Q_and_A_(30_Jun_14).docx

DOCX document 37 KB Posted

Attached to
Fire Extinguisher Inspection Services
Solicitation number
FA4803-14-T-0002
Issued by

About this file

As a result of the solicitation for the Fire Extinguisher Inspection an Interested Party submitted Questions requiring Answers

View the file

Other files

File Type Posted
TO_13F4-4-121.pdf PDF
Flight_Line_Fire_Ext_PWS_28_May_14_Revision_1.doc DOC document
20_CONS_QASP__24_Mar_14_(signed).pdf PDF
FA4803-14-T-0002-0001 _Fire_Extinguisher_Inspection_Amendment.doc DOC document
Q_and_A_(26_Jun_14).docx DOCX document
FY14_Inspection_List_(Autosaved).pdf PDF
FA4803-14-T-0002 _Fire_Extinguisher_Inspection.doc DOC document
FA4803-14-T-0002 _Fire_Extinguisher_Inspection.doc DOC document
WD_Rev_15.pdf PDF
Flight_Line_Fire_Ext_PWS_28_May_14.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DEPARTMENT OF THE AIR FORCE

20TH CONTRACTING SQUADRON

SHAW AFB SOUTH CAROLINA

30 June 2014

MEMORANDUM FOR Q&A

FROM:20 CONS/LGCB
321 CULLEN ST
SHAW AFB SC 29152

SUBJECT: As a result of the solicitation for the Fire Extinguisher Inspection – An Interested Party submitted Questions requiring Answers.

Question 1: Is the base providing a closed pump loop system for transfer of the Halon (similar to Remtec M1)?

i. Answer: Shaw FES will not provide closed pump loop system for transfer.

Question 2: For those extinguishers needing a Hydro testing will we be able to take off the base for testing?

i. Answer: As previously stated Extinguishers requiring Hydro testing will be condemned and replaced.

Question 3: Can we get clarification for AFOSH 91-506, and TO 13F4-4-121 regulations?

i. Answer: Remove reference AFOSH 91-506, TO 13F4-4-121 is the maintenance Technical Order for wheeled HALON extinguishers. TO 13F4-4-121 is provided below.

Question 4: Just to be clear, this is for 111 wheeled extinguishers with 4 option years to renew?

i. Answer: Yes.

Question 5: Our pricing should include inspection, maintenance, refurbishment, and recharging? i. Answer: Inspection, Maintenance, and Recharging as needed.

2. If you have any questions concerning this memorandum, please contact SSgt Derek Sampson at derek.sampson@shaw.af.mil or via telephone at (803) 895-5385 or SrA Karl Deffert at karl.deffert@shaw.af.mil or via telephone at (803) 895-5380.

DEREK D. SAMPSON, SSgt, USAF
Contracting Administrator

image1.wmf