BASE MAP

RICHARDSON HWY

1200 600 0 1200 2400 3600

SCALE IN FEET

PROJECT

LOCATION

BLDG 1346

F-35 TEMPORARY SOUTH GATE

ACCESS FOR CONSTRUCTION

H

AU

L R O

U

TE

1 View Name 1/8" = 1'-0"A101

Room name

LEGEND

NAME

NUMBER

SHEET LOCATION

SCALE

TRUE NORTH

GRID LINE

ROOM NAME

ROOM NUMBER

PLAN NORTH

SEE DISCIPLINES FOR SPECIFIC SYMBOLS

---SHEET LOCATION

DETAIL NUMBER

---SHEET LOCATION

DETAIL NUMBER

CODE SUMMARY

GOVERNING CODES:

2015 INTERNATIONAL BUILDING CODE - IBC

2015 INTERNATIONAL FIRE CODE - IFC

2015 NFPA 101 - LIFE SAFETY CODE

2017 NFPA 70 - NATIONAL ELECTRICAL CODE - NEC

UFC 3-600-01 FIRE PROTECTION ENGINEERING FOR FACILITIES (CHANGE 1, 28 NOV 2016)

UFC 1-200-01 GENERAL BUILDING REQUIREMENTS (20 JUN 2016)

AUTHORITY HAVING JURISDICTION

EIELSON AFB

LIQUID PENETRATE

ROOM 110:

FLUORESCENT PENETRANTS AND HYDROPHILIC EMULSIFIER ARE CALCULATED AS

COMBUSTIBLE LIQUIDS, CLASS IIIB PER IBC 2015. QUANTITIES IN OPEN USE IN FACILITY

DO NOT EXCEED TABLE 307.1(1). ROOM DOES NOT REQUIRE FIRE SEPARATION.

OCCUPANCY

NO CHANGE IN OCCUPANCY

BUILDING SHALL BE OCCUPIED DURING CONSTRUCTION

PROJECT SITE

FLIG

H

T LIN

E AVE

IN

N

ER

LO

O P

PROJECT

LOCATION

BLDG 1346

D ate

P roj ec t N o.

A r chit ect s

E n gin eer s

S u rve yor s

60 1 C olle ge R oa d F airb ank s A K 9 970 1 90 7.45 2.12 41 de sign alas ka.c om

0 4 J A N

2 01 9

F TQ

W

18 -0 20 3

A E

C C

S ht.

O f

3 54 th C iv il E n gi ne e r S q ua dr on

E ie lson A

FB, Alaska

P roj ec t E ng ine er

C hie f E ng in ee r D raw n By

D es ign ed B y

R efe re nc e

N o.

R ev

D es cri ptio n

B y D ate

E N

G

IN

E M A

IN

TE

N A

N C

E FA

C

IL IT Y

B

LD

G

1 3 46

1/3/2019 5:04:41 PM

GENERAL IN FORMATI ON

G

ARCHITECTURAL

A001 ARCHITECTURAL INFORMATION

A100 OVERALL DEMOLITION PLAN

A200 OVERALL RENOVATION PLAN

A500 EXTERIOR DETAILS

A600 REFLECTED CEILING PLAN

A800 INTERIOR ASSEMBLY TYPES AND DETAILS

A900 ROOM, MATERIAL, AND DOOR SCHEDULES

GENERAL

G001 GENERAL INFORMATION

ELECTRICAL

E001 ELECTRICAL LEGEND AND SCHEDULES

E002 ELECTRICAL DEMOLITION PLANS

E003 ELECTRICAL PLANS

DRAWING INDEX

REF. # SHEET TITLE

ENGINE MAINTENANCE FACILITY BLDG 1346

PROJECT NO. FTQW 18-0203

FIRE PROTECTION

F100 FIRE PROTECTION FIRST FLOOR PLAN

F101 FIRE PROTECTION PLANS AND DETAILS

F102 FIRE SUPPRESSION SCHEMATIC

MECHANICAL

M001 ABBREVIATIONS AND SCHEDULES

M101 DEMOLITION PLANS

M201 MECHANICAL PLANS

M202 MECHANICAL DETAILS

CONTRACTOR LAYDOWN AREA TO BE COORDINATED WITH GOVERNMENT AFTER AWARD.

LAYDOWN AREA

CONCRETE

EARTH

GYPSUM

RIGID INSULATION

MASONRY CONCRETE

PLYWOOD

MATERIAL LEGEND

BATT INSULATION

MASONRY BRICK

EXISTING

CONSTRUCTION

TEMPORARY

CONSTRUCTION

RIGID MINERAL FIBER

BATT/BLOWN INSULATION

ARCHITECTURAL SYMBOL LEGEND

150 SF

Room Name

DETAIL NAME

DETAIL NUMBER

SHEET LOCATION

DETAIL SCALE

TRUE NORTH

GRID LINE

ROOM NAME

ROOM NUMBER

PLAN NORTH

DETAIL NUMBER

SHEET LOCATION

SIMILAR

REVISION

SPOT ELEVATION

SEE OTHER DISCIPLINES FOR ADDITIONAL SYMBOLS

KEYED NOTE

DOOR TAG

A100

A100

EXTERIOR ELEVATION

SHEET LOCATION

DETAIL NUMBER

INTERIOR ELEVATION

SHEET LOCATION

DETAIL NUMBER

DETAIL NUMBER 4

1t

BUILDING SECTION

DETAIL NUMBER

SHEET LOCATION

SIMILAR

WALL SECTION

WINDOW TYPE

ROOM AREA

1/8" = 1'-0"A101 View Name

1/4" / 1'-0"

.SPOT SLOPE

101ROOM NUMBER

A

A101

SIM

A101

SIM

101A

SEE OTHER DISCIPLINES FOR ADDITIONAL ABBREVIATIONS.

SOME ABBREVIATIONS MAY NOT BE USED IN THIS PROJECT.

(E) EXISTING

ACT ACOUSTICAL CEILING TILE

ADA AMERICAN DISABILITIES ACT

AFF ABOVE FINISHED FLOOR

CFCI CONTRACTOR FURNISHED CONTRACTOR INSTALLED

CFOI CONTRACTOR FURNISHED OWNER INSTALLED

CMU CONCRETE MASONRY UNIT

CONC CONCRETE

ELEC ELECTRICAL

FRP FIBERGLASS REINFORCED PANEL

GYP GYPSUM BOARD

HM HOLLOW METAL

IBC INTERNATIONAL BUILDING CODE

INHM INSULATED HOLLOW METAL

INSUL INSULATION

ITSP INSULATED TRANSLUCENT SANDWICH PANEL

MAX MAXIMUM

MECH MECHANICAL

MFSD MANUFACTURER'S STANDARD

MIN MINIMUM

NIC NOT IN CONTRACT

OC ON CENTER

OD OVERFLOW DRAIN

OFOI OWNER FURNISHED OWNER INSTALLED

OFCI OWNER FURNISHED CONTRACTOR INSTALLED

OSB ORIENTED STRAND BOARD

PLAM PLASTIC LAMINATES

PLY PLYWOOD

RD ROOF DRAIN

SIP STRUCTURAL INSULATED PANEL

SPEC SPECIFICATION

STC SOUND TRANSMISSION CLASS

STRUC STRUCTURAL

SV STAIN/VARNISH

TYP TYPICAL

UL UNDERWRITERS LABORATORY

VCT VINYL COMPOSITION TILE

VTR VENT THROUGH ROOF

ARCHITECTURAL STANDARD ABBREVIATIONS

ARCHITECTURAL PROJECT SPECIFIC ABBREVIATIONS

NA NOT APPLICABLE

WX-3A

WALL ASSEMBLY CATEGORY - FUNCTION

WALL FRAMING MEMBER SIZE

WALL ASSEMBLY MODIFIER

WALL ASSEMBLY CATEGORY - FUNCTION

PROJECTS MAY NOT INCLUDE ALL ASSEMBLY CATEGORIES.

WF WALL - FOUNDATION

WR WALL - RETAINING

WX WALL - EXTERIOR

WALL FRAMING MEMBER SIZE

ASSEMBLIES MAY NOT INCLUDE A FRAMING MEMBER SIZE.

FURRING AND METAL STUDS

0 7/8" FURRING CHANNELS

1 1 5/8" METAL STUDS

2 2 1/2" METAL STUDS

3 3 5/8" METAL STUDS

4 4" METAL STUDS

6 6" METAL STUDS

8 8" METAL STUDS

SHAFT WALLS

2 2 1/2" METAL CH STUDS

4 4" METAL CH STUDS

6 4" METAL CH STUDS

WOOD STUDS

4 2x4 WOOD STUDS 6 2x6 WOOD STUDS 8 2x8 WOOD STUDS

CMU

2 1 5/8" CMU

4 3 5/8" CMU

6 5 5/8" CMU

8 7 5/8" CMU

10 9 5/8" CMU

12 11 5/8" CMU

CONCRETE

# CONCRETE THICKNESS

WALL ASSEMBLY MODIFIER

LETTERS A THRU Z REPRESENT DESCRIPTIONS OF ASSEMBLY

TYPES. THE BELOW ARE COMMONLY USED EXAMPLES.

A TYPICAL

F FIRE RATED

ASSEMBLY TAG LEGEND - WALL EXTERIOR

C-A1

CEILING ASSEMBLY CATEGORY

CEILING ASSEMBLY MODIFIER

CEILING ASSEMBLY CATEGORY

C CEILING

CEILING MATERIAL DESIGNATION

LETTERS A THRU Z REPRESENT DESCRIPTIONS OF

ASSEMBLY TYPES. THE BELOW ARE COMMONLY USED

EXAMPLES.

A ACOUSTIC CEILING TILE

G GYPSUM BOARD

S SPECIALTY MATERIAL

CEILING ASSEMBLY MODIFIER

NUMBERS REPRESENT DESCRIPTIONS OF ASSEMBLY

TYPES. THE BELOW ARE COMMONLY USED EXAMPLES.

1 TYPICAL

ASSEMBLY TAG LEGEND - CEILING

CEILING MATERIAL DESIGNATION

F-W1

FLOOR ASSEMBLY CATEGORY - FUNCTION

FLOOR ASSEMBLY MODIFIER

FLOOR ASSEMBLY CATEGORY - FUNCTION

FLOORS ON GRADE OR THOSE COMPRISING THE EXTERIOR

ENVELOPE OF THE BUILDING ARE CONSIDERED EXTERIOR.

F FLOOR - INTERIOR

FX FLOOR - EXTERIOR

FLOOR MATERIAL DESIGNATION

LETTERS A THRU Z REPRESENT DESCRIPTIONS OF

ASSEMBLY TYPES. THE BELOW ARE COMMONLY USED

EXAMPLES.

C CONCRETE

W WOOD

FLOOR ASSEMBLY MODIFIER

NUMBERS REPRESENT DESCRIPTIONS OF ASSEMBLY

TYPES. THE BELOW ARE COMMONLY USED EXAMPLES.

1 TYPICAL

ASSEMBLY TAG LEGEND - FLOOR

FLOOR MATERIAL DESIGNATION

W01-3A

WALL ASSEMBLY CATEGORY - FUNCTION

WALL SHEATHING DESIGNATION

WALL FRAMING MEMBER SIZE

WALL ASSEMBLY MODIFIER

WALL ASSEMBLY CATEGORY - FUNCTION

PROJECTS MAY NOT INCLUDE ALL ASSEMBLY CATEGORIES.

W WALL - INTERIOR

WALL SHEATHING DESIGNATION

ASSEMBLIES MAY NOT INCLUDE A SHEATHING DESIGNATION.

THE SHEATHING DESIGNATION REFERS TO THE NUMBER OF

SHEATHING LAYERS ON EACH SIDE OF THE FRAMING MEMBER.

