Install Stairwell Signage, Camp Kinser Request for Information Q & A’s

1. How many samples are required to be taken for the asbestos testing?

- Please refer to US EPA, 40 CFR 763.86, for asbestos bulk sampling. The Contractor may perform additional sample on his own discretion.

2. In reference to ANSI A117.1-2009 Chapter 703.4 regarding Braille. Will all the stairwell signage be installed with Braille?

- All signage’s shall be provided with braille.

3. The Architectural scope of work 5.1.1 G, Signage should comply with NFPA 101 section 7.10.8.1. As per NFPA 101 section 7.10.8.1, Special sign should be illuminated and in accordance with NFPA 101 sections 7.10.5 and 7.10.6.3; wherein according to those two sections, sign should be illuminated and permitted to flash upon activation fire alarm system and should have level of illumination of 5 ft. candles. Are these regulations on NFPA 101 be incorporated on these project? will the sign be connected with the Fire alarm system and have an illumination of 5-ft candles?

- Illumination is not required. Please see ANSI A117.1 para 703.2.10 Finish and Contrast for character and background finish.