UPDATE

FA4877-16-Q-0006

ELEVATOR MAINTENANCE SERVICE

QUESTIONS/ANSWERS

1) Question: Other federal installations require bi-annual certifications via a QEI; it was not stated in this PWS, is this a requirement for DMAFB?

Answer: Yes, please reference PWS paragraph 4.4. (below)

4.4. The contractor shall perform necessary inspections and tests as required under ASME A17.1 Appendix N, using a Qualified Elevator Inspector (QEI). The first annual test shall include the five-(5)-year test for all traction and roped hydraulic elevators regardless of due date. The three- (3) - year test shall be scheduled in conjunction with the annual test two years later from the first annual test.