Quick installation reduces installation costs, and TXVs, check valves, and heat pump piping are factory-installed.

High-efficiency, precision-balanced fans minimize air turbulence, surging, and unbalanced operation, cutting operating expenses.

The economizer accessory precisely controls the blend of outdoor air and room air to achieve comfort levels.

When the outside air enthalpy is suitable, outside air dampers can fully open to provide “free” cooling.

A U Q

Rugged dependability — The 40RUQ units are made to last. The die-formed galvanized steel panels ensure structural integrity under all operating conditions. Galvanized steel fan housings are securely mounted to a die-formed galvanized steel deck. Coil housings are galvanized steel, and coils have aluminum fins mechanically bonded to copper tubes. The condensate drain pans provide corrosion-free performance.

Coil flexibility — Model 40RUQ coils have galvanized steel casings; inlet and outlet connections are on the same end. The coils are designed for use with Puron (R--410A) refrigerant and have 3/8-in. diameter copper tubes mechanically bonded to aluminum sine-wave fins. The coils include matched, factory-installed TXVs with matching distributor nozzles. Check valves and heat pump piping are also included in all 40RUQ units.

Duplicate piping access holes on both sides of the unit eliminate drilling; condensate connections for both vertical and horizontal installations are also provided on both sides of the unit.

TABLE OF CONTENTS

PAGE

Features/Benefits 1

Model Number Nomenclature 3

AHRI Capacity Ratings 4

Physical Data 5

Options and Accessories 6

Base Unit Dimensions 8

Performance Data 12

Electrical Data 22

Typical Piping and Wiring 31

Typical Wiring Schematic 33

Application Data 40

Guide Specifications 41

MODEL NUMBER NOMENCLATURE

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

3 8 A U Q A 0 8 A 0 A 6 -- 0 A 0 A 0

Model Brand / Packaging 38AU = Commercial Split System 0 = Standard Puronr R---410A Refrigerant 1 = LTL Packaging

Type Electrical Options Q = Heat Pump A = None

C = Non---Fused Disconnect Refrigerant Options A = None Service Options B = Low Ambient 0 = None D = Single circuit two---stage (07, 08, 12 models only) 1 = Un---powered Convenience Outlet E = Single circuit two---stage with 2 = Powered Convenience Outlet

Low Ambient Controls (07, 08, 12 models only) Factory Assigned

Nominal Tonnage A = Default 07 = 6 Tons 16 = 15 Tons 08 = 7.5 Tons 25 = 20 Tons Base Unit Controls 12 = 10 Tons 0 = Standard Electrical Mechanical Controls

Factory Assigned Design Rev A = Default --- = Factory Assigned

Factory Assigned Voltage 0 = Default 1 = 575/3/60

5 = 208/230/3/60 Coil Options (Tube --- Fin --- Hail Guard) 6 = 460/3/60 A = Al/Cu Standard B = Pre Coat Al/Cu C = E---Coat Al/Cu M = Al/Cu Standard with louvered hail guard N = Pre Coat Al/Cu with louvered hail guard P = E---Coat Al/Cu with louvered hail guard

A

AHRI CAPACITY RATINGS

Cooling

UNIT COOLING

STAGES

NOM. CAPACITY

(TONS)

NET COOLING

CAPACITY (MBH)

TOTAL POWER

(kW) EER IEER IEER w/

2---SPEED

38AUQ(A,B)07 / 40RUQ07 1 6 70.0 6.4 11.0 12.6 N/A

38AUQ(D,E)07 / 40RUQ07 2 6 70.0 6.0 11.7 12.6 13.8

38AUQ08 (A,B) /40RUQ08 1 7.5 89.0 8.1 11.0 12.0 N/A

38AUQ08 (D,E) /40RUQ08 2 7.5 88.0 8.0 11.0 12.0 12.7

38AUQ(A,B)12 / 40RUQ12 1 10 112.0 10.2 11.0 12.0 N/A

38AUQ(D,E)12 / 40RUQ12 2 10 112.0 10.2 11.0 12.0 13.8

38AUQ16 / 40RUQ16 2 15 178.0 16.8 10.6 11.0 12.5

38AUQ25 / 40RUQ25 2 20 222.0 20.8 10.7 11.0 12.5

High Heat at 47_F (8_C)

UNIT HEATING

STAGES

NOM. CAPACITY

(TONS)

NET HEATING

CAPACITY (MBH) TOTAL POWER (kW) COP

38AUQ(A,B)07 / 40RUQ07 1 6 66.0 5.9 3.30

38AUQ(D,E)07 / 40RUQ07 1 6 66.0 5.9 3.30

38AUQ08 / 40RUQ08 1 7.5 87.0 7.7 3.30

38AUQ(A,B)12 / 40RUQ12 1 10 106.0 9.4 3.30

38AUQ(D,E)12 / 40RUQ12 1 10 106.0 9.4 3.30

38AUQ16 / 40RUQ16 1 15 178.0 15.3 3.40

38AUQ25 / 40RUQ25 1 20 214.0 17.9 3.50

Low Heat at 17_F (--8_C)

UNIT HEATING

STAGES

NOM. CAPACITY

(TONS)

NET HEATING

CAPACITY (MBH) TOTAL POWER (kW) COP

38AUQ(A,B)07 / 40RUQ07 1 6 39.0 4.8 2.40

38AUQ(D,E)07 / 40RUQ07 1 6 39.0 4.8 2.40

38AUQ08 / 40RUQ08 1 7.5 42.0 6.3 2.40

38AUQ(A,B)12 / 40RUQ12 1 10 66.0 8.5 2.40

38AUQ(D,E)12 / 40RUQ12 1 10 66.0 8.1 2.40

38AUQ16 / 40RUQ16 1 15 108.0 13.2 2.40

38AUQ25 / 40RUQ25 1 20 130.0 15.9 2.40

LEGEND

AHRI --- Air---Conditioning, Heating and Refrigeration Institute ASHRAE --- American Society of Heating, Refrigerating and Air Conditioning, Inc.

