Q&A Pt. 3 – B9545 – FA481920R0023
1) General conditions - 6.9 On-Site Field Oversite only mentions general requirements. What is the expectation of the customer? – Three separate site Superintendent, SSHO, and QCM or can a single person be Superintendent/SSHO/QCM?
This is a small job, there must be a supervisor (1) overseeing the work, safety, and scheduling… The QA (inspection of the work) must be performed by their license subcontractor supervisor (must be experience qualified)….
2) Page 9 of 28 Roofing: calls for a flat built up roof with structural metal decking; however, some of the QA seem to think this is a metal roof-Can you confirm Built -up is correct
“suggest metal roof”, roofs must meet Miami Dada code wind standards, the contractor must include in their proposal the type of roof.
3) The SOW is requesting 12’x15’ roll-ups but the eave height requested is only 14’-Canyou confirm correct door size or eave height?
The estimate height of the building is 14’ – The doors are 15’ Wide and 12’ tall.