This federal contract opportunity solicitation requests kitchen hoods and ducts exhaust system inspection, preventive maintenance, cleaning, testing, and certification services to be performed at Joint Base Elmendorf-Richardson in Alaska. The contractor shall furnish all required labor, equipment, tools, materials, supplies, and certifications to repair, maintain, and inspect kitchen hoods and ducts exhaust systems in accordance with NFPA Standard 96, UFC criteria, and original manufacturer specifications, following all applicable national, state, and local fire, safety, health, and electrical codes. The services must ensure the exhaust systems are accountable solely to the contractor, who is responsible to the Department of the Air Force's Pacific Air Forces agency.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
JBER Hood and Duct Program
Basic diagrams and system components
Table of Contents
Mandatory Inspection Items and Safety….slides 3-4
Monitoring Grease Accumulation and Additional Checks…..slides 5-6
List of Facilities and Hoods….slide 7
** Mandatory Inspection Items **
Personal Protective Equipment
- Eye protection
- Boots (no tennis shoes)
- Uniform or Department issued coveralls
Equipment
- Flashlight
- Grease Comb
- Fall protection (as identified on facility slides)
- Snake camera (as identified on facility slides)
** Safety**
- Is your PPE properly worn
- Prevents contact with cleaning chemicals, burns, and cuts.
- Evaluate the safety of a scene prior to inspection
- Ensure the ladder is properly placed and secure
- Can you safety get on and of the ladder maintaining 3 points of contact
- Is the ladder tied off (not applicable to A-Frame ladders)
- Do you have fall protection (if required)
- Are hoods, cooking equipment, and vats cool and safe to work around
- Evaluate risks for slips, trips, and falls
- Summer = wildlife
- Winter = cold weather and ice/slippery surfaces (need for cold weather gear)
If you feel the situation is unsafe, do not put yourself at risk!
** Measuring Grease Accumulation ** When measuring for grease accumulation place the grease depth gauge comb against the hood or duct surface. Drag the comb slowly and level across the surface. Evaluate the grease level on the comb
** Additional checks **
- Is the cleaning tag signed by the contractor and affixed to the hood
- Are the hood suppression manual pull stations visible and unobstructed
- Is the suppression system charged, armed, and current on its inspection
- Are fusible links dates not more than 1 year old
- Look at the last system inspection. If the system was, for example, inspected in 2017 and there are 2015 fusible links, the links need to be changed. It would be possible to have a 2017 inspection and 2016 links depending on when the inspection occurred. Refer to NFPA 96, 11.2 and UFC 3-600-02 Table 2-19 for further guidance
Manufactured in 2009
Richardson CDC/SAP/YC DFACS Restaurants
Kodiak, 6 Slides 8-9 Wilderness, 647 Slides 27-40 Burger King, 9 Slides 55-56
Talkeetna, 11 10-11 Gold Rush, 655 41-45 Taco Bell , 560 57-58
Two Rivers, 297 12-13
Illa, 36100 14-15
Elmendorf CDC/SAP/YC DFACS Restaurants
Sitka, 6376 16-19 Iditarod, 8088 46-54 Dominos, 3805 59-60
Ketchikan, 7163 20-21 Popeye's, 5800 61-62 & 71
Katmai, 7181 22-23 Vacant 63-64 & 71
