Floor Plan.pdf

PDF 2 MB Posted

Attached to
Chapel Sanctuary Lighting Upgrade
Solicitation number
FA466124Q0076
Issued by

About this file

The provided document is a floor plan for the Chapel Sanctuary Lighting Upgrade project at Dyess AFB, TX. The floor plan indicates the location to install a new lighting controller, along with details on the existing electrical infrastructure such as a 400A, 120/208V, 3-phase, 4-wire fusible main disconnect switch and a 1000W photocell sign at the front of the church.

The related federal contract opportunity is a solicitation (Solicitation Number FA466124Q0076) issued by the Department of the Air Force Global Strike Command for the Chapel Sanctuary Lighting Upgrade project. The scope of work includes removing old lighting and replacing it with new lighting fixtures and spotlights/floodlights. Interested offerors must provide a complete and signed Page 3 & 4 of the RFQ COMBO, FAR 52.212-3 Offeror Representations and Certifications paragraph b, and computer-generated photometric plans. Offers must be valid until September 30, 2024, and submitted by 10:00 CST on August 22, 2024.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1171701259C Polygon

1171701259C Typewritten Text

1171701259C Typewritten Text

7 INSTALL NEW LIGHTING

CONTROLLER IN THE AREA

INDICATED.

1171701259C Callout Install the new lighting controls with the existing sound board in this location (clouded) Verify with the end-user.

1171701259C Polygon

1171701259C Polygon

1171701259C Typewritten Text

CAPT. M. DAVIS

1171701259C Typewritten Text 08-21-24

L r

PULL BOX

� Ex. CIRCUIT I ,,---., I

TO PARKING

LOT LIGHT

EX. 400A., 1201208V., 30, 4W,

FUSIBLE MAIN DISCONNECT SWITCH

EX. SIGN AT

FRONT OF CHURCH

1ooow. PHOTO-

EX. 400A, 1201208V.,

30, 4W FUSIBLE

PANELBOARD--�.._

rr= J, 1' _

ELEC. CONTROL

,r

- 3011 DISCON.

,,.,,...-PRE-CAST CONG.

Iw•

PULL BOX

MECHANICAL RM

BLDG. 6220

2-#B'S, 2-#10'S, I u

/2-#B'S, 1-#10 GND., 1" C.

I II fl

/ / 1-#10 GND., 1" C.

2-#8'S, 3-#6'S, 1-#10 GND., 2" C.

2-#10'S, 1-#10 GND., 1" C. __,/

2-#10'S, 2-#8'S, 2-#8'S, 3-#6'S, 1-#10 GND., 2" C.

�_____,,___( 3--#6'S, 2-#B'S, 1-#10 GND., 1-1/4" C.

I

16220 I

1112.5 I

z

UNDERGROUND

PRIMARY CKT �c:::_t---_

4-500 MGM'S, 1-#3 GND., 4" C. __,,

4-350 MGM'S, IN EA OF 2-3" C.

OUTDOOR ELECTRICAL

ENCLOSURE

,<--PANEL 6220

.1---t-NEW 25013 rC., BREAKER@

I

I ,,-EX. 1201208V, 30, 4W MAIN

V PANELBOARD WITH 200A

MAIN BREAKER

MECHANICAL RM

BLDG. 6219

EX. 1201208V, 30, 4W

LIGHTING AND POWER PANEL

,,-NEW 1201208V, 30, 4W

/ PANELBOARD, 250A

MECHANICAL

ROOM - 120

4---------------�"'-- EX. 4-#3IO'S, 1-#6 GND., 2-1/2" C.

...---1-2/0 GND. ROD

- '-----4-250MCM'S, 1-#4 GND., 3" C.

NOTES INDICATED BY NUMBER IN O

1. PROVIDE NEW BREAKER IN "SPACE" OF EXISTING PANEL. BREAKER SHALL BE OF THE SAME

MANUFACTURER AS THE PANEL AND SHALL HAVE AN INTERRUPTING RATING NOT LESS

THAN THAT OF THE EXISTING BREAKERS IN THE PANEL.

