Questions and Responses 002.pdf

PDF 38 KB Posted

Attached to
RECOVERY-- FTQW071054 - Maintain Turbine Generator #4 (B6203)
Solicitation number
FA5004-09-R-C012
Issued by

About this file

Questions and Answers 002

View the file

Other files

File Type Posted
Amendment 0004.pdf PDF
JA-2 Wage Determination.pdf PDF
Amendment 0003.pdf PDF
SOW for Gen 4.doc DOC document
19 07-1054_Appendix 4 Foundation Drwng.TIF TIF image
Amendment 0002.pdf PDF
Questions and Responses 001.pdf PDF
Amendment 0001.pdf PDF
SOW for Gen 4.doc DOC document
JA-6 AF Form 66.xls XLS spreadsheet
Photos.pdf PDF
O M Manual Excerpts.pdf PDF
09-R-C012 Final.pdf PDF
JA-2 Wage Determination.doc DOC document
JA-3 Past Performance Questionaire - 2.doc DOC document
2003-2004 Overhaul Report.pdf PDF
JA-5 Haz Mat Sheet.doc DOC document
JA-4 Financial Reference Sheet.doc DOC document
Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions and Responses 002

Solicitation No. FA5004-09-R-C012

QUESTIONS AND RESPONSES

FOR

MAINTAIN TURBINE GENERATOR #4

AT

EIELSON AIR FORCE BASE, ALASKA

SOLICITATION NO. FA5004-09-R-C012

It shall be noted to all interested parties that the following questions have been received in writing regarding the subject acquisition. Additionally, responses have been provided to the below listed questions.

As a reminder, it is the responsibility of all Interested Parties to review this website

(http://www.fedbizopps.gov) frequently for any updates and/or amendments to any and all subject documents.

Question:

What is missing is the original pump data sheet for us to give (a) proposal to these two contractors. Would this information be available in the archives?

Response:

The Government was not able to locate the pump data sheet but here’s some information off the pump data plates:

Worthington

2-JZ-2 Pump

SN 1617646

Driver H.P. 10, 1750 RPM

TDH 140 FT.

GPM 120

The other pump is the same with SN 1617647. The pumps are redundant. Here is some more information that could help.

--Vacuum at the top of the water in the hot well is about minus 29 Inches H.G.

--Max condensate flow is around 75,000 to 80,000 lbs/hour at 5MW.

--Condensate temperature ranges between 70 to 100 degrees, but figure for about 130 max.

--The pump suction line is 4" and is only a few feet long (<10 ft).

--Hot well water level is controlled to about 46" above finished floor (AFF), but there is a mark on the site glass frame that seems to indicate low level alarm at about 37"

AFF. The pump would need to work efficiently at low level alarm conditions.

--Pump discharge and re-circ lines are 3" and the discharge line continues on to connect with the condensate lines from the other turbines and dumps into the main condensate tank which is located in another area of the basement. So, on the discharge side the pump is working against friction losses, head pressure and the other turbine condensate pumps, but there is an existing pressure gauge about 10 feet from the pump that is running today - the pressure gauge is at about 58" AFF - it reads 36 psig.