EER --- Energy Efficiency Ratio IEER --- Integrated Energy Efficiency Ratio

NOTES

1. Rated in accordance with AHRI Standard.

2. Ratings are based on:

Cooling Standard: 80_F (27_C) db, 67_F (19_C) wb indoor air temp and 95_F (35_C) db outdoor air temp.

IEER Standard: 80_F (27_C) db, 67_F (19_C) wb indoor air temp and 4 various outdoor temperatures.

3. All units comply with ASHRAE 90.1 Energy Standard for minimum EER and IEER requirements.

4. All units are AHRI listed as factory defined matched combinations of specific indoor and outdoor unit components.

Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program For verification of certification for individual products, go to www.ahridirectory.org.

07 --- 12 Models 16 & 25 Models

A

SOUND POWER LEVELS, dB

UNIT COOLING

STAGES

OUTDOOR SOUND (dB) A---Weighted 63 125 250 500 1000 2000 4000 8000

38AUQ(A,B)07 1 82 86.4 86.0 79.2 80.2 77.6 72.0 67.9 62.3

38AUQ(D.E)07 1 84 87.8 84.9 83.2 81.4 78.7 74.5 68.8 63.8

38AUQ08 1 & 2 82 86.8 85.7 80.3 80.3 77.7 72.3 70.2 65.4

38AUQ(A,B)12 1 82 82.8 81.5 79.2 79.4 76.2 72.3 69.4 64.2

38AUQ(D,E)12 1 84 84.8 92.0 80.8 82.6 78.4 74.0 69.2 67.8

38AUQ16 2 80 90.3 81.8 78.0 76.7 75.2 70.5 66.4 61.9

38AUQ25 2 85 91.0 85.0 80.0 86.0 79.0 73.0 68.0 63.0

LEGEND

dB = Decibel NOTE: Outdoor sound data is measure in accordance with AHRI standard 270.

PHYSICAL DATA

38AUQ(A,B)07 38AUQ(D,E)07 38AUQ(A,B)08 38AUQ(D,E)08 38AUQ(A,B)12 38AUQ(D,E)12 38AUQ16 38AUQ25

Refrigeration System

# Circuits / # Comp. / Type 1 / 1 / Scroll 1 / 1 / 2---Stage Scroll 1 / 1 / Scroll 1 / 1 /

Digital Scroll 1 / 1 / Scroll 1 / 2 / Scroll 2 / 2 / Scroll 2 / 2 / Scroll

Shipping charge A/B (lbs) 9.0 Puron 9.0 Puron 9.0 Puron 9.0 Puron 9.0 Puron 9.0 Puron 9.0/9.0 Puron 9.0/9.0 Puron System charge w/ fan coil *

A/B (lbs) 18 18 21 24 27 27 21 / 21 27 /27

Metering Device Acutrol Acutrol Acutrol Acutrol Acutrol Acutrol Acutrol Acutrol High---press. Trip / Reset

(psig) 630 / 505 630 / 505 630 / 505 630 / 505 630 / 505 630 / 505 630 / 505 630 / 505

Low---press. Trip / Reset (psig) 27 / 44 27 / 44 27 / 44 27 / 44 27 / 44 27 / 44 27 / 44 27 / 44

Outdoor Coil Material --- Tube / Fin Al/Cu Al/Cu Al/Cu Al/Cu Al/Cu Al/Cu Al/Cu Al/Cu

Coil type RTPF RTPF RTPF RTPF RTPF RTPF RTPF RTPF Rows / FPI 2 / 17 2 / 17 2 / 17 2 / 17 2 / 17 2 / 17 2 / 17 2 / 17

Total Face Area (ft2) 17.5 17.5 23.0 28.1 28.1 28.1 47.1 50.1 Outdoor fan / motor

Qty / Motor drive type 2 / direct 2 / direct 2 / direct 2 / direct 2 / direct 2 / direct 3 / direct 4 / direct Motor HP / RPM 1/4 / 1100 1/4 / 1100 1/4 / 1100 1/4 / 1100 1/4 / 1100 1/4 / 1100 1/4 / 1100 1/4 / 1100 Fan diameter (in) 22 22 22 22 22 22 22 22

Nominal Airflow (cfm) 6,000 6,000 6,000 6,000 6,000 6,000 10,000 14,000 Watts (total) 610 610 610 610 610 610 970 1150

Piping Connections Qty / Vapor (in. ODS) 1 / 11/8 1 / 11/8 1 / 11/8 1 / 11/8 1 / 13/8 1 / 13/8 2 / 13/8 2 / 13/8 Qty / Liquid (in. ODS) 1 / 13/8 1 / 13/8 1 / 1/2 1 / 1/2 1 / 1/2 1 / 1/2 2 / 1/2 2 / 1/2

LEGEND

* Approximate system charge with 25 ft. piping of sizes indicated with matched 40RUQ RTPF --- Round Tube / Plate Fin

A

OPTIONS AND ACCESSORIES

38AUQ

ITEM OPTION* ACCESSORY†

Disconnect Switch (non-fused)*** X Enviro-Shield Coil Protection X Convenience Outlet (115-v) Powered X Convenience Outlet Non---powered X Louvered Hail Guard X X

Low Ambient Temperature Motormaster Control** X X PremierLink Controls X Programmable Thermostats X

* Factory--- installed option † Field--- installed accessory ** Available as an option or accessory *** Not available when unit MOCP electrical rating exceeds 80 amps

Enviro--Shield outdoor coil options are available to match coil protection to site conditions for optimum durability. See the table below and refer to the Application data for selection guidance. Consult a Carrier representative for further information.

Low ambient temperature Motormasterr head pressure control operates in Cooling mode at outdoor temperatures below 35_F (2_C). The Motormaster control varies the speed of outdoor--fan motors to maintain correct condensing temperature down to –20_F.

115--v convenience outlet is available to provide power to electric drills, lights, and refrigerant recovery machines.