00 FIRST SIDE (0 LAYERS) + SECOND SIDE (0 LAYERS)

01 FIRST SIDE (0 LAYERS) + SECOND SIDE (1 LAYERS)

02 FIRST SIDE (0 LAYERS) + SECOND SIDE (2 LAYERS)

03 FIRST SIDE (0 LAYERS) + SECOND SIDE (3 LAYERS)

04 FIRST SIDE (0 LAYERS) + SECOND SIDE (4 LAYERS)

11 FIRST SIDE (1 LAYERS) + SECOND SIDE (1 LAYERS)

12 FIRST SIDE (1 LAYERS) + SECOND SIDE (2 LAYERS)

13 FIRST SIDE (1 LAYERS) + SECOND SIDE (3 LAYERS)

14 FIRST SIDE (1 LAYERS) + SECOND SIDE (4 LAYERS)

22 FIRST SIDE (2 LAYERS) + SECOND SIDE (2 LAYERS)

23 FIRST SIDE (2 LAYERS) + SECOND SIDE (3 LAYERS)

24 FIRST SIDE (2 LAYERS) + SECOND SIDE (4 LAYERS)

33 FIRST SIDE (3 LAYERS) + SECOND SIDE (3 LAYERS)

34 FIRST SIDE (3 LAYERS) + SECOND SIDE (4 LAYERS)

44 FIRST SIDE (4 LAYERS) + SECOND SIDE (4 LAYERS)

WALL FRAMING MEMBER SIZE

FURRING AND METAL STUDS

0 7/8" FURRING CHANNELS

1 1 5/8" METAL STUDS

2 2 1/2" METAL STUDS

3 3 5/8" METAL STUDS

4 4" METAL STUDS

6 6" METAL STUDS

8 8" METAL STUDS

SHAFT WALLS

2 2 1/2" METAL CH STUDS

4 4" METAL CH STUDS

6 4" METAL CH STUDS

WOOD STUDS

4 2x4 WOOD STUDS 6 2x6 WOOD STUDS 8 2x8 WOOD STUDS

CMU

2 1 5/8" CMU

4 3 5/8" CMU

6 5 5/8" CMU

8 7 5/8" CMU

10 9 5/8" CMU

12 11 5/8" CMU

CONCRETE

# CONCRETE THICKNESS

WALL ASSEMBLY MODIFIER

LETTERS A THRU Z REPRESENT DESCRIPTIONS OF ASSEMBLY

TYPES. THE BELOW ARE COMMONLY USED EXAMPLES.

A TYPICAL

F FIRE RATED

G FIRE AND SOUND RATED

H FIRE AND SOUND RATED WITH TILE

K TILE

L TILE AND SOUND RATED

P PLYWOOD

S SOUND RATED

W WOOD STUD

X WOOD STUD, FIRE RATED

Y WOOD STUD, FIRE AND SOUND RATED

Z WOOD STUD, SOUND RATED

LETTERS AA THRU ZZ REPRESENT DESCRIPTIONS OF

ASSEMBLY TYPES FOR CHASE WALLS. THE BELOW ARE

COMMONLY USED EXAMPLES.

FF FIRE RATED

GG FIRE AND SOUND RATED

HH FIRE AND SOUND RATED WITH TILE

LL TILE AND SOUND RATED

SS SOUND RATED

XX WOOD STUD, FIRE RATED

YY WOOD STUD, FIRE AND SOUND RATED

ZZ WOOD STUD, SOUND RATED

ASSEMBLY TAG LEGEND - WALL INTERIOR

A.

B.

C.

D.

E.

F.

G.

H.

I.

SEE G1 SHEETS FOR GENERAL CODE ANALYSIS.

COORDINATE ARCHITECTURAL WORK WITH CIVIL,

STRUCTURAL, MECHANICAL, ELECTRICAL, AND OTHER

DISCIPLINES.

SEE STRUCTURAL FOR SPECIFIC INFORMATION

REGARDING LOAD BEARING MEMBERS, MECHANICAL

FASTENERS, AND MASTIC ADHESION.

FIELD VERIFY DIMENSIONS SHOWN TO EXISTING

CONSTRUCTION. NOTIFY ARCHITECT WHERE

DISCREPANCIES AFFECT DESIGN.

DIMENSIONS AT EXISTING CONSTRUCTION ARE

MEASURED FROM FACE OF EXISTING FINISH UNLESS

NOTED OTHERWISE.

DIMENSIONS AT NEW CONSTRUCTION ARE MEASURED

FROM FACE OF FRAMING UNLESS NOTED OTHERWISE.

DIMENSIONS INDICATED AS 'CLEAR' REQUIRE CLEARANCE

MEASURED TO FINISHED FACES.

FURNITURE IS SHOWN FOR COORDINATION PURPOSES

ONLY. FURNITURE IS OWNER FURNISHED AND OWNER

INSTALLED UNLESS NOTED OTHERWISE.

PATCH, REPAIR, AND REFINISH EXISTING SURFACES TO

REMAIN, AFFECTED BY WORK.

ARCHITECTURAL NOTES

THIS REFERENCE IS INTENDED TO ASSIST WITH THE

LOCATION OF INFORMATION IN A TYPICAL PROJECT. THIS

PROJECT MAY VARY FROM THE REPRESENTATION BELOW.

SEE THE SHEET INDEX FOR SPECIFIC SHEET SEQUENCE.

A0 SHEETS ARCHITECTURAL INFORMATION

A1 SHEETS ARCHITECTURAL DEMOLITION

A2 SHEETS FLOOR AND ROOF PLANS

A3 SHEETS EXTERIOR ELEVATIONS

A4 SHEETS SECTIONS AND VERTICAL CIRCULATION

A5 SHEETS EXTERIOR DETAILS

A6 SHEETS INTERIOR PLANS

A7 SHEETS INTERIOR ELEVATIONS

A8 SHEETS INTERIOR DETAILS

A9 SHEETS SCHEDULES

ARCHITECTURAL SHEET SEQUENCE AKAF AL

TS

TA

E O

49 TH

S

JAMES D. BARTLETT

No. A10413

D E S I G N

A L

A S

K A

REGISTERED PROFESSIONAL ARCHITE

CT

D ate

P roj ec t N o.

A r chit ect s

E n gin eer s

S u rve yor s

60 1 C olle ge R oa d F airb ank s A K 9 970 1 90 7.45 2.12 41 de sign alas ka.c om

0 4 J A N

2 01 9

F TQ

W

18 -0 20 3

A E

C C

S ht.

O f

3 54 th C iv il E n gi ne e r S q ua dr on

E ie lson A

FB, Alaska

P roj ec t E ng ine er

C hie f E ng in ee r D raw n By

D es ign ed B y

R efe re nc e

N o.

R ev

D es cri ptio n

B y D ate

E N

G

IN

E M A

IN

TE

N A

N C

E FA

C

IL IT Y

B

LD

G

1 3 46

04-JAN-2019

1/2/2019 2:43:38 PM

JB

ARCHI TECTURAL I N FORMAT ION

A

J B

CHEMICAL

STORAGE

LIQUID

PENETRANT

BEARING

CLEANING

WASH

RACK

CKT

ROOM

OIL

ANALYSIS

ROOM

XRAY

ROOM

DARKROOM

XRAY

VAULT

TRAINING ROOM

1 2

STORAGE

MECHANICAL

CONTRACTOR WORK AREA

9' -9

11'-9 5/8"

SIM

CONTRACTOR

WORK AREA

'-0

27'-0"

'-5

A.

B.

C.

D.

PROVIDE DEMOLITION REQUIRED TO ACCOMMODATE NEW

WORK.

SEE ELECTRICAL AND MECHANICAL DOCUMENTS FOR

ADDITIONAL DEMOLITION REQUIREMENTS.

EXISTING STRUCTURAL SYSTEMS INCLUDING COLUMNS,

BEAMS, AND STRUCTURAL WALLS TO REMAIN.

GOVERNMENT TO REMOVE EQUIPMENT PRIOR TO START OF

WORK.

DEMOLITION NOTES

DEMOLITION LEGEND

EXISTING CONSTRUCTION

EXISTING WALL TO REMAIN

DEMOLISH DOOR, WALL TO REMAIN

DEMOLISH WALL AND DOOR

COMPUTER

ROOM

SECTION

OFFICE

BREAK

ROOM

EQUIPMENT

PLATFORM

KEYNOTES

REMOVE EXISTING WALL GYPSUM BOARD AT WALLS AS

REQUIRED TO ACCOMMODATE CEILING WORK.

REMOVE GYPSUM BOARD LID.

REMOVE GYPSUM BOARD SUSPENDED CEILING. REMOVE

MECHANICAL AND ELECTRICAL CEILING MOUNTED ITEMS

AND SALVAGE FOR REINSTALLATION. PROVIDE

TEMPORARY SUPPORT FOR ITEMS THAT ARE REQUIRED

TO REMAIN.

REMOVE LEAD LINED SLIDING DOOR, FRAME AND

HARDWARE. SALVAGE DOOR MONITORING SYSTEM FOR

REINSTALLATION.

CONTRACTOR SHALL MAINTAIN ACCESS TO ROOM. ROOM

SHALL BE IN USE FOR DURATION OF CONSTRUCTION.

EXISTING DOOR AND FRAME TO REMAIN. REMOVE FIRE

RATING PLATES FROM DOOR AND FRAME.

MODIFY WALL AS REQUIRED TO ACCOMMODATE WORK.

PREPARE EXISTING GYPSUM CEILING TO RECEIVE NEW

FINISH AS SCHEDULED.

PROVIDE TEMPORARY POLYETHYLENE DUST AND DEBRIS

BARRIER TO 10'-0" AFF. BARRIER CONSTRUCTION TO

ALLOW PASSAGE FOR SIX PASSENGER TRUCK AND

ENGINE ON A TRAILER. REMOVE AT COMPLETION OF

WORK.

REMOVE DOOR AND FRAME (LEAD LINED).

REMOVE EXISTING CONCRETE SLAB. SEE 5/A800 FOR

EXCAVATION AND REPLACEMENT SLAB DETAILS.

MAINTAIN DRIVE LANE TO ALLOW PASSAGE FOR SIX

PASSENGER TRUCK AND ENGINE ON A TRAILER.

AKAF AL

TS

TA

E O

49 TH

S

JAMES D. BARTLETT

No. A10413

D E S I G N

A L

A S

K A

REGISTERED PROFESSIONAL ARCHITE

CT

D ate

P roj ec t N o.

A r chit ect s

E n gin eer s

S u rve yor s

60 1 C olle ge R oa d F airb ank s A K 9 970 1 90 7.45 2.12 41 de sign alas ka.c om

0 4 J A N

2 01 9

F TQ

W

18 -0 20 3

A E

C C

S ht.

O f

3 54 th C iv il E n gi ne e r S q ua dr on

E ie lson A

FB, Alaska

P roj ec t E ng ine er

C hie f E ng in ee r D raw n By

D es ign ed B y

R efe re nc e

N o.

