Question and Answer Pool_CE_Answered 8 May 2025.docx

DOCX document 15 KB Posted

Attached to
Langley CDC Kitchen Exhaust Hood Federal contract opportunity
Solicitation number
FA480025QA067
Issued by
Department of the Air Force Air Combat Command

About this file

The document is a Question and Answer Pool for Solicitation FA480025QA067, a small business set-aside contract for a kitchen exhaust hood package at Langley Air Force Base. The 633d Contracting Squadron is seeking new kitchen exhaust hood equipment with a required delivery date of 45 days after receipt of order (ARO). A mandatory site visit is scheduled for 9:30 am EST on 5 May 2025 at 74 Burrell Loop Building 61 JBLE Langley, VA, with vendors required to pre-register by providing attendee details by noon on 1 May 2025.

Vendors must submit any clarification questions to Mrs. Sharmayne Brown and Ms. AnnMarie Shields via email by noon on 6 May 2025, and quote submissions are due by 4:00 PM EST on 9 May 2025. The solicitation specifies that all items must be new, with no refurbished or used equipment accepted. The opportunity is issued by the Department of the Air Force Air Combat Command, and site visit attendees must bring a hard hat and vest as the location is an active construction site.

View the file

Other files for this federal contract opportunity

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Question and Answer Pool Contract Opportunity – 633d FSS Kitchen Exhaust Hood Current as of 8 May 2025

All answers should reflect in the Statement of Work (SOW).

1. Is a Stainless Steel Back Splash required as a part of the hood package? If so, what is the size required?

Answer: Backsplash shall be required. Assuming an installation elevation of 6’6” (or based upon manufacturers recommendation) the backsplash shall measure the length of the hood and run down to an elevation of 18” above finished floor elevation.

2. Can you verify the fan size, make, model, and if a VFD is required?

Answer: Fan is 1200 CFM, Greenheck CUE-120-A. No VFD is required. 1725 RPM 115v/60hz/single phase.