This means that a separate 115--v power supply is no longer required.

Non--powered convenience outlet requires the filed installation of a general purpose 125--volt 15--A circuit powered from a source elsewhere in the building.

Non--fused disconnect switch removes power locally at the condensing unit. This switch also includes a power lockout capability to protect the service person. This lockout switch saves time and effort as the service person no longer needs to access a distant disconnect switch while servicing the unit.

Outdoor coil louvered hail guard protects outdoor units from hail and other flying debris.

PremierLink controller is a field retrofit split system control compatible with Carrier Comfort Networkr (CCN) controls and other building automation systems (BAS).

This control is designed to allow users the access and ability to change factory--defined settings thus expanding the function of the standard unit.

Carrier commercial thermostats provide 7--day programmable capability for commercial application.

Outdoor Coil Protection Applications

Enviro-Shield

DESCRIPTION

ENVIRONMENT

Standard Non---Corrosive

Mild Coastal

Moderate Coastal

Severe Coastal Industrial

Combined Coastal and Industrial

Alum Fin / Cu Tube X Pre-Coated Al/Cu X E-Coated Al/Cu X X X X X

A

OPTIONS AND ACCESSORIES (cont.)

40RUQ

ITEM OPTION* ACCESSORY{

Alternate Fan Motors X Alternate Drives X Prepainted Units X CO2 Sensors X Condensate Drain Trap X Discharge Plenum X Economizer X Electric Heat X Hot Water Heating Coils X Overhead Suspension Package X Programmable Thermostats X Return Air Grille X Steam Heating Coil X Subbase X

* Factory--- installed option.

{ Field--- installed accessory

Factory--installed options

Alternate fan motors and drives are available to provide the widest possible range of performance.

Prepainted steel units are available from the factory for applications that require painted units. Units are painted with American Sterling Gray color.

Field--installed accessories

CO2 sensors can be used in conjunction with the economizer accessory to help meet indoor air quality requirements. The sensor signals the economizer to open when the CO2 level in the space exceeds the set point. A Carrier Comfort System programmable thermostat can be used to override the sensor if the outside--air temperature is too high or too low.

Condensate drain trap includes an overflow shutoff switch that can be wired to turn off the unit if the trap becomes plugged. Kit also includes a wire harness that can be connected to an alarm if desired. The transparent trap is designed for easy service and maintenance.

Discharge plenum directs the air discharge directly into the occupied space; integral horizontal and vertical louvers enable redirection of airflow. Accessory is available unpainted or painted. Field assembly is required (only applicable for vertical application).

Economizer (enthalpy controlled) provides ventilation air and “free” cooling if outside ambient temperature and humidity are suitable. It can also be used with CO2 sensors to help meet indoor air quality requirements.

Electric resistance heat coils have an open--wire design and are mounted in a rigid frame. Safety cutouts for high temperature conditions are standard. Terminal block for single--point power connection is included.

Two--row hot water coils have copper tubes mechanically bonded to aluminum plate fins and non--ferrous headers.

Overhead suspension package includes necessary brackets to support units in horizontal ceiling installations.

Carrier’s line of thermostats provide both programmable and non--programmable capability with the new Debonairr line of commercial programmable thermostats. The TEMP System controls offer communication capability with staged heating and cooling, and the Commercial Electronic thermostats provide 7--day programmable capability for economical applications.

Return--air grille provides a protective barrier over the return--air opening and gives a finished appearance to units installed in the occupied space. Accessory is available unpainted or painted.

One--row steam coil has copper tubes and aluminum fins.

The Inner Distributing Tube (IDT) design provides uniform temperatures across the coil face. The steam coil has a broad operating pressure range; up to 20 psi (138 kPag) at 260_F (126_C). The IDT steam coils are especially suited to applications where sub--freezing air enters the unit.

Subbase provides a stable, raised platform and room for condensate drain trap connection for vertical floor--mounted units. Accessory is available unpainted or painted.

A

DIMENSIONS (cont.)

C14344

Fig. 4 -- 38AUQ16

A

40RUQ07---25

Split System Heat Pump Indoor Unit (Air---Handling Unit) With PuronR Refrigerant 60 Hz

Product Data

40RUQ 07 - 12

40RUQ 16 -25

C10887

Carrier’s versatile packaged heat pump air-handling units satisfy design requirements with:

S Multi--position design for horizontal or vertical installation without modification.

S Standard sloped drain pans and cleanable insulation treated with Environmental Protection Agency (EPA) registered antimicrobial agent improve indoor air quality.

S High-static design meets a wider range of applications than competitive packaged air handler lines.

S Economizer accessory provides ventilation air and “free” cooling.

S Cooling coils with mechanically bonded fins provide peak heat transfer.

S Hot water coil, steam coil, and electric heat accessories are available.

S Standard factory--installed thermo--static expansion valves (TXV) with removable power element on 40RUQ units.

S Die-formed galvanized steel casings provide durability and structural integrity. Optional paint is available.

FEATURES/BENEFITS

Easy-to-install and economical 40RU units provide reliable service.

The 40RUQ Series units with direct--expansion coils are the best choice for packaged heat pump air handlers. All models offer excellent fan performance, a unique combination of indoor air quality features, easy installation, and affordable prices. Their versatility and state--of--the--art features will provide economical performance now and in the future.

Indoor air quality features

The unique combination of features in the 40RUQ Series air handlers ensures that clean, fresh, conditioned air is delivered to the occupied space.

Cooling coils prevent the build--up of humidity in the room, even during part--load conditions.

Two--inch (51--mm) disposable filters remove dust and airborne particles from the occupied space.

Thermal insulation contains an immobilized anti--microbial agent to inhibit the growth of bacteria and fungi. The anti--microbial agent is registered with the U.S.

Environmental Protection Agency (EPA).

Pitched drain pan can be adjusted for a right--hand or left--hand connection to provide positive drainage and prevent standing condensate. Each unit contains two separate drain pans which are provided for either vertical or horizontal fan coil positions.