R ev

D es cri ptio n

B y D ate

E N

G

IN

E M A

IN

TE

N A

N C

E FA

C

IL IT Y

B

LD

G

1 3 46

04-JAN-2019

1/2/2019 2:43:41 PM

JB

OVERAL L DEMOL IT ION PL AN

A

LSM

1/8" = 1'-0"A100

1 DEMOLITION PLAN - 1ST FLOOR

1/8" = 1'-0"A100

2 DEMOLITION PLAN - 2ND FLOOR

KEYPLAN

XRAY

VAULT

CHEMICAL

STORAGE

LIQUID

PENETRANT

BEARING

CLEANING

CKT

ROOM

21 DARK

ROOM

OIL

ANALYSIS

ROOM

WASH

RACK

MECHANICAL

TRAINING

ROOM

25A

16'-0"

'-4

/8

XRAY

ROOM

STORAGE

FIRE

PUMP

W11-6F

9' -1

1/

4"

12'-4 1/4"

119A

9 23A

A500

8'-0"

5' -0

W11-6F

A800

A800

SIM

CONTRACTOR

WORK AREA

W11-6A

A200

CONTRACTOR WORK AREA

SIMW11-6A

SECTION

CHIEF

OFFICE

BREAK

ROOM

EQUIPMENT

PLATFORM

COMPUTER

ROOM

KEYNOTES

PROVIDE LEAD LINED GYPSUM BOARD AND LEAD LINED

WRAP AT WALL AS REQUIRED TO PROVIDE CONTINUOUS

BARRIER FROM FLOOR TO CEILING. SEE 1/A800 FOR WALL

TO CEILING JOINT DETAIL.

PROVIDE 8 LB, 1/8" LEAD SHIELDING WITH ALL

PENETRATIONS, DOOR JAMBS, AND THRESHOLDS/ SWEEPS

SHIELDED TO THE SAME LEVEL. THE LEAD OVERLAP MUST

BE IN THE SAME PLANE AS THE SHIELDING IN THE DOOR.

SEE A800.

PROVIDE 8 LB, 1/8" LEAD LINED GYPSUM BOARD WITH ALL

PENETRATIONS AND OVERLAP SHIELDED TO THE SAME

LEVEL STARTING AT 4'-0" ABOVE FLOOR LEVEL TO THE

CEILING. SEE 1/A800 FOR WALL TO CEILING JOINT DETAIL.

REINSTALL SALVAGED MECHANICAL AND ELECTRICAL

CEILING MOUNTED ITEMS.

PATCH WALL AT AREA OF DESTRUCTIVE TESTING, ± 9'-0"

AFF.

EXISTING HAND/GUARD RAIL TO REMAIN.

CONCRETE LANDING.

PROVIDE WORDS 'NO STORAGE ABOVE' HELVETICA FONT 4"

HEIGHT MINIMUM AT 10'-0" AFF.

PROVIDE DOOR AND FRAME. THIS DOOR WILL REQUIRE 3

LB, 3/32" LEAD INSIDE OF THE DOOR AND INSIDE OF THE

DOOR JAMB WITH OVERLAP BETWEEN THE DOOR AND THE

JAMB, SEE A800.

DUST AND DEBRIS BARRIER, SEE A100.

PROVIDE 2 LB, 1/32" LEAD SHIELDING AT ALL

PENETRATIONS AND OVERLAP SHIELDED TO THE SAME

LEVEL. AT THE UPPER PORTION OF THIS WALL, THE 8 LB,

1/8" LEAD MUST INTEGRATE AND OVERLAP WITH THE 1/32"

LEAD DOWN 1'-0" FROM THE CEILING. SEE 1/A800 FOR WALL

TO CEILING JOINT DETAIL.

MAINTAIN DRIVE LANE. SEE A100.

LEGEND

EXISTING CONSTRUCTION

1-HOUR FIRE RATED

RENOVATION NOTES

1. SEE A800 FOR SEALING PENETRATIONS THROUGH LEAD-

LINED GYPSUM BOARD.

KEEP AREA CLEAR

4" 4"

2"

BLACK

CAUTION YELLOW

HELVETICA FONT

AKAF AL

TS

TA

E O

49 TH

S

JAMES D. BARTLETT

No. A10413

D E S I G N

A L

A S

K A

REGISTERED PROFESSIONAL ARCHITE

CT

D ate

P roj ec t N o.

A r chit ect s

E n gin eer s

S u rve yor s

60 1 C olle ge R oa d F airb ank s A K 9 970 1 90 7.45 2.12 41 de sign alas ka.c om

0 4 J A N

2 01 9

F TQ

W

18 -0 20 3

A E

C C

S ht.

O f

3 54 th C iv il E n gi ne e r S q ua dr on

E ie lson A

FB, Alaska

P roj ec t E ng ine er

C hie f E ng in ee r D raw n By

D es ign ed B y

R efe re nc e

N o.

R ev

D es cri ptio n

B y D ate

E N

G

IN

E M A

IN

TE

N A

N C

E FA

C

IL IT Y

B

LD

G

1 3 46

04-JAN-2019

1/10/2019 9:06:50 AM

JB

OVERAL L RENOVAT ION P L AN

A

LSM

1/8" = 1'-0"A200

1 OVERALL PLAN - 1ST FLOOR

1/8" = 1'-0"A200

2 OVERALL PLAN - 2ND FLOOR

KEYPLAN

1/2" = 1'-0"A200 REFERENCE: 1/ A200

3 INTERIOR PLAN DETAIL - CLEAR AREA WARNING

A.

B.

C.

D.

E.

F.

G.

1 - TYPICAL

ASSEMBLIES ARE DIAGRAMS ONLY, DO NOT SCALE.

ASSEMBLIES ARE INTENDED TO DESCRIBE MATERIALS AND

THEIR RELATIONSHIP WITHIN A GIVEN CEILING, FLOOR,

ROOF, OR WALL. PENETRATIONS, JOINTS, FINISHES, AND

INTERSECTIONS BETWEEN ASSEMBLIES ARE NOT SHOWN.

SEE A0 SHEETS FOR ARCHITECTURAL NOTES, SHEET

SEQUENCE, AND ASSEMBLY TAG LEGENDS.

SEE A2 SHEETS FOR FLOOR PLAN ASSEMBLY LOCATIONS.

SEE A5 SHEETS FOR EXTERIOR DETAILS.

SEE A8 SHEETS FOR INTERIOR ASSEMBLIES, INTERIOR

ASSEMBLY NOTES, AND INTERIOR DETAILS.

SEE A9 SHEETS FOR ROOM SCHEDULE CEILING ASSEMBLY

LOCATIONS.

EXTERIOR ASSEMBLY NOTES

INTERIOREXTERIOR

CONTINUOUS SEALANT AND BACKER ROD

ENTIRE PERIMETER

DUCT AND HOOD PER MECHANICAL

PRE-FINISHED METAL

FLASHING WITH DRIP EDGE

6" METAL STUD FRAMING SIMILAR TO 2/A500,

BOX HEADERS NOT REQUIRED

FILL SHIM SPACE WITH SPRAY FOAM

(SIMILAR AT JAMBS)

DOOR

ROUGH

OPENING

6" INSULATED BOX HEADER

(E) 8" ZEE GIRT

(E) 8" ZEE GIRT (E) 8" ZEE GIRT

(2) 600S162-54 WELDED KING STUD

FILLED WITH BATT INSULATION SIMPSON SSC4.25 CLIPS,

TYPICAL. CUT EXPOSED

FASTENER ENDS FLUSH

3/8" ⌀ CONCRETE

SCREW, 4" EMBED

~NEW SLAB~

A500

A500

A500

A500

OPP

HAND

EXISTING ASPHALT

TO REMAIN

TOP OF STEM WALL

FI

E

LD

V

E R

IF

Y

/4

FI

E

LD

V

E R

IF

Y

/4

INTERIOREXTERIOR

EXISTING 8" GIRT

6" METAL STUD

BOX HEADER WITH

BATT INSULATION

PRE-FINISHED

METAL FLASHING

WITH DRIP EDGE

CONTINUOUS

SEALANT AND BACKER

ROD EACH SIDE

DOOR AND FRAME PER

DOOR SCHEDULE

FILL SHIM SPACE WITH

SPRAY FOAM

PROVIDE BATT

INSULATION

FILL VOID WITH

BATT INSULATION

FILL DOOR FRAME

WITH SPRAY FOAM

SELF EXTINGUISHING

VAPOR RETARDER

FABRIC LINER AS IT

COMPLIES WITH: ASTM

1136, TYPES I THROUGH

VI; NFPA 701 LARGE

SCALE; FLAME SPREAD

OF 25 OR LESS PER ASTM

E-84 (EQUIVALENT TO

NFPA 255, ANSI 2.5 OR

UL/ULC 723)

TERMINATION

BAR PERIMETER

OF OPENING

SEAL NEW VAPOR

RETARDER ON TO

EXISTING MINIMUM

OVERLAP 4"

INTERIOR

EXTERIOR

EXISTING 8" GIRT

WELDED KING STUD

WITH BATT INSULATION

PRE-FINISHED METAL FLASHING

WITH DRIP EDGE

CONTINUOUS SEALANT AND

BACKER ROD EACH SIDE

DOOR AND FRAME PER DOOR SCHEDULE

CLIP

FILL SHIM SPACE WITH SPRAY FOAM

FILL DOOR FRAME WITH SPRAY FOAM

TERMINATION BAR

PERIMETER OF OPENING

VAPOR RETARDER, SEE DETAIL 3/A500

INTERIOREXTERIOR

DOOR AND FRAME PER

DOOR SCHEDULE

DOOR FRAME BEYOND

EXISTING STRUCTURE BEYOND

THERMALLY BROKEN

THRESHOLD SEALED

MODIFY EXISTING

FLASHING AS REQUIRED

TO INSTALL THRESHOLD

CONCRETE LANDING

PER 5/A800

EXISTING STEM

WALL TO REMAIN

CONCRETE SLAB

PER 5/A800

AKAF AL

TS

TA

E O

49 TH

S

JAMES D. BARTLETT

No. A10413

D E S I G N

A L

A S

K A

REGISTERED PROFESSIONAL ARCHITE

CT

D ate

P roj ec t N o.

A r chit ect s

E n gin eer s

S u rve yor s

60 1 C olle ge R oa d F airb ank s A K 9 970 1 90 7.45 2.12 41 de sign alas ka.c om

0 4 J A N

2 01 9

F TQ

W

18 -0 20 3

A E

C C

S ht.

O f

3 54 th C iv il E n gi ne e r S q ua dr on

E ie lson A

FB, Alaska

P roj ec t E ng ine er

C hie f E ng in ee r D raw n By

D es ign ed B y

R efe re nc e

N o.

R ev

D es cri ptio n

B y D ate

E N

G

IN

E M A

IN

TE

N A

N C

E FA

C

IL IT Y

B

LD

G

1 3 46

04-JAN-2019

1/2/2019 2:43:46 PM

JB

EXTER IOR DETA IL S

A

M L M

3" = 1'-0"A500

1 EXTERIOR SECTION DETAIL - MECHANICAL HOOD PENETRATION

1" = 1'-0"A500

2 STRUCTURAL ELEVATION - DOOR OPENING CONSTRUCTION

3" = 1'-0"A500

3 EXTERIOR SECTION DETAIL - DOOR HEAD

3" = 1'-0"A500

4 EXTERIOR SECTION DETAIL - DOOR JAMB

3" = 1'-0"A500

5 EXTERIOR SECTION DETAIL - DOOR SILL

CEILING PLAN NOTES

B.

C.

D.

E.

COORDINATE MECHANICAL ELEMENTS INCLUDING

EXISTING SPRINKLERS, DIFFUSERS, RETURN AIR SLOTS,

ACCESS PANELS, AND EQUIPMENT.

COORDINATE ELECTRICAL ELEMENTS INCLUDING SMOKE

DETECTOR, LIGHTING, SENSORS, SIGNAGE, ACCESS

PANELS, AND EQUIPMENT WITH ELECTRICAL DOCUMENTS.

NOT ALL CEILING MOUNTED ITEMS ARE SHOWN NOR

IDENTIFIED. CONTRACTOR TO FIELD VERIFY.

SEE A800 FOR SEALING PENETRATIONS THROUGH LEAD-

LINED GYPSUM BOARD.

ANY PENETRATIONS THROUGH THE CEILING SHOULD

HAVE TWO BENDS WITH 1.5 TIMES LINE OF SIGHT

OVERLAP. THESE CAN THEN HAVE SHIELDING BOXES

THAT WOULD MATE WITH DIRECT LEAD CONTACT AT THE

CEILING LEVEL FOR EASE OF MAINTENANCE.