ELECTRICAL SINGLE LINE DIAGRAM - BLDG. 6220/6219

SCALE: NONE

ELECTRICAL SYMBOL LEGEND PANEL "LA" LIGHTING FIXTURE SCHEDULE

SYMBOL

4:1

:Im

�Fl

Q)

G.F.I.

W.P.

IO

DESCRIPTION

SPST WALL SWITCH

(SWITCHING FIXTURES WHERE "a" IS INDICATED)

3-WAY SWITCH

4-WAY SWITCH

MOTOR RATED SWITCH

DUPLEX RECEPTACLE - IN WALL +18" A.F.F. OR AS

NOTED.

DEDICATED 20A, DUPLEX RECEPTACLE, WALL MOUNTED

AT +18" A.F.F. OR AS NOTED

DUPLEX RECEPTACLE

SUBSCRIPT "GFI" INDICATES GROUND FAULT TYPE:

DOUBLE DUPLEX RECEPTACLE, WALL MOUNTED AT

+18" A.F.F. OR AS NOTED.

FLOOR MOUNTED DUPLEX RECEPTACLE

ELECTRIC MOTOR

HP RATED DISCONNECT SWITCH

CONTROLLER, MAGNETIC

SURFACE MOUNTED PANELBOARD

RECESSED MOUNTED PANELBOARD

JUNCTION BOX WITH COVER

GROUND FAULT INTERRUPTER

"W.P." BY ANY ELECTRICAL DEVICE SYMBOL INDICATES

THAT THE DEVICE IS TO BE WEATHERPROOF

CONDUIT "HOME RUN" TO PANEL (HASH MARKS

INDICATE THE NUMBER OF CONDUCTORS

2x4 FLUORESCENT LIGHTING FIXTURE (TYPE "A")

CEILING MOUNTED

DOWNLIGHT FIXTURE/CEILING MOUNTED

WALL MOUNTED LIGHT FIXTURE

EMERGENCY EXIT LIGHT

COMBINATION TELEPHONE AND DATA OUTLET

BOX, WALL MOUNTED 18" A.F.F., WITH 112" C. &

PULL STRING TO ABOVE CEILING

TELEPHONE OUTLET BOX, WALL

MOUNTED 18" A.F.F., WITH 112" C. &

PULL STRING TO ABOVE CEILING

TV CABLE OUTLET BOX, ALL MOUNTED 18" A.F.F.,

WITH PULL STRING TO ABOVE CEILING

EXISTING DUPLEX RECEPTACLE

EXISTING COMBINATION TELEPHONE AND DATA

OUTLET BOX

EXISTING TV CABLE OUTLET BOX

SERVICE: 1201208V., 30, 4W.

MINIMUM CIRCUIT BREAKER

INTERRUPTING CAPACITY

10,000 A.

CONDUCTOR COLOR CODE

LEG 1 - BLACK

LEG 2 - RED

LEG 3 - BLUE

GROUND - GREEN

GROUNDED

LOAD

M. L. 0. BUS RATING: 250 A.

SEPARATE GROUNDING

BAR 35%

MARK MANUFACTURER AND CAT. NO. FIXTURE TYPE

A

A1

B

LITHONIA 2SP8 G 2 32 A12 MVOLT GEB10IS FLUORESCENT

LITHONIA 2SP8 G 2 32 A12 MVOLT GEB10IS EL FLUORESCENT

RESERVED

MTG. LAMP TYPE

LAY-IN 2 - 32W TS (48")

LAY-IN 2 - 32W TS (48")

REMARKS

#12 ACRYLIC LENS, NOTE 1

#12 ACRYLIC LENS, NOTE 1,2

PANEL MAY BE TOP OR

BOTTOM FEED AT

CONTRACTORS OPTION

NEUTRAL - WHITE -MAIN BREAKER OR

MAIN LUGS ONLY

AS INDICATED

MAIN BREAKER RATING: - C

__ -__ .A. SYM. INTER. CAP. D

LITHONIA CA 2 32 MVOL T GEB10IS FLUORESCENT

HALO M200 720 20P METAL HALIDE

SURFACE 2 - 32W T8 (48")

RECESSED 1 - 50W

MOUNT 8'-0" A.F.F., NOTE 1

NOTE S

POLE

NO.