Denali, 7377 24-26 Dominos, 5800 65-66 & 71
Charlies, 5800 67-68 &71
Chicago's, 5800 69-71
Ten Pins, 7176 72-73
Burger King , 7508 74-76
Pico N' Salsa, 7535 77-82
Hillberg, 23400 83-84
Moose Run, 27000 85-86 7
Up-blast
Access
Access Hood
Kodiak CDC, 6
- Roof access by ladder, usually the north side
- Fusible link
- Drip pan
Nozzle
11 Feet
Roof line
Kodiak CDC, 6
Up-blast Access
Hood
Talkeetna CDC, 11
- Roof access by ladder
Fusible link Drip pan Nozzle
Roof line
9 Feet
Platform
East Side Exterior Roof Access
Talkeetna CDC, 11
Access Hood
Two Rivers YC, 297
- Roof access by ladder
- Fusible link
- Drip pan
Nozzle
11 Feet
Roof line
Fire Damper
West Side Exterior Roof Access 12
Two Rivers YC, 297 297, Two Rivers
Access
Above Ceiling Access
Access
Hood
Illa SAP, 36100
- Roof access mounted ladder on East side
Fusible link Drip pan Nozzle
- Fall protection required Roof line
Side view
Hood
Change of direction
10 Feet
6 Feet
3 Feet
East Side Exterior Roof Access
Platform
Illa SAP, 36100
Access panel under hood
Hood 1A
Sitka CDC, 6376
- Roof access not needed
- Duct access in mechanical room
- No roof upblast, system vented through HVAC system
- No drip pans, installed wash system
- Fusible link
Nozzle
Side view
Hood
2 Feet
Ceiling Line
HVAC Tie-in
Access through mechanical room on the North side then up to the second floor 16
Hood 1B
HRU
Hood 1A
Kitchen/Boiler Room wall
Ceiling Line
Access
Sitka CDC, 6376
2nd floor mezzanine
Sitka CDC, 6376
Ducting from hood into mechanical room
Hood vents through the Heat Recovery Unit, no roof up-blast or termination
From hood to ducting
Airflow
Sitka CDC, 6376
Access Hood
Ketchikan CDC, 7163
- Roof access by ladder
- Fusible link
- Drip pan
Nozzle
Roof line
10 Feet
East Side Exterior Roof Access 20
Ketchikan CDC, 7163
Katmai CDC, 7181
- Roof access by ladder
- Fusible link
- Drip pan
Nozzle
9 Feet
Roof line
West Side Exterior Roof Access 22
Katmai CDC, 7181
Access Panel (Mech Room)
Access panel under hood
Hood 1A
Denali CDC, 7377
- Roof access not needed
- Duct access in mechanical room
- No roof upblast, system vented through HVAC system
- No drip pans, installed wash system
- Fusible link
Nozzle
Side view
Hood
Change of direction
2 Feet
2 Feet
Ceiling Line
HVAC Tie-in Bulb Sprinklers
Denali CDC, 7377
Two access panels 2nd floor in mechanical room
Overhead View
View of hood above the ceiling wall Kitchen
Mechanical Room
6 feet behind first panel
1 2
Denali CDC, 7377
Wilderness DFAC, 647
- Roof access not needed
- Duct access in lading bay and men's locker room
- No roof upblast, system vented through HVAC system
- No drip pans, installed wash system
- Fusible link
Nozzle
Access
Ceiling line
Hood 5B
To HRU 5
Air Flow
Hood “5A, 5D” Hood “5B, 5C”
Side View
To HRU 5
Hood 5C
Access through loading dock HRUs 2-5
Access to HRU 1 in the men's locker room, ladder required
Ceiling line
Hood 5A
Air Flow
Hood 5D
To HRU 5
Wilderness DFAC, 647 Hood 5A, 5D Hood 5B, 5C
Hood 1J
Roof line
Hood I
To HRU 4 To HRU 4
Hood I Hood 1J
Hood 2H
Oven Conveyor
Oven Conveyor
To HRU 3
Roof Line
Hood 3F
Hood G
2To HRU 2 To HRU 2
Wilderness DFAC, 647
Wilderness DFAC, 647 Hood G Hood 3F
Hood 4E
2To HRU 1
Wilderness DFAC, 647
HRU
HRU
HRU
5 HRU
A = Duct access panel
L = Ladder Access
L
Access through male restroom/locker room.