CEILING LEGEND

PNT-#

(SEE FINISH SCHEDULE FOR #)

PROVIDE, PATCH, REPAIR, PREPARE AND

PAINT GYPSUM BOARD CEILING

LOCATION OF PREVIOUSLY REMOVED

SPRINKLER HEADS

MECHANICAL EQUIPMENT

XRAY

VAULT

CHEMICAL

STORAGE

LIQUID

PENETRANT

BEARING

CLEANING

CKT

ROOM

DARK

ROOM

OIL

ANALYSIS

ROOM

WASH

RACK

MECHANICAL

TRAINING

ROOM

EXISTING HVAC DIFFUSERS.

REMOVE AND REPLACE IN KIND

AS REQUIRED TO ACCOMMODATE

LEAD LINING INSTALLATION.

WRAP EXISTING DUCT ABOVE

WITH LEAD LINING PER DETAIL:

C-G2

XRAY

ROOM

A800

FIRE

PUMP

C-G1 C-G3

A600

CONTRACTOR TO FIELD

VERIFY EXISTING DUCT

SIZES AND LAYOUT

BREAK

ROOM

EQUIPMENT

PLATFORM

KEYNOTES

PROVIDE 8 LB, 1/8" LEAD LINED GYPSUM BOARD WITH ALL

PENETRATIONS AND OVERLAP SHIELDED TO THE SAME

LEVEL, SEE A800.

PROVIDE GYPSUM BOARD AND SUSPENSION SYSTEM.

REMOVE AND REINSTALL EXISTING MECHANICAL AND

ELECTRICAL CEILING MOUNTED ITEMS AS REQUIRED TO

ACCOMMODATE FIRE SPRINKLER INSTALLATION.

JO

ISTS PER

ASSEMBLY TYPE

(E) ZEE GIRT

A600

INTERIOR EXTERIOR

FIRE SEALANT AT BACK SIDE OF

FLUTED METAL SIDING.

CONTRACTOR TO CUT GYPSUM

BOARD TO FIT FLUTES

FIRE SEALANT

C-G3

6" METAL STUD WALL

WITH 5/8" GYPSUM BOARD

8"

TAPE / SEAL CUT EDGE

OF INSULATION WITH

ALUMINUM TAPE.

FILL CAVITY WITH BATT

INSULATION

TAPE / SEAL CUT EDGE

OF INSULATION WITH

ALUMINUM TAPE.

AKAF AL

TS

TA

E O

49 TH

S

JAMES D. BARTLETT

No. A10413

D E S I G N

A L

A S

K A

REGISTERED PROFESSIONAL ARCHITE

CT

D ate

P roj ec t N o.

A r chit ect s

E n gin eer s

S u rve yor s

60 1 C olle ge R oa d F airb ank s A K 9 970 1 90 7.45 2.12 41 de sign alas ka.c om

0 4 J A N

2 01 9

F TQ

W

18 -0 20 3

A E

C C

S ht.

O f

3 54 th C iv il E n gi ne e r S q ua dr on

E ie lson A

FB, Alaska

P roj ec t E ng ine er

C hie f E ng in ee r D raw n By

D es ign ed B y

R efe re nc e

N o.

R ev

D es cri ptio n

B y D ate

E N

G

IN

E M A

IN

TE

N A

N C

E FA

C

IL IT Y

B

LD

G

1 3 46

04-JAN-2019

1/2/2019 2:43:48 PM

JB

REFL ECTED CE IL ING PL AN

A

LSM

1/8" = 1'-0"A600

1 INTERIOR PLAN - CEILING - 1ST FLOOR

1/8" = 1'-0"A600

2 INTERIOR PLAN - CEILING - 2ND FLOOR

KEYPLAN

1/4" = 1'-0"A600

3 FRAMING PLAN - CEILING

1 1/2" = 1'-0"A600

4 FRAMING SECTION - CEILING

INTERIOR DETAIL NOTES

B.

C.

D.

E.

F.

G.

SEE A0 SHEETS FOR ASSEMBLY TAG LEGEND.

SEE A5 SHEETS FOR EXTERIOR ASSEMBLIES AND

DETAILS.

PROVIDE FINISHES TO FULL HEIGHT OF WALL UNLESS

NOTED OTHERWISE.

LEAD WRAP TO MATCH THICKNESS OF LEAD LINING IN

LEAD-LINED GYPSUM BOARD.

SEAL PENETRATIONS IN LEAD LINED CONSTRUCTION PER

ANSI 43.3 2008 AND OTHER APPLICABLE CODES AND

STANDARDS.

PROVIDE 20 GAUGE METAL STUDS UNLESS NOTED

OTHERWISE.

PROVIDE ADDITIONAL LEAD WRAP AT PENETRATIONS

THROUGH LEAD LINING TO INCLUDE BUT NOT LIMITED TO;

LIGHTING, CONDUIT, SMOKE DETECTORS, SPRINKLER

HEADS, DUCT, VENTILATION DIFFUSERS, HYDRONIC

PIPING AND ELECTRICAL BOXES SHALL BE LINED WITH

LEAD WRAP. WHERE PENETRATIONS HAVE A BEND

PROVIDE LEAD WITH 1.5 TIMES LINE OF SIGHT OVERLAP.

AT CEILING PROVIDE LEAD LINED SHIELDING BOXES THAT

WOULD OVERLAP WITH LEAD LINED GYPSUM BOARD.

W11-6A

LEAD LINED GYPSUM

AT STUD WALL

GYPSUM BOARD - 1/32" LEAD LINED

NORTH WALL, 1/8" WEST WALL

EXISTING WALL ASSEMBLY

W11-6F

WALL INTERIOR 6" STUD

1 HOUR FIRE RATED

IBC TABLE 721.1(2): 13-1.1

GA FILE NUMBER: WP 1072

UL NUMBER: U465

5/8" GYPSUM BOARD

3 5/8" 16 GAUGE METAL

STUDS AT 16" OC

5/8" GYPSUM BOARDEXISTING 1/16" LEAD LINED

GYPSUM BOARD

PROVIDE METAL FRAME -

1/8" LEAD LINED UNLESS

NOTED OTHERWISE

EXTEND LEAD-LINED

GYPSUM WALL BOARD

INTO FRAME TO ALLOW

FOR OVERLAP

EXTERIOR

X-RAY ROOM

INTERIOR

X-RAY ROOM

PROVIDE GYPSUM BOARD

LEAD LINED

3"

PROVIDE STEEL

ASTRAGAL AT PAIR

DOOR - 1/8" LEAD

LINED UNLESS

NOTED OTHERWISE

EXISTING CMU WALL TO REMAIN

PROVIDE WOOD

DOOR - 1/8" LEAD

LINED UNLESS NOTED

OTHERWISE

1/

2"

(DOOR HEAD SIMILAR)

1/

2"

1/ 2"

GYPSUM BOARD LINED

WITH 1/8" LEAD UNLESS

NOTED OTHERWISE

EXISTING DUCT

5/ 8"

MECHANICAL DUCT

PENETRATION

EXISTING PLYWOOD

SHEATHING ON STRUCTURE

LEAD WRAP ALL

SIDES OF DUCT

1/

4"

3/ 4"

4' -0

12"

1 1/2"

PROVIDE GYPSUM BOARD -

1/8" LEAD LINED UNLESS

NOTED OTHERWISE

EXISTING LEAD-LINED

GYPSUM BOARD TO REMAIN

PROVIDE CONTINUOUS 1/8" LEAD

WRAP FROM CEILING ONTO WALL

PROVIDE GYPSUM BOARD 1/8" LEAD LINED

4"

" A

T N

O R

TH

, E

A S

T A

N D

S O

U

TH

W

AL

L.

S

TA

R T

LE

A

D L

IN

E

D G

Y P

S U

M A

T

" A .F

.F

A N

D E

XT

EN

D T

O U

N D

ER

SI

D E

O F

C E

IL

IN

G

A T

W E

S T

W

AL

L

GYPSUM BEAD

EXTERIOR

X-RAY VAULT

INTERIOR

X-RAY VAULT

PROVIDE DOOR

SWEEP - 1/8" LEAD

LINED UNLESS NOTED

OTHERWISE

PROVIDE ALUMINUM

THRESHOLD - 1/8" LEAD

UNLESS NOTED

OTHERWISE

1/ 2"

PROVIDE WOOD DOOR -

1/8" LEAD LINED UNLESS

NOTED OTHERWISE

*SIM AT DOOR 23A

WITH 3/32" LEAD

LINING.

C-G3

CEILING INTERIOR - SUSPENDED GYPSUM BOARD -

1 HOUR FIRE RATED

5/8" GYPSUM BOARD FINISH

PER ROOM SCHEDULE

6" 18 GAUGE METAL JOISTS AT 16" OC

FINISH PER ROOM SCHEDULE

5/8" GYPSUM BOARD

3 1/2 BATT INSULATION

GA FILE NUMBER: FC 4503

UL NUMBER: P512

SEE ROOM SCHEDULE FOR

ASSEMBLY LOCATION AND FINISH

C-G1 CEILING INTERIOR - GYPSUM BOARD

FINISH PER ROOM SCHEDULE

5/8" GYPSUM BOARD

SEE ROOM SCHEDULE FOR ASSEMBLY LOCATION AND FINISH

SUSPENDED GYPSUM GRID SYSTEM

C-G2 CEILING INTERIOR - GYPSUM BOARD

FINISH PER ROOM SCHEDULE

5/8" GYPSUM BOARD - 1/8" LEAD LINED

SEE ROOM SCHEDULE FOR ASSEMBLY LOCATION AND FINISH

EXISTING STRUCTURE TO REMAIN

6" S

LA

B

#5 AT 12" OCEW, CENTERED IN SLAB

EXISTING ASPHALT TO REMAIN

2'-0" COMPACTED STRUCTURAL FILL

IN-SITU SOILS TO REMAIN

MATCH

TOP OF

STEM WALL

SEE A200 FOR NEW WALL

EXISTING WALL TO REMAIN

EXISTING CONCRETE TO REMAIN

SLOPE EXCAVATION AS

NECESSARY TO PREVENT

UNDERMINING OF EXISTING

ASPHALT

NOTE: SEE 31 00 00 FOR

EARTHMOVING REQUIREMENTS

PROVIDE METAL FRAME -

3/32" LEAD LINED UNLESS

NOTED OTHERWISE

EXTEND LEAD-LINED

GYPSUM WALL BOARD

INTO FRAME TO ALLOW

FOR OVERLAP

EXTERIOR

X-RAY ROOM

INTERIOR

X-RAY ROOM

PROVIDE GYPSUM BOARD

LEAD LINED

EXISTING CMU WALL TO REMAIN

PROVIDE WOOD

DOOR - 3/32" LEAD

LINED UNLESS NOTED

OTHERWISE

1/

2"

(DOOR HEAD SIMILAR)

AKAF AL

TS

TA

E O

49 TH

S

JAMES D. BARTLETT

No. A10413

D E S I G N

A L

A S

K A

REGISTERED PROFESSIONAL ARCHITE

CT

D ate

P roj ec t N o.

A r chit ect s

E n gin eer s

S u rve yor s

60 1 C olle ge R oa d F airb ank s A K 9 970 1 90 7.45 2.12 41 de sign alas ka.c om

0 4 J A N

2 01 9

F TQ

W

18 -0 20 3

A E

C C

S ht.

O f

3 54 th C iv il E n gi ne e r S q ua dr on

E ie lson A

FB, Alaska

P roj ec t E ng ine er

C hie f E ng in ee r D raw n By

D es ign ed B y

R efe re nc e

N o.