Accessory economizer can provide ventilation air to improve indoor air quality. When used with CO2 sensors, the economizer admits fresh outdoor air to replace stale, recirculated indoor air.

Economy

The 40RUQ Series packaged air handlers have low initial costs, and they continue to save money by providing reduced installation expense and energy--efficient performance.

Quick installation is ensured by the multi--position design.

Units can be installed in either the horizontal or vertical (upflow) configuration without modifications. All units have drain--pan connections on both sides, and pans can be pitched for right--hand or left hand operation with a simple adjustment.

Fan motors and contactors are pre--wired and TXVs are factory--installed on 40RUQ models.

High--efficiency, precision balanced fans minimize air turbulence, surging, and unbalanced operation, thereby cutting operating expenses.

Economizer accessory precisely controls the blend of outdoor air and room air to achieve comfort levels. When the outside air enthalpy is suitable, outside air dampers can fully open to provide “free” cooling.

Rugged dependability

Die--formed galvanized steel panels ensure structural integrity under all operating conditions. Mechanically bonded coil fins provide improved heat transfer.

Galvanized steel fan housings are securely mounted to a die--formed galvanized steel deck.

Coil flexibility

Model 40RUQ air handling units have galvanized steel casings; inlet and outlet connections are on the same end.

Direct expansion (DX) coils are designed for use with Puronr R--410A refrigerant and have copper tubes mechanically bonded to aluminum sine--wave fins.

Direct--expansion coils include matched, factory--installed thermostatic expansion valves (TXVs) with matching distributor nozzles.

Easier installation and service

The multi--position design and component layout allow for quick unit installation and operation. The DX coils have factory--installed TXVs with matching distributor nozzles. Units can be converted from horizontal to vertical operation by simply repositioning the unit.

Drain pan connections are duplicated on both sides of the unit. The filters, motor, drive, TXVs, and coil connections are easily accessed by removing a single side panel.

TABLE OF CONTENTS

PAGE

FEATURES AND BENEFITS 1

MODEL NUMBER NOMENCLATURE 3

PHYSICAL DATA 4

OPTIONS AND ACCESSORIES 5

DIMENSIONS 6

PERFORMANCE DATA 15

ELECTRICAL DATA 20

TYPICAL PIPING AND WIRING 30

TYPICAL CONTROL WIRING SCHEMATIC 32

APPLICATION DATA 33

GUIDE SPECIFICATIONS 36

R

MODEL NUMBER NOMENCLATURE

Model Type 40RU = Packaged Air Handling Unit with Puron® R-410A Refrigerant

Type of Coil Q = DX Coil for Heat Pump Duty

Refrigerant Options A = None

Nominal Tonnage 07 = 6 Ton 16 = 15 Ton 08 = 7.5 Ton 25 = 20 Ton 12 = 10 Ton

Fan Motor Speed Controller A = None - Standard T = 2 Speed Fan Controller (VFD) - Staged Air Volume (SAVTM)

Indoor Fan Motor Options - Belt Drive NOTE: See the following two tables for Indoor Fan Motor Options for Single Speed and 2-Speed Motors. Available motors are indicated by a checkmark.

4Example 0 R U Q A 1 2 A 1 A 6 - 0 A 0 A 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Packaging 0 = Standard

Future Use A = Standard

Cabinet Paint 0 = None 1 = Painted

Future Use A = Standard

Revision Number

- = Standard

Voltage* 1 = 575/3/60 3 = 208/230-1-60 (07 and 08 sizes only) 5 = 208/230/3/60 6 = 460/3/60Coil Options

A = Standard Aluminum Fin / Copper Tube

Future Use 0 = Standard

Position

Notes:

* All 40RUQ07 through 16 units with a “6” voltage designation are triple voltage; ie., 208/230/460-3-60.

Size 40RUQ16 is also triple voltage in the “6” configuration unless the High Static (Alternate) motor option is used that is discrete 460-3-60.

Units that require 2-Speed indoor fan motor must use dedicated voltage models listed. The VFD used is not multi voltage.

C160009

Single Speed Motors Position 10 Motor Description Voltage

Unit Size 07 08 12 16 25

1 Std Static, Std Efficient Motor / Std Drive All n n n n – 4 Std Static, High Efficient Motor / Std Drive All – – – – n

2 Std Static, Std Efficient Motor / Med Drive All n n n n – 5 Std Static, High Efficient Motor / Med Drive All – – – – n

3 High (Alternate) Static, Std Efficient Motor / High Drive

575---3---60 n n n – – 208/230---1---60 n n – – – 208/230---3---60 460---3---60 n n n – –

6 High (Alternate) Static, High Efficient Motor / High Drive 575---3---60 – – – n n

208/230---3---60 460---3---60 – – – n n

2---Speed Motors Position 10 Motor Description Voltage

Unit Size 07 08 12 16 25

Std Static, Std Efficient Motor / Std Drive All n n n n – Std Static, High Efficient Motor / Std Drive All – – – – n

Std Static, Std Efficient Motor / Med Drive All n n – n – All – – – – n

High (Alternate) Static, Std Efficient Motor / Med Drive 575---3---60 – – n – – 208/230---3---60 460---3---60 – – – – –

High (Alternate) Static, High Efficient Motor / Med Drive 575---3---60 – – – – – 208/230---3---60 460---3---60 – – n – –

High (Alternate) Static, Std Efficient Motor / High Drive 575---3---60 n n n – – 208/230---3---60 460---3---60 n n – – –

High (Alternate) Static, High Efficient Motor / High Drive 575---3---60 – – – n n

208/230---3---60 460---3---60 – – n – –

R

PHYSICAL DATA

UNIT 40RUQ* 07 07T 08 12 16 25

NOMINAL CAPACITY (Tons) 6 6 71/2 10 15 20

OPERATING WEIGHT (lb) Base Unit with TXV 381 381 385 427 713 720 Plenum 175 175 175 175 225 225