Small extension ladder stored across hallway
Main Kitchen Hoods 5A, 5B, 5C, 5D
I and 1J
2H
G and 3F
4E
L
Dirty Air
Clean AirAccess
Contractor will ladder the roof from the serving side
Ducting down to hood
Wilderness DFAC, 647 Floor grates are removed for access
Contractor will ladder the roof from the serving side
Gold Rush, 655
- Roof access, interior ladder, Janitors closet 2
- Fusible link
- No drip pans, has installed water wash stations
Nozzle
Locked access door at top of ladder, CE197 key
Ceiling line
Hood 2D
To HRU 2 Hood “2A, 2D” Hood “2B, 2C”
Side View
To HRU 2
Hood 2A Change when ACA labels hoods. Drawing of left side stations Should bee hood 2A, B, C, D
2A 2B
2D
2C
2B and 2C are non-grease laden hoods
Hood 1A
To HRU 1
Ceiling Line
Roof Access
Return Air Hood Air
HRU 2
Hood 2
HRU 1
Hood 1
Iditarod DFAC, 8088
Hood
Ducting
Heat Recovery Unit (HRU)
Roof Fan
Roof Line
Ceiling Line
Air Flow
2nd Floor accessed through Mech room
Ceiling Space
Access through mechanical room on the North side, then up the ladder in the back
Mechanical Room
- HVAC access from Mech room on west side
Fusible link Nozzle
Ceiling line
Hood
Hood “1A, 1C” Hood “1B, 1D”
Side View
To HRU 1
Air Flow
To HRU 1
Hood 1A Hood 1B
Hood 1C Hood 1D
Up ducting from hood C and D
Up ducting from hood A and B
HRU 1 Ducting for hoods 1A, 1B, 1C, and 1D 2nd Floor Mech Room
Hood 2F Hood 2G Hood 2H
Vents to HRU Through Ceiling
Hood 2E
Access
HRU 2
Hood
5 feet
Pertains to all 3 hood stations52
Hood 2E Hood 2F Hood 2G Hood 2H
Serving Line Hoods
E F
Ducting for Hood E, F
Ducting for Hood G Ducting for
Hood H
Hoods A-D connection to exhaust ducting
Ducting leading up to HRU 1
Ducting leading up to HRU 2
Burger King, 9
- Roof access, ladder South side-
- Fusible link
- Drip pan
Nozzle
Roof access on West side
Up-blast
Access
Hood 1
9 Feet 9 Feet
Up-blast
Ceiling Line
Roof Line
Scope needed to look back an behind heat shield
Hood 2
Fryer
Hood 2
Ladder
Burger King, 9
Hood 1 Hood 2
Hood 1
Taco Bell, 560
- Building mounted ladder on South side
- Suppression tanks above ceiling
- Drip Pan
Fusible link Nozzle
Up-blast Access
Hood
12 Feet
2 Feet
10 Feet
Roof Line
Access
South Side Exterior Roof
Access panel in ceiling near hood
Taco Bell, 560
Dominos, 3505
- Roof access, ladder required South side
- No fire suppression system
Down-blast roof termination, south side
Down-blast Access
8 Feet
Roof line
Hood
Oven Conveyor
Oven Conveyor
Oven Conveyor
Ceiling Line
Dominos, 3505
Popeye's, 5800
- Roof access from stairwell on west side
- Fusible link
- Drip pan
Nozzle
Roof line
6 Feet
10 Feet
Cooking Area
Access
Void space that collects grease on both ends, removable covers
Popeye's, 5800
Vacant, 5800
- Roof access from stairwell on west side
- Fusible link
- Drip pan
9 Feet
Roof line
Information may not correct, system my move based on new tenants
Add photo when cooking area is occupied
Dominos, 5800
- Roof access from stairwell on west side
- Fusible link
- Drip pan
Nozzle
10 Feet
Roof line
Hood
Oven Conveyor
Oven Conveyor 65
Dominos, 5800
Access
Hood
Charley's, 5800
- Roof access from stairwell on west side
- Fusible link
- Drip pan
Nozzle
Roof line
10 Feet
Charley’s, 5800
Access
Hood
Chicago’s, 5800
- Roof access from stairwell on west side
- Fusible link