R ev

D es cri ptio n

B y D ate

E N

G

IN

E M A

IN

TE

N A

N C

E FA

C

IL IT Y

B

LD

G

1 3 46

04-JAN-2019

1/2/2019 2:43:50 PM

JB

IN TER IOR ASSEMBL Y TYPES AND DETA IL S

A

LSM

3" = 1'-0"A800

3 INTERIOR DOOR DETAIL - LEAD-LINED DOOR AND FRAME JAMB

3" = 1'-0"A800

4 INTERIOR PENETRATION DETAIL - THRU DUCT WRAP CEILING

3" = 1'-0"A800

1 WALL TO CEILING JOINT

3" = 1'-0"A800

2 INTERIOR DETAIL - LEAD-LINED DOOR THRESHOLD

1" = 1'-0"A800

5 INTERIOR DETAIL - SLAB REPLACEMENT 3" = 1'-0"A800

6 INTERIOR DOOR DETAIL - LEAD-LINED DOOR AND FRAME JAMB AT ROOM 23 18

ROOM SCHEDULE NOTES

B.

PROVIDE FINISHES TO FULL HEIGHT OF WALL UNLESS

NOTED OTHERWISE.

SEE CEILING PLAN WHERE CEILING FINISH VARIES.

1.

2.

ROOM IS LEAD LINED.

PAINT ENTIRE WALL. EXISTING RUBBER BASE AND FIN

TUBE CABINET TO REMAIN, DO NOT PAINT. PAINT ALL

EXPOSED UNPAINTED AND PREVIOUS PAINTED CONDUIT.

ROOM SCHEDULE REMARKS

SEE A001 FOR STANDARD ARCHITECTURAL ABBREVIATIONS

SEE MATERIAL SCHEDULE FOR MATERIAL TYPES

AFF ABOVE FINISHED FLOOR

MFSD MANUFACTURER'S STANDARD

NIC NOT IN CONTRACT

CONC CONCRETE SEALED

ROOM SCHEDULE ABBREVIATIONS

DOOR SCHEDULE REMARKS

DOOR SCHEDULE AND TYPE NOTES

A.

B.

C.

D.

E.

COORDINATE ROUGH OPENING AND SHIM SPACE WITH

MANUFACTURER.

DOOR AND FRAME TYPES REPRESENTED AS VIEWED

FROM EXTERIOR SIDE UNLESS NOTED OTHERWISE.

COORDINATE POWER AND SECURITY WITH ELECTRICAL.

SEE A5 SHEETS FOR EXTERIOR ASSEMBLIES AND

DETAILS.

SEE A8 SHEETS FOR INTERIOR ASSEMBLIES AND DETAILS.

1.

2.

DOOR AND FRAME ARE LEAD LINED.

CONTRACTOR TO FIELD VERIFY DOOR OPENING.

DOOR SCHEDULE ABBREVIATIONS

SEE A001 FOR STANDARD ARCHITECTURAL ABBREVIATIONS

SEE MATERIAL SCHEDULE FOR MATERIAL TYPES

INHM INSULATED HOLLOW METAL

LLWD LEAD LINED WOOD DOOR

LLHM LEAD LINED HOLLOW METAL

MFSD MANUFACTURER STANDARD FINISH

WD WOOD DOOR

DOOR TYPES

F2

FLUSH PAIR

PER SCHEDULE

P E

R S

C H

E D

U

LE

EQ EQ

F1

FLUSH SINGLE

SCHEDULE

PER

P E

R S

C H

E D

U

LE

FRAME TYPES

2" PER SCHEDULE 2"

P E

R S

C H

E D

U

LE

2"

HARDWARE GROUP

HDW-1

DOOR 25A

6 HINGE BB5006 4-1/2 x 4-1/2 N 630 BOOMER INDUSTRIES

1 STOREROOM LOCKSET 45H-7D15H PATD 630 BEST ACCESS SYSTEMS

MANUAL FLUSH BOLT INACTIVE

LEAF TOP & BOTTOM

1 DOOR CLOSER QDC115P 689 STANLEY COMMERCIAL

2 OVERHEAD STOP 1020 A SERIES US32D ABH MANUFACTURING

2 GASKETING 127 SA HEAD & JAMBS NA

2 DOOR SWEEP 200 NA NA

1 THRESHOLD 8426 x 1/4-20 MS/EA AL NA

2 ASTRAGAL - LEAD LINED

*HARDWARE LISTED IS BASIS OF DESIGN. CONTRACTOR TO PROVIDE CYLINDERS, REMOVABLE AND INTERCHANGEABLE CORE SYSTEM: BEST COREMAX PATENTED 7-PIN. ALL OTHER HARDWARE IS "OR

EQUAL".

DOOR HARDWARE SHALL NOT COMPROMISE LEAD SHIELDING.

PROVIDE LEAD FLASHING AS REQUIRED BY MANUFACTURER TO MAINTAIN CONTINUOUS SHIELDING OF

DOOR ASSEMBLY.

HDW-2

DOOR 119A

6 HINGE BB5006 4-1/2 x 4-1/2 N 630 BOOMER INDUSTRIES

1 STOREROOM LOCKSET 45H-7D15H PATD 630 BEST ACCESS SYSTEMS

MANUAL FLUSH BOLT INACTIVE

LEAF TOP & BOTTOM

1 DOOR CLOSER QDC115P 689 STANLEY COMMERCIAL

2 OVERHEAD STOP 1020 A SERIES US32D ABH MANUFACTURING

2 GASKETING 127 SA HEAD & JAMBS NA

2 DRIP CAP 16 A - 4" ODW NA

2 DOOR SWEEP 200 NA NA

1 THRESHOLD 8426 x 1/4-20 MS/EA AL NA

2 ASTRAGAL

HDW-3

DOOR 23A

3 HINGE BB5006 4-1/2 x 4-1/2 N 630 BOOMER INDUSTRIES

1 STOREROOM LOCKSET 45H-7D15H PATD 630 BEST ACCESS SYSTEMS

1 DOOR CLOSER QDC115P 689 STANLEY COMMERCIAL

1 GASKETING 127 SA HEAD & JAMBS NA

1 DOOR SWEEP 200 NA NA

1 THRESHOLD 8426 x 1/4-20 MS/EA AL NA

MATERIAL SCHEDULE NOTES

A.

B.

SEE CEILING PLANS AND ROOM SCHEDULE FOR

LOCATION OF FINISHES.

THE MATERIAL SCHEDULE IS ORGANIZED BY SPEC

NUMBER. MATERIALS WITH SPEC NUMBERS INCLUDING

'NA' ARE INTENDED AS A BASIS OF DESIGN WITH NO

CORRELATING SPEC SECTION.

1.

MISCELLANEOUS

NOT USED

MATERIAL SCHEDULE REMARKS

SEE A001 FOR STANDARD ARCHITECTURAL ABBREVIATIONS

MATERIAL TYPES DEFINED IN MATERIAL SCHEDULE

MFSD MANUFACTURER'S STANDARD

SPEC SPECIFICATION

TYP TYPICAL

MATERIAL SCHEDULE ABBREVIATIONS

A.

B.

C.

D.

E.

F.

COMPOSITE WOOD AND AGRIFIBER PRODUCTS

(INCLUDING ASSOCIATED SUBSTRATE) MUST CONTAIN

NO ADDED UREA-FORMALDEHYDE.

CLEAR WOOD FINISHES, FLOOR COATINGS, STAINS,

PRIMERS, SEALERS, AND SHELLACS (INCLUDING TILE

SETTING ADHESIVE, AND GROUT) APPLIED TO INTERIOR

ELEMENTS MUST NOT EXCEED THE VOC CONTENT LIMITS

ESTABLISHED IN SCAQMD RULE 1113 AS OF 01 JAN 2004.

ADHESIVES, SEALANTS, AND SEALANT PRIMERS APPLIED

TO INTERIOR ELEMENTS MUST COMPLY WITH SCAQMD

RULE 1168 AS OF 01 JULY 2005. AEROSOL ADHESIVES

APPLIED TO INTERIOR ELEMENTS MUST COMPLY WITH

GREEN SEAL GS-36 AS OF 19 OCTOBER 2000.

HARD SURFACE FLOORING AND WALL BASE MUST BE

FLOORSCORE CERTIFIED.

CARPET MUST MEET GREEN LABEL PLUS

REQUIREMENTS. CARPET CUSHION MUST MEET GREEN

LABEL REQUIREMENTS.

ARCHITECTURAL PAINTS AND COATINGS APPLIED TO

INTERIOR ELEMENTS MUST NOT EXCEED THE VOC

CONTENT LIMITS ESTABLISHED IN GREEN SEAL

STANDARD GS-11 AS OF 20 MAY 1993.

LOW EMITTING

LE-

LE-

LE-

LE-

LE-

LE-

AKAF AL

TS

TA

E O

49 TH

S

JAMES D. BARTLETT

No. A10413

D E S I G N

A L

A S

K A

REGISTERED PROFESSIONAL ARCHITE

CT

D ate

P roj ec t N o.

A r chit ect s

E n gin eer s

S u rve yor s

60 1 C olle ge R oa d F airb ank s A K 9 970 1 90 7.45 2.12 41 de sign alas ka.c om

0 4 J A N

2 01 9

F TQ

W

18 -0 20 3

A E

C C

S ht.

O f

3 54 th C iv il E n gi ne e r S q ua dr on

E ie lson A

FB, Alaska

P roj ec t E ng ine er

C hie f E ng in ee r D raw n By

D es ign ed B y

R efe re nc e

N o.

R ev

D es cri ptio n

B y D ate

E N

G

IN

E M A

IN

TE

N A

N C

E FA

C

IL IT Y

B

LD

G

1 3 46

04-JAN-2019

1/2/2019 2:43:52 PM

JB

ROOM, MATER IA L, AND DOOR SCHEDULES

A

M L M

ROOM SCHEDULE

ROOM FLOOR WALL CEILING ROOM

NUMBER NAME FINISH BASE FINISH

ASSEMBLY

TYPE FINISH HEIGHT REMARKS NUMBER

25 XRAY VAULT EXIST EXIST PNT-50 C-G2 PNT-80 12' - 0" 1, 2 25

109 CHEMICAL STORAGE EXIST EXIST EXIST (E) C-G1 PNT-80 9' - 0" 109

110 LIQUID PENETRANT EXIST EXIST EXIST C-G1 PNT-80 9' - 0" 110

111 BEARING CLEANING EXIST EXIST EXIST (E) C-G1 PNT-80 9' - 0" 111

118 STORAGE EXIST EXIST EXIST -- EXIST OTS 118

119 FIRE PUMP CONC -- PNT-50 C-G3 PNT-80 14' 6" 119

MATERIAL SCHEDULE

SPEC TYPE DESCRIPTION LOCATION

BASIS OF DESIGN REMARKS

TYPEMANUFACTURER MODEL COLOR

LOW

EMITTING MISCELLANEOUS

08 10 00 - OPENINGS - DOORS AND FRAMES

08 14 16 WD-1 FLUSH WOOD DOOR PER DOOR SCHEDULE CECO DOORS LEAD LINED DOOR MATCH EXISTING WD-1

09 90 00 - FINISHES - PAINTING AND COATING

09 91 13 PNT-20 EXTERIOR PAINT - DOOR PER DOOR SCHEDULE SHERWIN WILLIAMS EXTERIOR ACRYLIC LATEX TO BE DETERMINED PNT-20 09 91 13 PNT-30 EXTERIOR PAINT - DOOR FRAME PER DOOR SCHEDULE SHERWIN WILLIAMS EXTERIOR ACRYLIC LATEX MATCH MTF-1 PNT-30 09 91 23 PNT-50 INTERIOR PAINT - WALL PER ROOM SCHEDULE SHERWIN WILLIAMS PROMAR 200 INTERIOR LATEX MATCH EXISTING LE-F PNT-50 09 91 23 PNT-70 INTERIOR PAINT - DOOR FRAME PER DOOR SCHEDULE SHERWIN WILLIAMS PROMAR 200 INTERIOR LATEX MATCH EXISTING LE-F PNT-70 09 91 23 PNT-80 INTERIOR PAINT - CEILING PER ROOM SCHEDULE SHERWIN WILLIAMS PROMAR 200 INTERIOR LATEX MATCH EXISTING LE-F PNT-80 09 91 23 SEAL-1 INTERIOR WOOD SEALER EXPOSED INTERIOR WOOD SHERWIN WILLIAMS STAIN / VARNISH MATCH EXISTING LE-B SEAL-1

