Amendment 2 - 7 CES Pump Station Questions.docx
DOCX document 16 KB Posted
- Attached to
- 7 CES Lift Station Pump
- Solicitation number
- FA466125Q0084
About this file
This document is an Amendment 2 detailing technical specifications for a lift station pump solicitation from the Department of the Air Force Global Strike Command at Dyess AFB, Texas. The pump requirements include a submersible sewage pump (HOMA AMX3343.0TFM model) with specific technical parameters: 3" discharge diameter, single-phase 208V power, 32-foot minimum power cable, and a duplex system capable of handling wastewater with solids ranging from toilet paper to human waste. Operating conditions include ambient temperatures of 70-110 degrees, a head range of 25-45 feet, and a discharge length of 15-30 feet.
The solicitation (FA466125Q0084) is for pump acquisition without installation, with key dates including a question submission deadline of 6 May 2025 at 10:00 a.m. CST and quote submission deadline of 9 May 2025 at 10:00 a.m. CST. Vendors should submit questions and quotes via email to jaython_anthony.quichocho@us.af.mil and maren.quinones-burgess@us.af.mil. The pumps will be used in a waste management application with standard warranty terms, and the technical specifications are based on meeting specific operational requirements for the lift station.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFQ FA466125Q0084 Amendment 1.pdf | ||
| FA466125Q0084 Provisions and Clauses.docx | DOCX document | |
| RFQ FA466125Q0084.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
7 CES Pump Station Questions
Is there an actual model # in the bid advertisement ? Or of a pump they are replacing?
Model number is based off specifications. HOMA (Submersible sewage pump) AMX3343.0TFM.
if you could please provide us with the FOH/psi needed for the application, the type of fluid being pumped, and any other info like specific gravity, etc, No necessary PSI applicable, the fluid will be semi-solid.
What is the total discharge length that you are pumping?
Discharge length begins at the bottom of the lift station and ends at sewer entrance. Typically 15 – 30 feet.
What is the elevation difference between the surface level of the water and the end of the discharge line?
Waste management application. 15 – 30 feet minimum.
What is the discharge diameter?
The diameter of the discharge line is 3”.
Are there any bends or elbows in the line?
2. At the top and at the bottom.
What is the pH level of the fluid?
Its wastewater. Uknown.
If acidic, what type of acid is present?
Unknown. Not for use in chemical situations.
What is the ratio of acid to water?
Unknown.
What is the temperature of the fluid being pump?
Ambient temperature ranging from 70 to 110, depending on the season.
Are there any solids that we need to pass? If so please describe nature and size?
Solids range from toilet paper to human waste. Variable shapes and sizes.
What are the dimensions of the area you want to pump? (length x width x depth of material are you looking to remove?
Lift station ranges from 15 – 30 feet, with 2 pumps needed.
What type of electric power are you operating off of?
Alternating Current. (AC)
Is there a minimum flow or rate that must be met?
Only needs to meet standards met from specifications.
What Phase does your pump need single or three phase?
Single.
What Voltage does your pump need 115, 230, 460, 575?
208 V
What is the head (Pounds per Square Inch or Total Dynamic Head/Feet)?
Ranges from 25 – 45 feet of head.
How many ft in power cable does your pump need 30, 50, or 100?
32 feet minimum.
Is this for a duplex or simplex system?
Duplex system.
Do you need a control panel?
Negative.
Do you need a guide rail adapter or a complete built guide rail system?
Negative.
Do you need an adapter such as elbow adapters to change pumps from Ansi Flanged to NPT?
Negative.
Will you require the coupling / element for each pump and motor connection?
Negative.
What is the required warranty?
Standard warranty
File details come from the government source that posted it. Updated .