FANS

Qty...Diam. (in.) 1...15 1...15 1...15 1...15 2...15 2...15 Nominal Airflow (cfm) 2400 2400 3000 4000 6000 8000 Airflow Range (cfm) 1800---3000 1800---3000 2250---3750 3000---5000 4500---7500 6000---10000 Nominal Motor Hp (Standard Motor)* 208/230---1---60 1.3 1.3 2.4 — — — 208/230---3---60 and 460---3---60 2.4 2.4 2.4 2.4 3.7 5.0 575---3---60 1.0 1.0 2.0 2.0 3.0 5.0 Motor Speed (rpm) 208/230---1---60 1725 1725 1725 — — — 208/230---3---60 and 460---3---60 1725 1725 1725 1725 1725 1760 575---3---60 1725 1725 1725 1725 1725 1745

REFRIGERANT R---410A R---410A R---410A R---410A R---410A R---410A

Operating charge (lb) (approx per circuit){ 3.0 3.0 3.0 2.0/2.0 3.0/3.0 3.5/3.5

DIRECT---EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine---Wave Fins Max Working Pressure (psig) 650 650 650 650 650 650 Face Area (sq ft) 8.33 8.33 8.33 10.0 16.56 19.9 No. of Splits 1 1 1 2 2 2 No. of Circuits per Split 15 12 12 9 10 10 Split Type...Percentage --- --- --- Face...50/50 Face...50/50 Face...50/50 Rows...Fins/in. 3...15 4...15 4...15 4...15 4...15 4...15

PIPING CONNECTIONS,

Quantity...Size (in.)

DX Coil — Suction (ODF) 1...11/8 1...11/8 1...11/8 2...11/8 2...11/8 2...11/8 DX Coil — Liquid Refrigerant (ODF) 1...5/8 1...5/8 1...5/8 2...5/8 2...5/8 2...5/8 Steam Coil, In (MPT) 1...21/2 1...21/2 1...21/2 1...21/2 1...21/2 1...21/2 Steam Coil, Out (MPT) 1...11/2 1...11/2 1...11/2 1...11/2 1...11/2 1...11/2 Hot Water Coil, In (MPT) 1...11/2 1...11/2 1...11/2 1...11/2 1...2 1...2 Hot Water Coil, Out (MPT) 1...11/2 1...11/2 1...11/2 1...11/2 1...2 1...2 Condensate (PVC) 1...15/8 ODM / 11/4 IDF

FILTERS Throwaway — Factory Supplied

Quantity...Size (in.) 4...16 x 24 x 2 4...16 x 24 x 2 4...16 x 24 x 2 4...16 x 24 x 2 4...16 x 20 x 2 4...16 x 24 x 2

4...16 x 20 x 2 4...16 x 24 x 2

Access Location Either Side Either Side Either Side Either Side Either Side Either Side

STEAM COIL}

Max Working Pressure (psig at 260° F) 20 20 20 20 20 20 Total Face Area (sq ft) 6.67 6.67 6.67 6.67 13.33 13.33 Rows...Fins/in. 1...9 1...9 1...9 1...9 1...10 1...10

HOT WATER COIL}

Max Working Pressure (psig) 150 150 150 150 150 150 Total Face Area (sq ft) 6.67 6.67 6.67 6.67 13.33 13.33 Rows...Fins/in. 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 Water Volume (gal) 8.3 8.3 8.3 8.3 13.9 13.9 (ft3) 1.1 1.1 1.1 1.1 1.85 1.85

LEGEND

DX — Direct Expansion TXV— Thermostatic Expansion Valve { Units are shipped without refrigerant charge.

} Field installed accessory only.

* Refer to Alternate Fan Motor Data table for alternate motor data.

R

OPTIONS AND ACCESSORIES

ITEM OPTION* ACCESSORY{

Alternate Fan Motors X Alternate Drives X Staged Air Volume System X CO2 Sensors X Condensate Drain Trap X Discharge Plenum X Economizer Ultra LOW LEAK---FDD X Economizer Standard Leak X Electric Heat X Hot Water Heating Coils X Overhead Suspension Package X Prepainted Units X Programmable Thermostats X Return Air Grille X Steam Heating Coil X Subbase X Display Kit for SAV system with VFD X

* Factory--- installed option.

{ Field--- installed accessory

Factory--installed options Alternate fan motors and drives are available to provide the widest possible range of performance.

Prepainted steel units are available from the factory for applications that require painted units. Units are painted with American Sterling Gray color.

Staged Air Volume (SAV) system saves energy and installation time by utilizing a Variable Frequency Drive (VFD) to automatically adjust the indoor fan motor speed in sequence with the units cooling operation. Per ASHRAE

90.1 2010 standard section 6.4.3.10.b, during the first stage of cooling operation the VFD will adjust the fan motor to provide 2/3rd of the total cfm established for the unit. When a call for the second stage of cooling is required, the VFD will allow the total cfm for the unit established (100%).

During the heating mode the VFD will allow total design cfm (100%) operation and during the ventilation mode the VFD will allow operation to 2/3rd of total cfm.

Compared to single speed indoor fan motor systems, Carrier’s SAV system can save substantial energy, 25%+*, versus single speed indoor fan motor systems.

*Data based on .10 ($/kWh) in an office application utilizing Carrier’s HAP 4.6 simulation software program.

The VFD used in Carrier’s SAV system has soft start capabilities to slowly ramp up the speeds, thus eliminating any high inrush air volume during initial start--up. It also has internal over current protection for the fan motor and a field installed display kit that allows adjustment and in depth diagnostics of the VFD.

This SAV system is available on models with 2--stage cooling operation with electrical mechanical controls.

The SAV system is very flexible for initial fan performance set up and adjustment. The standard factory shipped VFD is pre--programmed to automatically stage the fan speed between the first and second stage of cooling. The unit fan performance static pressure and cfm can be easily adjusted using the traditional means of pulley adjustments. The other means to adjust the unit static and cfm performance is to utilize the field installed

Display Kit and adjust the frequency and voltage in the VFD to required performance requirements. In either case, once set up, the VFD will automatically adjust the speed between the cooling stage operations.