DOOR SCHEDULE

DOOR

NUMBER

DIMENSIONS DOOR FRAME DETAIL FIRE RATING

(MINUTES)

HARDWARE

GROUP

POWER /

SECURITY REMARKS

DOOR

NUMBERWIDTH HEIGHT MATERIAL TYPE FINISH MATERIAL TYPE FINISH HEAD JAMB SILL

23A 3'-0" 7'-0" LLWD F1 SEAL-1 LLHM 2 PNT-70 6/A800 SIMILAR 6/A800 2/A800 -- HDW-3 -- 1, 2 23A 25A 6'-0" 7'-0" LLWD F2 SEAL-1 LLHM 2 PNT-70 3/ A800 SIMILAR 3/ A800 2/A800 -- HDW-1 -- 1, 2 25A 119A 6'-0" 6'-8" INHM F2 PNT-20 INHM 2 PNT-30 3/A500 4/A500 5/A500 -- HDW-2 -- 119A

ABBREVIATIONS AND SCHEDULES

Marcus P. Curley

No. ME14660

REGISTERED PROFESSIONAL ENGIN

EE

R

02-JAN-2019

DEMOLITION PLANS

No. ME14660

REGISTERED PROFESSIONAL ENGIN

EE

R

02-JAN-2019

MECHANICAL PLANS

No. ME14660

REGISTERED PROFESSIONAL ENGIN

EE

R

02-JAN-2019

MECHANICAL DETAILS

No. ME14660

REGISTERED PROFESSIONAL ENGIN

EE

R

02-JAN-2019

XRAY VAULT

CHEMICAL

STORAGE

LIQUID

PENETRANT

BEARING

CLEANING

CKT ROOM

DARK ROOM

OIL ANALYSIS

ROOM

WASH RACK

MECHANICAL

DEMOLISH EXISTING HALON PIPING ABOVE

HARD LID CEILING AS REQUIRED TO INSTALL

SPRINKLER PIPING. PROVIDE BRANCH

PIPING OR ARMOVERS TO SERVE NEWLY

INSTALLED SPRINKLER HEADS SERVING

SPACES SHOWN. PROVIDE CHROME

PLATED ESCUTCHEONS SERVING ALL

SPRINKLER HEADS.

REMOVE ALL SPRINKLER HEAD

ESCUTCHEONS IN THIS AREA

AND PROVIDE NEW CHROME

PLATED ESCUTCHEONS ON ALL

SPRINKLER HEADS.

EXISTING CROSS MAIN PIPING

SERVING ROOMS TO WEST,

SEE PFOS/PFOA SHEET NOTES.

APPROXIMATE

LOCATION OF

REMOVED HALON

HEAD, 5 TYP.

TRAINING ROOM

XRAY ROOM

FIRE PUMP

F101

EXISTING 3" SPRINKLER PIPING

ABOVE HARD LID CEILING

FACP LOCATED IN ROOM 106

MECHANICAL

EXISTING FDC

TO REMAIN

EXISTING CROSS MAIN UP TO 2ND FLOOR

EXISTING BFP

DEMOLISH EXISTING 6" ELBOW, 2 TYP.

REMOVE

EXISTING DPV

EXISTING 3"

BRANCH

PIPING TO

REMAIN

EXISTING 4"

BRANCH

PIPING TO

REMAIN

FIRE PROTECTION SYMBOLS

CONNECTION TO EXISTING

MANUAL PULL STATIONP

SPEAKER/STROBE

D ate

P roj ec t N o.

A r chit ect s

E n gin eer s

S u rve yor s

60 1 C olle ge R oa d F airb ank s A K 9 970 1 90 7.45 2.12 41 de sign alas ka.c om

0 4 J A N

2 01 9

F TQ

W

18 -0 20 3

A E

C C

S ht.

O f

3 54 th C iv il E n gi ne e r S q ua dr on

E ie lson A

FB, Alaska

P roj ec t E ng ine er

C hie f E ng in ee r D raw n By

D es ign ed B y

R efe re nc e

N o.

R ev

D es cri ptio n

B y D ate

E N

G

IN

E M A

IN

TE

N A

N C

E FA

C

IL IT Y

B

LD

G

1 3 46

1/9/2019 5:07:54 PM

M

SO

F IRE PROTECT ION F IRST F LOOR PL AN

F1 00

M

SO

FIRE PROTECTION NOTES

1.

2.

3.

4.

5.

6.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

1.

2.

3.

4.

1.

2.

3.

4.

5.

6.

7.

8.

9.

APPLICABLE CODES:

UFC 3-600-01 (CHANGE 1, 28 NOVEMBER 2016)

EIELSON AFB FIRE PROTECTION DESIGN GUIDE - (16 AUGUST 2017)

NFPA 11 (2016)

NFPA 13 (2016)

NFPA 20 (2016)

NFPA 72 (2016)

SCOPE OF WORK:

BUILDING IS PROTECTED WITH EXISTING DRY PIPE SYSTEM.

EXISTING HALON PROTECTION HAS BEEN PREVIOUSLY REMOVED FROM ROOMS 109, 110, 111.

EXISTING FIRE WATER SUPPLY IS NOT ADEQUATE TO SERVE EXISTING DRY PIPE SYSTEM. PROVIDE A SINGLE FIRE PUMP TO PROVIDE ADEQUATE PRESSURE FOR THE EXISTING SUPPRESSION SYSTEM.

PROVIDE SPRINKLER PROTECTION TO ROOMS 109, 110, 111 IN ACCORDANCE WITH UFC 3-600-01 FOR

AN ORDINARY HAZARD SPACE.

EXTEND EXISTING SPRINKLER SYSTEM TO PROVIDE PROTECTION IN NEWLY CREATED FIRE PUMP 119.

PROTECT IN ACCORDANCE WITH UFC 3-600-01 FOR ORDINARY HAZARD.

REPLACE EXISTING DRY PIPE VALVE.

PROVIDE FIRE WATCH IN ACCORDANCE WITH NFPA 25 IF SPRINKLER SYSTEM IS OFFLINE FOR MORE

THAN FOUR HOURS.

TEST ALL NEW AND MODIFIED COMPONENTS IN ACCORDANCE WITH NFPA 25 TABLE 5.5.1.

MODIFY EXISTING MONACO FIRE ALARM SYSTEM TO PROVIDE INPUT MODULES FOR MONITORING NEW FIRE PUMP INSTALLATION, INPUTS TO INCLUDE: RUNNING, LOSS OF PHASE, PHASE REVERSAL).

CONNECT INITIATING DEVICES SHOWN ON PLANS TO EXISTING SYSTEM. TEST MODIFIED FIRE ALARM

SYSTEM IN ACCORDANCE WITH NFPA 72 14.4.2.

EXISTING MANACO FACP IS LOCATED IN ROOM 106 (CEMS OFFICE)

EIE406 SCOPE OF WORK (FOR REFERENCE ONLY):

THIS PROJECT RECENTLY MODIFIED THE WATER SUPPLY FROM B1310(FIRE PUMP BUILDING) TO BE

FROM THE 12-INCH DOMESTIC BASE-WIDE WATER SUPPLY.

REPLACED 6-INCH WATER SUPPLY, DEMOLISH AND REPLACE 6-INCH PIPING FROM WATER SUPPLY TO

POINT OF CONNECTION AT EXISTING DRY PIPE VALVE.

INSTALL DOUBLE CHECK BACKFLOW PREVENTER.

REPLACE FIRE DEPARTMENT CONNECTION PIPING.

FIRE PUMP REQUIREMENTS:

PROVIDE MAINTENANCE ACCESS TO THE FIRE PUMP AND DRIVER SO THEY MAY BE REMOVED FROM

THE ROOM.

PROVIDE A MINIMUM OF 3FT OF CLEARANCE ON THE FRONT SIDE OF THE FIRE PUMP ASSEMBLY FOR MAINTENANCE AND IN FRONT OF THE PUMP CONTROLLER. PROVIDE MINIMUM 3FT FROM THE ROOM

ENTRY TO THE FIRE PUMP AND CONTROLLER.

PROVIDE A MINIMUM 3FT ACCESS TO AND IN FRONT OF ALL EQUIPMENT AND 6IN BEHIND.

PROVIDE LABELING ON THE SURFACES OF THE PIPING IN THE PUMP ROOM TO SHOW THE WATER FLOW DIRECTION AND PIPE FUNCTION (SUCTION, DISCHARGE, TO FDC, TO BYPASS, TO TEST HEADER, TO SPRINKLER SYSTEM). PROVIDE WHITE PAINTED STENCILED LETTERS AND ARROWS, A MINIMUM OF

2IN IN HEIGHT AND VISIBLE FROM AT LEAST THREE SIDES WHEN VIEWED FROM THE FLOOR.

ARRANGE FIRE PUMP TO AUTOMATICALLY SHUT DOWN AFTER REACHING THE STOP PRESSURE AND THE EXPIRATION OF A MINIMUM OF 10-MINUTE RUN TIMER. STOP PRESURE MUST BE AT LEAST 5PSI

BELOW MAX CHURN PRESSURE AT THE LOWEST AVAILABLE STATIC PRESSURE.

FIRE PUMP ACTIVATION MUST TRANSMIT AN ALARM CONDITION TO THE INSTALLATION RECEIVING

STATION BUT NOT ACTIVATE THE FACILITY NOTIFICATION APPLIANCE CIRCUITS.

PROVIDE A TEST HEADER MANIFOLD ON THE FACILITY EXTERIOR THAT PERMITS FLOW TESTING

DIRECTLY FROM THE HEADER.

PROVIDE A FLOW METER INSTALLED IN ACCORDANCE WITH NFPA 20.

PROVIDE A BYPASS IN ACCORDANCE WITH NFPA 20 AROUND THE FIRE PUMP.

PFOS/PFOA SHEET NOTES

1.

2.

THE BUILDING FIRE SUPPRESSION SYSTEM IS KNOWN TO BE CONTAMINATED WITH PFOS/PFOA FROM PUMP STATION 1310. ALL SUPPRESSION PIPING AND EQUIPMENT REMOVED IS REQUIRED TO BE TREATED

AS CONTAMINTED AND DISPOSED OF IN ACCORDANCE WITH APPLICABLE FEDERAL, STATE, AND

INSTALLATION REGULATIONS.

ACCEPTANCE TESTING OF THE MODIFIED SPRINKLER HEADS SYSTEM SHALL INCLUDE REQUIRED

TESTING AT WORKING PRESSURE.

