Q A as of 12 June 2020.pdf

PDF 18 KB Posted

Attached to
NETWORK CABLE INSTALLATION AT YOKOTA AIR BASE Federal contract opportunity
Solicitation number
FA5209-20-Q-0040
Issued by
Department of the Air Force Pacific Air Forces

View the file

Other files for this federal contract opportunity

Other files attached to NETWORK CABLE INSTALLATION AT YOKOTA AIR BASE, newest first.
File Type Posted
Q A as of 22 June 2020.pdf PDF
Q A as of 9 June 2020.pdf PDF
1 Business w US Government.pdf PDF
6 Atch 3 PP Peformance Reference List.doc DOC document
5 Atch 2 Price List.pdf PDF
3 Solicitation - FA520920Q0040.pdf PDF
7 Atch 4 Reference Q A.pdf PDF
4 Atch 1 PWS.pdf PDF
2 Notice to Offeror signed.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions & Answers Solicitation No. FA520920Q0040

Network Cable Installation at Yokota Air Base As of 12 June 2020

Question 1: Regarding Communication Rack in Task 2, would you be able to provide us with the size, material, whether lock system is required, and what to be installed inside Rack (i.e. breaker box, LAN cables, POE Hub, etc.)?

Answer 1: • Horizontal and vertical wire management should be installed in the rack.

• The communication rack should be a standard 42U 19” rack with lockable doors.

• The rack also needs to be grounded and anchored down.

The costing is strictly for the Contractor to purchase and install the rack.

Question 2: For CAT6, with shielded or no shield?

Answer 2: Not shielded.

Question 3: For wire management panel, would you prefer 1U or 2U?

Answer 3: 2U

Question 4: For ladder rack, is it okay to use 11.8”W (little oversized) that we can get in japan?

Answer 4: Yes.

Question 5: Please explain to us what a “ground ladder rack” is.

Answer 5: Each section of ladder rack should be grounded to the next and the last section should be grounded to facility or rack ground.

Question 6: From power to communication rack, how long should we assume?

Answer 6: Assume 300 feet.

File details come from the government source that posted it. Updated .