Field--installed accessories CO2 sensors can be used in conjunction with the economizer accessory to help meet indoor air quality requirements. The sensor signals the economizer to open when the CO2 level in the space exceeds the set point. A Carrier Comfort System programmable thermostat can be used to override the sensor if the outside--air temperature is too high or too low.

Condensate drain trap includes an overflow shutoff switch that can be wired to turn off the unit if the trap becomes plugged. Kit also includes a wire harness that can be connected to an alarm if desired. The transparent trap is designed for easy service and maintenance.

Discharge plenum directs the air discharge directly into the occupied space; integral horizontal and vertical louvers enable redirection of airflow. Accessory is available unpainted or painted. Field assembly is required (only applicable for vertical application).

Economizers -- temperature dry bulb controlled --

Ultra LOW LEAK -- EconoMi$er X with solid--state W7220 controller, gear--driven, modulating damper, spring return actuator. Supply and outdoor air sensors, and CO2 sensor compatible, for use in electro mechanical controls only.

Also includes return and outside air damper leakage that meets California Title 24 section 140.4 requirements.

Controller meets California Title 24 Section 120.2 Fault Detection and Diagnostic (FDD) requirements.

STANDARD -- EconoMi$er IV -- with gear driven damper blades and W7212 controller (Use ----HH----57AC--078 for enthalpy control).

Electric resistance heat coils have an open--wire design and are mounted in a rigid frame. Safety cutouts for high temperature conditions are standard. Terminal block for single--point power connection is included.

Two--row hot water coils have copper tubes mechanically bonded to aluminum plate fins and non--ferrous headers.

Overhead suspension package includes necessary brackets to support units in horizontal ceiling installations.

Return--air grille provides a protective barrier over the return--air opening and gives a finished appearance to units installed in the occupied space. Accessory is available unpainted or painted.

One--row steam coil has copper tubes and aluminum fins.

The Inner Distributing Tube (IDT) design provides uniform temperatures across the coil face. The steam coil has a broad operating pressure range; up to 20 psi (138 kPag) at 260_F (126_C). The IDT steam coils are especially suited to applications where sub--freezing air enters the unit.

Subbase provides a stable, raised platform and room for condensate drain trap connection for vertical floor--mounted units. Accessory is available unpainted or painted.

R

DIMENSIONS

C14200

40RUQ*07, 08, 12

R

DIMENSIONS (cont.)

C14201

40RUQ*16 & 25

R

Product Data

25HNB6

Infinityrr 2---Stage Heat Pump with Puronr Refrigerant 2 to 5 Nominal Tons

Carrier’s heat pumps with Puronr refrigerant provide a collection of features unmatched by any other family of equipment. The 25HNB6 has been designed utilizing Carrier’s Puron refrigerant.

The environmentally sound refrigerant allows consumers to make a responsible decision in the protection of the earth’s ozone layer.

This product has been designed and manufactured to meet Energy Starr criteria for energy efficiency when matched with appropriate coil components. Refer to the combination ratings in the Product Data for system combinations that meet Energy Starr guidelines.

NOTE: Ratings contained in this document are subject to change at any time. Always refer to the AHRI directory (www.ahridirectory.org) for the most up--to--date ratings information.

INDUSTRY LEADING

FEATURES / BENEFITS

Energy Efficiency

S 13.7 -- 17.2 SEER/11.2 -- 13.3 EER/8.0 -- 9.5 HSPF

S Microtube Technologyt refrigeration system S Indoor air quality accessories available

Sound S Sound level as low as 67 dBA S Quiet mount split post compressor grommets S Forward--swept condenser fan blade S Compressor sound hood S Laminated steel compressor mounting plate S 8 pole PSC ball bearing outdoor condenser fan motor

Comfort S System supports Infinity Controlt or standard 2--stage thermostat controls

Reliability S Puronr refrigerant -- environmentally sound, won’t deplete the ozone layer and low lifetime service cost.

S Front--seating service valves S 2--stage scroll compressor S Internal pressure relief valve S Internal thermal overload S High pressure switch S Loss of charge switch S Filter drier S Balanced refrigeration system for maximum reliability S Crankcase heater standard

Durability WeatherArmor Ultrat protection package:

S Solid, Durable sheet metal construction S Steel louver coil guard S Baked--on, complete outer coverage, powder paint

Controls and Diagnostics S Infinityt Control or Thermostat S 2 control wires to outdoor unit with Infinity Control (serial numbers 3112E and newer).

S Utility Interface Connection S Enhanced diagnostics capability with Infinityt Control

Applications S Long--line -- up to 250 feet (76.2 m) total equivalent length, up to 200 feet (60.96 m) condenser above evaporator, or up to 80 ft.

(24.38 m) evaporator above condenser (See Longline Guide for more information.)

S Low ambient cooling (down to 0_F / --17.8_C ) with approved low ambient accessory kits or complete Infinity system.

1 2 3 4 5 6 7 8 9 10 11 12 13 N N A A A/N N N N A/N A/N A/N N N

2 5 H N B 6 3 6 A 0 0 3 0

Product Series

Product Family Tier Major

Series SEER Cooling Capacity Variations Open Open Voltage Minor

Series

25 = HP H = RES HP N=

Infinity Series B = Puron 6=16 SEER 1,000 Btuh

(nominal) A = Standard 0=Not Defined

0=Not Defined 3=208/230---1 0, 1, 2...

the environmentally sound refrigerant

This product has been designed and manufactured to meet Energy Star criteria for energy efficiency when matched with appropriate coil components. However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should follow all manufacturing refrigerant charging and air flow instructions. Failure to confirm proper charge and air flow may reduce energy efficiency and shorten equipment life.

Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program For verification of certification for individual products, go to www.ahridirectory.org.