3/16" = 1'-0"F100

1 FIRE SUPPRESSION PLAN

1/4" = 1'-0"F100

2 FIRE PROTECTION DEMOLITION PLAN

FIRE PROTECTION ABBREVIATIONS

KEY NAME

FIRE PROTECTION

ABBREVIATIONS

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NPSH NET PUMP SUCTION HEAD

NTS NOT TO SCALE

OS&Y OUTSIDE SCREW & YOKE

PH PHASE

PRDV PRESSURE REDUCING VALVE

PRV PRESSURE RELIEF VALVE

RPM REVOLUTIONS PER MINUTE

S/M SHEET METAL

S/S START/STOP

SH SHOWER

SIM SIMILAR

TYP TYPICAL

VFD VARIABLE FREQUENCY DRIVE

W/ WITH

W/O WITHOUT

FIRE PROTECTION ABBREVIATIONS

KEY NAME

FIRE PROTECTION

ABBREVIATIONS

# NUMBER

& AND

@ AT

APPROX APPROXIMATE

BFP BACKFLOW PREVENTOR

CW COLD WATER

DIA DIAMETER

DPV DRY PIPE VALVE

ELEC ELECTRICAL

EXIST EXISTING

FACP FIRE ALARM CONTROL PANEL

FD FLOOR DRAIN

FDC FIRE DEPARTMENT CONNECTION

FP FIRE PROTECTION

MAX MAXIMUM

MECH MECHANICAL

MIN MINIMUM

LINETYPE LEGEND

DEMOLISHED

EXISTING

NEW

AKAF AL

TS

TA

E O

49 TH

S

D E S I G N

A L

A S

K A

REGISTERED PROFESSIONAL ENGIN

EE

R

03-JAN-2019

Mitchell S. O'Bryant

No. FP14690

P

F101

F101

FIRE PUMP

MECHANICAL

3 5

6 14

EXISTING BRANCH PIPE

ROUTED THROUGH FIRE

PUMP 119, NOT SHOWN

FOR CLARITY. MODIFY

BRANCH PIPING TO

PROVIDE SPRINKLER

PROTECTION WITHIN

FIRE PUMP 119. MODIFY

PIPING ABOVE ROOM TO

PROVIDE PROTECTION

TO LARGER SPACE AT

ROOF LEVEL AS

REQUIRED.

EXISTING ELECTRICAL GEAR

1ST FLOOR

0"

F101

1ST FLOOR

0' - 0"

FIRE PUMP

TO DRY

PIPE

RISER

F101

6 4

TO DRY PIPE RISER

TO FIRE PUMP

TEST HEADER

13 13

2 PIPE DIAM. MIN.

F102

FIRE PUMP

MECHANICAL

MAXIMIZE STRAIGHT

SUCTION PIPING

LENGTH

D ate

P roj ec t N o.

A r chit ect s

E n gin eer s

S u rve yor s

60 1 C olle ge R oa d F airb ank s A K 9 970 1 90 7.45 2.12 41 de sign alas ka.c om

0 4 J A N

2 01 9

F TQ

W

18 -0 20 3

A E

C C

S ht.

O f

3 54 th C iv il E n gi ne e r S q ua dr on

E ie lson A

FB, Alaska

P roj ec t E ng ine er

C hie f E ng in ee r D raw n By

D es ign ed B y

R efe re nc e

N o.

R ev

D es cri ptio n

B y D ate

E N

G

IN

E M A

IN

TE

N A

N C

E FA

C

IL IT Y

B

LD

G

1 3 46

1/9/2019 5:07:59 PM

M

SO

F IRE PROTECT ION P L ANS AND DETAI LS

F1 01

M

SO

1/2" = 1'-0"F101

1 FIRE PROTECTION ENLARGED PLAN

FIRE PROTECTION KEYNOTES

1 VERTICAL IN-LINE ELECTRIC FIRE PUMP

2 ELECTRIC IN-LINE JOCKEY PUMP

1/2" = 1'-0"F101

3 FIRE PUMP TEST HEADER ELEVATION

1/2" = 1'-0"F101

2 FIRE PUMP ELEVATION

3 CHECK VALVE

4 OS&Y GATE VALVE WITH TAMPER SWITCH, NORMALLY OPEN

5 INDICATING BUTTERFLY VALVE, NORMALLY OPEN

6 INDICATING BUTTERFLY VALVE, NORMALLY CLOSED

7 FIRE PUMP TEST METER

8 FIRE PUMP TEST HEADER (4) 2-1/2" HOSE VALVES WITH CAPS,

COORDINATE INSTALL WITH DUCTWORK, DO NOT INSTALL UNDER

INTAKE HOOD.

10 EXISTING BFP

11 6-INCH DRY PIPE VALVE, CONNECT TO EXISTING AIR

COMPRESSOR AND DRAIN PIPING.

9 FIRE PUMP TEST LOOP TO PUMP SUCTION

12 EXISTING FDC

13 PRESSURE GAUGE

14 4" CONCRETE HOUSEKEEPING PAD, 3/F102

15 8" PIPE REQUIRED FOR 10 PIPE DIAMETERS UPSTREAM OF PUMP

SUCTION FLANGE

AKAF AL

TS

TA

E O

49 TH

S

D E S I G N

A L

A S

K A

REGISTERED PROFESSIONAL ENGIN

EE

R

03-JAN-2019

Mitchell S. O'Bryant

No. FP14690

16 MECHANICAL EQUIPMENT, FOR REFERENCE

17 FIRE PUMP CONTROLLERS

FIRE PUMP

PRESSURE

MAINTENANCE

PUMP

FLOW METER

EXTERIOR FIRE

PUMP TEST

HEADER . (4) 2-1/2"

HOSE VALVES.

NO NO

NO

NC

EXISTING

FDC

NC

6"

6"

6"

6"

6"

8"

NEW 6-INCH DRY

PIPE VALVE

EXISTING DRY PIPE

TO BUILDING

NC

NO

FIRE PUMP 119 MECHANICAL 117

8"

8" 6"

EXISTING 8" FROM UTILIDUCT

BFP

NO NO

EXISTING BACKFLOW PREVENTER

6"

NO EXISTING

DOMESTIC

WATER PIPING

DRAIN VALVE

ISOLATION VALVE WITH INTEGRAL TAMPER SWITCH

OS&Y ISOLATION VALVE WITH TAMPER SWITCH

CHECK VALVE

FIRE DEPARTMENT CONNECTION

HOSE VALVE WITH CAP AND CHAIN

PRESSURE GAUAGE

SECTION A-APLAN

1.

2.

3.

4.

5.

6.

7.

8.

HOUSEKEEPING PAD PLAN DIMENSIONS ARE DEPENDANT ON

EQUIPMENT. SEE FIRE SUPPRESSION EQUPMENT.

6X6-W1.4XW1.4 WELDED WIRE REINFORCEMENT, CENTERED IN

PAD

#3 DOWELS WITH 4 1/2'' LEGS. DRILL AND EPOXY WITH HILTI-HY

200 EPOXY OR APPROVED EQUAL WITH 2 1/2'' EMBED

DOWELS AT 24'' ON CENTER EACH WAY

CHAMFER EXPOSED EDGES 3/4''

BASE SLAB

3'' EDGE DISTANCE FOR DOWELS

4'' PAD THICKNESS UNLESS NOTED OTHERWISE

NOTES

2' - 0"

(3) (2)

(1)

(5) (5)

(6)

(2) (1)

(3)

(8

A A

D ate

P roj ec t N o.

A r chit ect s

E n gin eer s

S u rve yor s

60 1 C olle ge R oa d F airb ank s A K 9 970 1 90 7.45 2.12 41 de sign alas ka.c om

0 4 J A N

2 01 9

F TQ

W

18 -0 20 3

A E

C C

S ht.

O f

3 54 th C iv il E n gi ne e r S q ua dr on

E ie lson A

FB, Alaska

P roj ec t E ng ine er

C hie f E ng in ee r D raw n By

D es ign ed B y

R efe re nc e

N o.

R ev

D es cri ptio n

B y D ate

E N

G

IN

E M A

IN

TE

N A

N C

E FA

C

IL IT Y

B

LD

G

1 3 46

1/9/2019 5:08:13 PM

M

SO

F IRE SUPPRESS ION SCHEMAT IC

F1 02

M

SO

F102

1 FIRE PUMP ROOM ISOMETRIC

NO SCALEF102

2 FIRE SUPPRESSION SCHEMATIC

SHEET NOTES:

1.

2.

THE SCHEMATIC DRAWING IS REPRESENTATIVE / CONCEPTUAL IN NATURE. SEE OTHER FIRE

SUPPRESSION SHEETS FOR ADDITIONAL DETAIL, LOCATIONS, CLEARANCES, ETC.

PROVIDE PUMP CONTROLLER PRESSURE SENSING LINES IN ACCORDANCE WITH UFC 3-600-01.

SCHEMATIC SYMBOL LEGEND:

1/2" = 1'-0"F102

3 HOUSEKEEPING PAD

AKAF AL

TS

TA

E O

49 TH

S

D E S I G N

A L

A S

K A

REGISTERED PROFESSIONAL ENGIN

EE

R

03-JAN-2019

Mitchell S. O'Bryant

No. FP14690

CMU DOOR HEADER

JUNCTION BOX

X-RAY DUAL

INTERLOCK

SWITCH

DOOR

SURFACE MOUNT LIGHTING FIXTURE

J JUNCTION BOX

ELECTRICAL LEGEND

EMERGENCY LIGHTING UNIT

IS DOOR ACCESS HARDWARE - DUAL INTERLOCK SWITCH

WALL MOUNT EMERGENCY EXIT LIGHTING FIXTURE

SPST MANUAL LIGHTING CONTROL DEVICE

M

T

GFCI DUPLEX RECEPTACLE

+4'-0" A.F.F. U.O.N.

MOTOR (HP, VOLTAGE & PHASE NOTED ON DRAWING)

MANUAL MOTOR SWITCH W/ THERMAL OVERLOADS

(PROVIDE WITH MANUFACTURER'S ENCLOSURE FOR A

U.L. LISTED DEVICE)

EQUIPMENT CONNECTION

EXISTING CT

CABINET

EXISTING 480V

DISCONNECT

EXISTING METER

TO EXISTING 480V MAIN

DISTRIBUTION PANEL

(MDP-2)

TO EXISTING 225 KVA

PAD MOUNT SERVICE

TRANSFORMER

SERVICE ENTRANCE RATED

FIRE PUMP CONTROLLER

WITH DISCONNECT AND SOFT

STARTER (NOT TO EXCEED 400%

INRUSH CURRENT).

M

PROVIDE JUNCTION BOX

TO TAP SECONDARY

CONDUCTORS FOR FIRE

PUMP SERVICE

EQUIPMENT

PROVIDE NEW

METER BASE WITH

NEW SMART

METER PER EAFB

METERING

STANDARDS

PROVIDE

JUNCTION BOX

(CT CABINET)

WITH LOOP OR

SPLIT CORE CT'S

200:5

(4) # 4/0 AWG,

#2 AWG SUPPLY SIDE

BONDING

MIN. 2" RMC

ROUTED ALONG

EXTERIOR OF

FACILITY

7,040

X,XXX = AVAILABLE SYMMETRICAL THREE PHASE FAULT CURRENT

INTERIOREXTERIOR

GROUNDING

BUSBAR

FIRE PUMP

125 HP

480V, 3 PH

(3) # 4/0 AWG,

#1/0 GND,

2" C.

#2 AWG GROUNDING ELECTRODE CONDUCTOR

TYP. #2 AWG GROUNDING

ELECTRODE CONDUCTOR TO

OTHER GROUNDING ELECTRODES

LOCATED WITHIN ROOM

#2 AWG GROUNDING

ELECTRODE

CONDUCTOR TO 3/4" X

10' CU. GROUNDING

ELECTRODE.

PROVIDE #2 AWG

BONDING JUMPER TO

ADJACENT GROUNDING

ELECTRODE SYSTEM

AT THE EXISTING 480V

ELECTRICAL SERVICE.

EXISTING TRANSFORMER

RATING

%Z

X/R

V (PRI)

V (SEC)

225 KVA

3.9

3.4 (TYP.)