- Drip pan
Nozzle
Roof line
17 Feet
Chicago’s, 5800
Building 5800 Roof Top Terminations/Up-blast From the roof door vantage point roof access door
DominosCharlies Popeye’s Chicago's Vacant
Ten Pins, 7176
- Roof access, ladder South side- Fall protection required
- Fusible link
- Drip pan
Nozzle
Exterior access on South side
Up-blast
Access Roof line
20 Feet
Hood 1 Hood 2
Pizza Oven Grill
Ceiling Line
Hood 1, Grill side Hood 2, Pizza Side
Ten Pins, 7176
Fan Housing
Access
Hood
Burger King , 7508
- Roof access mounted ladder interior
Fusible link Drip pan Nozzle
Roof line
Side view
Hood
Change of direction 8 Feet
10 Feet
2 Feet
To Roof
Access
Fan
Ceiling
Access to roof 74
Access above ceiling
7508 Burger King
7508 Burger King
Pico N’ Salsa, 7535
- Roof access, exterior West side
- Fusible link
- No drip pans, has installed water wash stations
Nozzle
Roof access on West side
Hood 1A Hood 1B
Side View
To HRU
Ceiling line
Hood 1A
Ceiling line
Hood B
Pico N’ Salsa, 7535
Platform and Ladder
Access port under ladder
Access
Hood
Hillberg, 23400
- Roof access, ladder north side
- Fusible link
- Drip pan
Nozzle
Roof line
16 Feet
North Side Exterior Roof Access 83
Hillberg, 23400
Access
Hood
27000, Moose Run
- Roof access North side, need a ladder
Fusible link Drip pan Nozzle
Roof line Platform
9 Feet
North Side Exterior Roof Access 85
27000, Moose Run
| JBER Hood and Duct Program |
| Table of Contents |
| Slide Number 3 |
| Slide Number 4 |
| Slide Number 5 |
| Slide Number 6 |
| Slide Number 7 |
| Slide Number 8 |
| Slide Number 9 |
| Slide Number 10 |
| Slide Number 11 |
| Slide Number 12 |
| Slide Number 13 |
| Slide Number 14 |
| Slide Number 15 |
| Slide Number 16 |
| Slide Number 17 |
| Slide Number 18 |
| Slide Number 19 |
| Slide Number 20 |
| Slide Number 21 |
| Slide Number 22 |
| Slide Number 23 |
| Slide Number 24 |
| Slide Number 25 |
| Slide Number 26 |
| Slide Number 27 |
| Slide Number 28 |
| Slide Number 29 |
| Slide Number 30 |
| Slide Number 31 |
| Slide Number 32 |
| Slide Number 33 |
| Slide Number 34 |
| Slide Number 35 |
| Slide Number 36 |
| Slide Number 37 |
| Slide Number 38 |
| Slide Number 39 |
| Slide Number 40 |
| Slide Number 41 |
| Slide Number 42 |
| Slide Number 43 |
| Slide Number 44 |
| Slide Number 45 |
| Slide Number 46 |
| Slide Number 47 |
| Slide Number 48 |
| Slide Number 49 |
| Slide Number 50 |
| Slide Number 51 |
| Slide Number 52 |
| Slide Number 53 |
| Slide Number 54 |
| Slide Number 55 |
| Slide Number 56 |
| Slide Number 57 |
| Slide Number 58 |
| Slide Number 59 |
| Slide Number 60 |
| Slide Number 61 |
| Slide Number 62 |
| Slide Number 63 |
| Add photo when cooking area is occupied |
| Slide Number 65 |
| Slide Number 66 |
| Slide Number 67 |
| Slide Number 68 |
| Slide Number 69 |
| Slide Number 70 |
| Building 5800 Roof Top Terminations/Up-blast�From the roof door vantage point |
| Slide Number 72 |
| Slide Number 73 |
| Slide Number 74 |
| Slide Number 75 |
| Slide Number 76 |
| Slide Number 77 |
| Slide Number 78 |
| Slide Number 79 |
| Slide Number 80 |
| Slide Number 81 |
| Slide Number 82 |
| Slide Number 83 |
| Slide Number 84 |
| Slide Number 85 |
| Slide Number 86 |
File details come from the government source that posted it. Updated .