This product has been designed and manufactured to meet Energy Star criteria for energy efficiency when matched with appropriate coil components. However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should follow all manufacturing refrigerant charging and air flow instructions. Failure to confirm proper charge and air flow may reduce energy efficiency and shorten equipment life.

STANDARD FEATURES

FEATURES

Unit Size --- Voltage, Series

24---32 36---31 48---31 60---32

Puron Refrigerant X X X X

2 control wires to outdoor unit with Infinity Control (serial numbers 3112E and newer). X X X X

Maximum SEER Rating* 17.2 17.0 16.5 16.0

2---Stage Scroll Compressor X X X X

Louvered Coil Guard X X X X

Field Installed Filter Drier X X X X

Front Seating Service Valves X X X X

Internal Pressure Relief Valve X X X X

Long Line capability X X X X

Loss of Charge Switch X X X X

High Pressure Switch X X X X

Crankcase Heater X X X X

Low ambient cooling down to 0_F capability with Infinity Control or Approved Kits X X X X

Utility Interface Connections X X X X

Enhanced Diagnostics with Infinity Control X X X X

Sound Blanket X X X X

X = Standard

* With approved combinations

H N B

PHYSICAL DATA

UNIT SIZE SERIES 24---32 36---31 48---31 60---32

Operating Weight lb (kg) 275 (125) 296 (134) 328 (149) 350 (159) Shipping Weight lb (kg) 318 (144) 339 (154) 371 (168) 395 (179) Compressor Type Ultratechr Scroll REFRIGERANT Puronr (R---410A) Control TXV (Puron Hard Shutoff) Charge lb (kg) 13.07 (5.93) 13.70 (6.21) 13.73 (6.23) 14.78 (6.70)

Outdoor Htg Piston # 46 55 61 67 COND FAN Propeller Type, Direct Drive Air Discharge Vertical Air Qty (CFM) 3200 3200 4350 5000 Motor HP 1/12 1/12 1/4 1/4 Motor RPM 800 800 825 825

COND COIL

Face Area (Sq ft) 25.2 25.2 25.2 30.18 Fins per In. 20 20 20 20 Rows 2 2 2 2 Circuits 8 8 8 10

VALVE CONNECT. (In. ID) Vapor 3/4 7/8 7/8 7/8 Liquid 3/8

REFRIGERANT TUBES (In. OD) Rated Vapor* 3/4 7/8 1---1/8 1---1/8 Max Liquid Line 3/8

* Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset.

Note: See unit Installation Instruction for proper installation.

VAPOR LINE SIZING AND COOLING CAPACITY LOSS

Acceptable vapor line diameters provide adequate oil return to the compressor while avoiding excessive capacity loss. The suction line diameters shown in the chart below are acceptable for AC systems with Puron refrigerant:

Unit Nominal Size (Btuh)

Maximum Liquid Line Diameters (In. OD)

Vapor Line Diameters (In.) OD

Cooling Capacity Loss (%) Total Equivalent Line Length ft. (m)

Standard Application Long Line Application Requires Accessories

26---50 (7.9---15.2)

51---80 (15.5---24.4)

81---100 (24.7---30.5)

101---125 (30.8---38.1)

126---150 (38.4---45.7)

151---175 (46.0---50.3)

176---200 (53.6---60.0)

201---225 (61.3---68.6)

226---250 (68.9---76.2)

24,000 2---Stage HP with Puron

3/8 5/8 0 1 1 2 3 3 4 4 5

3/4 0 1 1 1 1 1 1 1 1

36,000 2---Stage HP with Puron

3/8

5/8 1 2 4 5 6 7 9 10 11

3/4 0 0 1 1 2 2 3 3 4

7/8 0 0 — — — — — — — 48,000 2---Stage HP with Puron

3/8

3/4 1 2 2 3 4 5 6 7 7

7/8 0 1 1 2 2 2 3 3 4

1---1/8 0 0 — — — — — — — 60,000 2---Stage HP with Puron

3/8

3/4 1 2 4 5 6 8 9 10 11

7/8 0 1 2 2 3 4 4 5 5

1---1/8 0 0 — — — — — — — Standard Length = 80 ft. (24.4 m) or less total equivalent length Applications in this area are long line. Accessories are required as shown recommended on Long Line Application Guidelines Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit.

— Applications in this area are not recommended due to insufficient oil return.

H N

REFRIGERANT PIPING LENGTH LIMITATIONS

Maximum Line Lengths:

The maximum allowable total equivalent length for heat pumps varies depending on the vertical separation. See the tables below for allowable lengths depending on whether the outdoor unit is on the same level, above or below the outdoor unit.

Maximum Line Lengths for Heat Pump Applications

MAXIMUM ACTUAL LENGTH

ft (m)

MAXIMUM EQUIVALENT LENGTH{

ft (m)

MAXIMUM VERTICAL SEPARA-

TION ft (m)

Units on equal level 200 (61) 250 (76.2) N/A Outdoor unit ABOVE indoor unit 200 (61) 250 (76.2) 200 (61)

Outdoor unit BELOW indoor unit See Table ’Maximum Total Equivalent Length: Outdoor Unit BELOW Indoor Unit’

{ Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.

Maximum Total Equivalent Length{ -- Outdoor Unit BELOW Indoor Unit

Size Liquid Line Diameter w/ TXV

HP with Puronr Refrigerant --- Maximum Total Equivalent Length{ Vertical Separation ft (m) Outdoor unit BELOW indoor unit;

0---20 (0 --- 6.1)

21---30 (6.4 --- 9.1)

31---40 (9.4 --- 12.2)

41---50 (12.5 --- 15.2)

51---60 (15.5 --- 18.3)

61---70 (18.6 --- 21.3)

71---80 (21.6 --- 24.4)

HP with Puron

3/8 250* 250* 250* 250* 250* 250* 250*

HP with Puron

3/8 250* 250* 250* 250* 250* 250* 250*

HP with Puron

3/8 250* 250* 250* 250* 230 160 --- ---

HP with Puron

3/8 250* 225* 190 150 110 --- --- --- ---

* Maximum actual length not to exceed 200 ft (61 m) { Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.