7200 V

480Y/277 V

FLA (PRI)

FLA (SEC)

MOCP (PRI-FUSE)

18.04 A

270.63 A

65 A NEC 450.3(A), NOTE 1(b)

FIRE PUMP SERVICE CALCULATIONS

FIRE PUMP SIZE

VOLTAGE

FLA

LRC

JOCKEY PUMP SIZE

125 HP

480 V

156 A

908 A

1/2 HP

VOLTAGE

FLA

LRC

480 V

1.1 A

10 A

EXISTING 480V MAIN DISTRIBUTION PANEL (MDP-2)

PARTS CAGE

AHU-2 (3 HP)

MP-1

20 A

4.8 A

100 A

DEMAND LOAD 126 A

TRANSFORMER CALCULATION

125% FIRE PUMP LOADS

SUBTOTAL

100% BUILDING LOADS

156 + 1.1

196.4 A

26 A

26 A WITHOUT MP-1

MIN. SIZE PER LOADS 222.4 A

MIN. SIZE (480V) 185 KVA 225 NEXT STANDARD SIZE

PRIMARY OVERCURRENT CALCULATION

TOTAL LRC

SUBTOTAL

BUILDING LOADS

908 + 10

918 A

26 A

MIN. SIZE PER LOAD (SEC) 944 A

62.93 A 480V TO 7200V

CONDUCTOR AMPACITY

125% FIRE PUMP LOADS

SUBTOTAL

125% BUILDING LOADS

1.25(156 + 1.1)

196.4 A

1.25(26)

SUBTOTAL 32.5 A

MIN. SINGLE FEEDER 228.9 A EXISTING 4/0 RATED 230A

LESS MP-1

LESS MP-1

MIN. SIZE PER LOAD (PRI)

EXISTING LOADS

MCB RATING 300 A

TYPE GE SPECTRA SERIES APNB

NEC TABLE 430.251(B)

NEC TABLE 430.251(B)

ANNOTATION SYMBOLS

L1-12

L1-12

AHU-1

PANEL & CIRCUIT IDENTIFICATION

PANEL & CIRCUIT IDENTIFICATION

B LIGHTING FIXTURE TAG

'L1' DENOTES PANEL NAME, '24' DENOTES CIRCUIT NUMBER.L1-24

LIGHTING FIXTURE TAG (SEE LIGHTING FIXTURE SCHEDULE)B2

SPECIFIC NOTE KEY

(REFERENCE # UNDER 'SPECIFC NOTES' ON EACH SHEET)

a

SWITCH IDENTIFICATION TAG

a SWITCH IDENTIFIER

EQUIPMENT IDENTIFIER, SEE ELECTRIC MOTOR

SCHEDULE

ABBREVIATIONS

AVAILABLE INTERRUPTING CAPACITYAIC

AMERICAN WIRE GAUGEAWG

CURRENT TRANSFORMERCT

COPPERCU

EXISTING TO REMAIN(E)

GROUNDGND

MAIN CIRCUIT BREAKERMCB

RIGID METAL CONDUITRMC

GROUND FAULT CIRCUIT INTERRUPTERGFCI

ABOVE FIXED FLOORAFF

AKAF AL

TS

TA

E O

49 TH

S

D E S I G N

A L

A S

K A

REGISTERED PROFESSIONAL ENGIN

EE

R

D ate

P roject N o.

A rchitects

E ngineers

S urveyors

601 C ollege R oad Fairbanks AK 99701 907.452.1241 designalaska.com

04 JA

N

FTQ

W

18-0203

A E

C C

S ht.

O f

354th C ivil E ngineer Squadron

E ielson A

FB

, A laska

P roject E ngineer

C hief E ngineer D raw n By

D esigned By

R eference

N o.

R ev

D escription

By D ate

E N

G

IN

E M A

IN

TE

N A

N C

E FA

C

ILITY

B

LD

G

03-Jan-2019

Jeffrey M. Leonelli

EE 107788

1/3/2019 2:53:04 PM

JM

L

ELECTRICAL LEGEND AND SCHEDULES

E

JM

L

NOT TO SCALEE001

2 X-RAY INTERLOCK SWITCH DETAIL

ELECTRIC MOTOR SCHEDULE

TAG DESCRIPTION HP VOLTAGE PH FLA DISC. TYPE MOCP CONDUCTOR AND RACEWAY PANEL

CIRCUIT

NUMBER

JOCKEY PUMP JOCKEY PUMP 1/2 480 V 3 1.1 A JOCKEY PUMP CONTROLLER 20 A (3) #12 AWG, #12 GND., 3/4" C. MDP-2 14,16,18 UH-2 UNIT HEATER 1/20 120 V 1 4.4 A RATED SWITCH 20 A (2) #12 AWG, #12 GND., 1/2" C. M 21 VF-1 VENT FAN 1/2 120 V 1 9.8 A SWITCH W/ THERMAL OVERLOADS 20 A (2) #12 AWG, #12 GND., 1/2" C. M 30

LIGHTING FIXTURE SCHEDULE

FIXTURE

TAG

LAMP BASIS OF DESIGN LIGHTING FIXTURE BASIS OF DESIGN

LAMP

TYPE

LAMP QTY

/ FIXTURE

NOMINAL

LUMENS

PER LAMP

CCT (K) DESCRIPTION MOUNTING MANUFACTURER MODEL

INPUT

LOAD

(W) A2 LED 1 3,200 4,000 1' x 2' CHAIN HUNG LINEAR LED FIXTURE

WITH CLEAR POLYCARBONATE LENS.

+10'-0" AFF DIALIGHT LPM3N4D2P 33

EM LED EMERGENCY LIGHTING UNIT. +7'-6" AFF LITHONIA ELM2-LED-SD 2

SHEET SPECIFIC NOTES

1 COORDINATE WITH EAFB ELECTRICAL SHOP AND UTILITIES TO PROVIDE PRIMARY

FUSE PROTECTION AT FUSE CUTOUTS TO HOLD IN 65A AT 7200V INDEFINITELY UNDER

FIRE PUMP LOCKED ROTOR CONDITION.

2 PROVIDE CONNECTION FROM FIRE PUMP CONTROLLER TO SHUNT TRIP MP-1 CIRCUIT

BREAKER IN MDP-2. CONTROLLER SHALL SHUNT TRIP ON LOW PRESSURE (AUTOMATIC

START CONDITIONS). SHUNT TRIP OPERATION SHALL NOT OCCUR ON PUMP START TO

AVOID CIRCUIT BREAKER RESET AFTER EVERY REQUIRED MAINTENANCE TEST.

NOT TO SCALEE001

1 ONE-LINE RISER DIAGRAM

*** DENOTES CIRCUIT BREAKER WITH SHUNT TRIP OPERATION.

Notes:

Total Est. Demand Current: 127 A Total Conn. Current: 126 A

Total Est. Demand: 105669 VA Equipment 99766 VA 100.00% 99766 VA Total Conn. Load: 104671 VA Motor 4905 VA 120.34% 5903 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 126 A 126 A 126 A Total Load: 34890 VA 34890 VA 34890 VA

17 -- -- -- 27713 305 -- -- -- 18 15 -- -- -- 27713 305 -- -- -- 16

13 ***MP-1 (100A) 200 A 3 27713 305 3 20 A JOCKEY PUMP 14

11 -- -- -- 5543 1330 -- -- -- 12 9 -- -- -- 5543 1330 -- -- -- 10

7 (E) PARTS CAGE 20 A 3 5543 1330 3 20 A (E) AHU-2 (3 HP) 8

5 -- -- -- 0 0 -- -- -- 6 3 -- -- -- 0 0 -- -- -- 4

1 (E) SPARE 60 A 3 0 0 3 60 A (E) SPARE 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: TYPE 1 MCB Rating: 300 A Mounting: SURFACE Wires: 4 Mains Rating: 400 A

Supply From: 225 KVA SERVICE TRANSFORMER Phases: 3 Mains Type: MCB Location: STORAGE 118 Volts: 480Y/277V A.I.C. Rating: 25,000

Panel: MDP-2

GENERAL ELECTRICAL NOTES

1.

A.

B.

C.

D.

E.

2.

3.

PROVIDE ELECTRICAL WORK AS SHOWN ON THE DRAWINGS AND GENERALLY

NOTED BELOW. ALL ELECTRICAL WORK AND MATERIAL IS NEW, AND PROVIDED BY

THE CONTRACTOR UNLESS OTHERWISE INDICATED.

REMOVE AND REINSTALL ELECTRICAL FIXTURES IN ROOM 25 XRAY VAULT

TO FACILITATE ADDITIONAL LEAD SHEILDING.

PROVIDE ADDITIONAL INTERLOCK SWITCH FOR DOUBLE DOOR TO ROOM

25 XRAY VAULT.

REMOVE AND REINSTALL ELECTRICAL FIXTURES IN ROOMS 109-111 TO

FACILITATE WORK ASSOCIATED FOR NEW FIRE SUPPRESSION SYSTEM.

PROVIDE SERVICE TO FIRE PUMP CONTROLLER AND ASSOCIATED

EQUIPMENT.

PROVIDE BRANCH CIRCUITS TO ELECTRICAL FIXTURES IN NEW FIRE PUMP

ROOM.

ALL SUPPORT PENETRATIONS INTO THE WALL AND CEILING SHALL USE

ASSOCIATED FASTENERS OF THE LEAD-LINED WALL ASSEMBLY AND INSTALLED

PER MANUFACTURER'S INSTRUCTION TO MAINTAIN PROPER PROTECTION OF THE

AREA.

FIXTURES DAMAGED DURING THE SALVAGE AND REINSTALLATION SHALL BE

PROVIDED NEW WITH SIMILIAR TYPE AND STYLE FIXTURE.

IS

M

XRAY VAULT

EXISTING XRAY INTERLOCK

SYSTEM CONTROL PANEL

EXISTING INTERLOCK

TERMINAL BOX

TYP. SALVAGED

LIGHT FIXTURE

XRAY ROOM

DARK ROOM

EXISTING MP-1

EXISTING

MP-1

DISCONNECT

TYP. SALVAGED LIGHT FIXTURE

LIQUID

PENETRANT

CHEMICAL

STORAGE

BEARING

CLEANING

(E)

(E)

WASH RACK

MECHANICAL

EXISTING

480V MAIN

DISTRIBUTION

PANEL

(MDP-2)

EXISITING 480V ELECTRICAL SERVICE EQUIPMENT

STORAGE

EXISTING 1200A,

208V SWITCHGEAR

EXISTING

PANEL M

TELEPHONE

AKAF AL

TS

TA

E O

49 TH

S

D E S I G N

A L

A S

K A

REGISTERED PROFESSIONAL ENGIN

EE

R

D ate

P roject N o.

A rchitects

E ngineers

S urveyors

601 C ollege R oad Fairbanks AK 99701 907.452.1241 designalaska.com

04 JA

N

FTQ

W

18-0203

A E

C C

S ht.

O f

354th C ivil E ngineer Squadron

E ielson A

FB

, A laska

P roject E ngineer

C hief E ngineer D raw n By

D esigned By

R eference

N o.

R ev

D escription

By D ate

E N

G

IN

E M A

IN

TE

N A

N C

E FA

C

ILITY

B

LD

G

03-Jan-2019

Jeffrey M. Leonelli

EE 107788

1/3/2019 2:53:07 PM

JM

L

ELECTRICAL DEMOLITION PLANS

E

JM

L

1/4" = 1'-0"E002

1 1ST FLOOR PLAN - ROOM 25 - DEMO

1/4" = 1'-0"E002

2 1ST FLOOR PLAN - ROOMS 109, 110, 111 - DEMO

SHEET SPECIFIC NOTES

1 REMOVE AND REINSTALL ALL ELECTRICAL CONDUIT,

JUNCTION BOXES, DEVICES AND FIXTURES AFFECTED BY

THE ARCHITECTURAL…