--- --- = outside acceptable range

LONG LINE APPLICATIONS

An application is considered Long Line when the refrigerant level in the system requires the use of accessories to maintain acceptable refrigerant management for systems reliability. Defining a system as long line depends on the liquid line diameter, actual length of the tubing, and vertical separation between the indoor and outdoor units.

For Heat Pump systems, the chart below shows when an application is considered Long Line. Beyond these lengths, long line accessories are required:

HP WITH PURONr REFRIGERANT LONG LINE DESCRIPTION ft (m) Beyond these lengths, long line accessories are required

Liquid Line Size Units On Same Level Outdoor Below Indoor Outdoor Above Indoor

3/8 80 (24.4) 20 (6.1) vertical or 80 (24.4) total 80 (24.4)

Note: See Long Line Guideline for details

H N

ACCESSORIES

KIT NUMBER KIT NAME 24---32 36---31 48---31 60---32

KHALS0401LLS SOLENOID VALVE X X X X

KHASS0606MPK* SNOW STAND X X X X

KSAHS2501AAA{ HARD START KIT X X

KSAHS2801AAA{ HARD START KIT X X

KSASF0101AAA SUPPORT FEET X X X X

KAAFT0101AAA FREEZE THERMOSTAT X X X X

KSALA0301410 LOW AMBIENT PRESSURE SWITCH X X X X

KHAIR0201AAA ISOLATION RELAY X X X X

x = Accessory S = Standard

* Available from RCD { Not backward compatible to previous series.

ACCESSORY CONTROLS

PART NO. DESCRIPTION

SYSTXCCITN01 Infinity Touch Control (non---Wi---Fi)

SYSTXCCITW01 Infinity Touch Control with Wi---Fi & Wireless Access Point

SYSTXCCUID01-V Infinity Control Deluxe 7-Day Programmable (Wall-mounted system control.)

SYSTXCCUIZ01-V Infinity Control Deluxe Zoning 7-Day Programmable (Wall-mounted control for a multi-zone system.)

SYSTXCC4ZC01 Infinity 4-Zone Damper Control Module (Wall-mounted control for a four-zone system.)

SYSTXCCSMS01 Infinity Smart Sensor (Optional wall control used to monitor temperature and/or fan control in an individual zone.)

SYSTXCCRRS01 Infinity Remote Room Sensor (Monitors temperature in an individual zone.)

SYSTXCCRCT01

or

SYSTXCCRWF01

Infinity System Access Module (Hardware for wireless access and control via internet.)

SYSTXCCNIM01 Infinity Network Interface Module (Connects Heat Recovery and Energy Recovery Ventilators on Non-zoning applications.)

SYSTXXXBPU01 Decorative Back Plate for Infinity Control (Decorative wall plate.)

H N

ACCESSORY USAGE GUIDELINE

Accessory

Required for Low Ambient

Cooling Applications Utilizing 2---Stage

Thermostat on 16 SEER Models Only

(Below 55° F / 12.8° C)

Required for Low Ambient

Cooling Applications Utilizing UI

(Below 55° F / 12.8° C)

Required for Long Line Applications*

Required for Sea Coast

Applications (within 2 miles/3.2 km)

Compressor Start Assist Capacitor and Relay No No No No

Crankcase Heater Yes (standard on some units)

Yes (standard on some units)

Yes (standard on some units) No

Evaporator Freeze Thermostat Yes (kit required) Standard with Infinity Control (no kit required)

No No

Isolation Relay Yes (kit required) Standard with Infinity Control (no kit required)

No No

Liquid Line Solenoid Valve No No No No

Low---Ambient Pressure Switch Yes (kit required) Standard with Infinity

Control (no kit required)

See Residential Piping and Long Line Guideline No

Puron Refrigerant Balance Port Hard Shutoff TXV

Yes (standard w/factory approved indoor unit)

Yes (standard w/factory approved indoor unit)

Yes (standard w/factory approved indoor unit)

Yes (standard w/factory approved indoor unit)

Support Feet Recommended Recommended No Recommended

* For tubing set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 20 ft. (6.10 m) vertical differential (total equivalent length), refer to the Residential Piping and Long Line Guideline

Accessory Description and Usage (Listed Alphabetically)

1. Compressor Start Assist -- Capacitor and Relay Start capacitor and relay gives a “hard” boost to compressor motor at each start up.

Usage Guideline:

Not required on this unit since compressor always starts unloaded.

Available if required by local codes.

2. Crankcase Heater An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart and minimizes the chance of liquid slugging.

Usage Guideline:

Required in low ambient cooling applications.

Required in long line applications.

3. Evaporator Freeze Thermostat An SPST temperature--actuated switch that stops unit operation when evaporator reaches freeze--up conditions.

Usage Guideline:

Required when low ambient kit has been added.

4. Isolation Relay An SPDT relay which switches the low ambient controller out of the outdoor fan motor circuit when the heat pump switches to heating mode.

Usage Guideline:

Required in all heat pumps where low ambient kit has been added.

5. Low--Ambient Pressure Switch A long life pressure switch which is mounted to outdoor unit service valve. It is designed to cycle the outdoor fan motor in order to maintain head pressure within normal operating limits. The control will maintain working head pressure at low--ambient temperatures down to 0_F (--17.8_C) when properly installed.

Usage Guideline:

A Low--Ambient Pressure Switch must be used when cooling operation is used at outdoor temperatures below 55_F (12.8_C).

Suggested in all commercial applications.

6. Liquid--Line Solenoid Valve (LLS) An electrically operated shutoff valve which stops and starts refrigerant liquid flow in response to compressor operation. It is to be installed at the outdoor unit to control refrigerant off cycle migration in the heating mode.

Usage Guideline:

An LLS is required in all long line heat pump applications to control refrigerant off cycle migration in the heating mode. See Long Line Guideline.

Suggested for all commercial applications.

7.