SERVES t---�L=O�A=D __ +-B=R=E=A=K=E�R'-' POLE 1 2 3 POLELEG AMPS

1 LIGHTS - 113-116 9

3 LIGHTS - 117-119

5 LIGHTS - 112, 120-124

7 EXTERIOR LIGHTS 4

9 EXIT LIGHTS

11 RECEPT. - 111-113

13 RECEPT. - 113 6

15 RECEPT. - 114,115

17 RECEPT. - 114,115

19 RECEPT. - 115,116 6

21 RECEPT. - 115,116

23 RECEPT. - 116

25 25

27 WATER HEATER

31 UNIT HTR. #1-12 10

35 EXH. FAN #1-12,#2-12

37 EXH. FAN #3-12 2

39 SPACE ONLY

41 TEMP. CONTROL PNL

2 3 POLES

35 /

25 / 3 20 ./

3 2011

1 2011

NO.

NOTES:

1. PROVIDE GFI BREAKER.

2. PROVIDE "HACR" CIRCUIT BREAKER.

SEAL PER

SPECIFICATION

FOR NON-FIRE RATED

WALL ASSEMBLY

FIRE SEALANT, 3M

FIREDAM 150

CLASSIFIED PER ASTM

E814 (UL 1479) AND

ASTM E119 {UL263)

WHERE REQUIRED FOR

�----�--�-·;·"�·-a-t,,./\'_;·-·,�-,_.'._ F

IR

E

RA

TED ASSEMBLY

PIPE SLEEVE TO

BE 2 PIPE SIZES

LARGER THAN PIPE

DETAIL

,i ·:.;,-"',r'l"';S

,,,-WALL

NO.

0 TYPICAL PIPE THRU WALL PENETRATION

SCALE: NONE

E LITHONIA LQM SW3R 120/277 ELN LED SURFACE FURN. W/ UNIT NOTE 3

SERVES

t----L�O~A~D-___,rB~R=E~A~K-ER'-'-7 P0LE LEG AMPS F LITHONIA TWR1 100M 120 PE LPI METAL HALIDE SURFACE 1 - 100W MOUNT 9'-0" A.F.G., NOTE 4,7

RECEPT. - 117

t--1�-2�-3---,,.....-,p�o-L=E=s---< NO.

6 2W1 2 G LITHONIA CA 1 17 MVOLT GEB10IS FLUORESCENT SURFACE 1 - 17W T8 (24") MOUNT ABOVE DOOR, NOTE 1

RECEPT. - 117 6 2011 4 H LITHONIA LF6N 1126TRT F601AZ MVOLT FLUORESCENT RECESSED 1 - 26W TRT TRIPLE TUBE COMPACT FLUOR.

RECEPT. - 117,118

RECEPT. - 118,119

RECEPT. - 118,119

RECEPT. - 118,119

RECEPT. - 119

RECEPT. - 120,124

RECEPT. - 121-123 (1)

ELEC. WTR. COOLER (1)

EXTERIOR RECEPT. (1)

SPARE

A.H.U. #1-12

HEAT PUMP #1-12 (2)

SPACE ONLY

SPACE ONLY

SPACE ONLY

GRADE

2011 6 2011 8 2011 10 2011 12 2011 14 2011 16 2011 18 2011 20 2011 22 2011 24

80 / 26

HALO H745ICAT457P INCANDESCENT

J NOT USED

K HALO H745ICAT457SC INCANDESCENT

L LITHONIA M 2 32 A12 MVOLT GEB10IS FLUORESCENT

NOTES:

1. HIGH FREQUENCY, INSTANT START, ELECTRONIC BALLAST.

RECESSED 1 - 75W PAR30IFLOOD NOTE 5

RECESSED 1 - 75W PAR30ISPOT NOTE 6

SURFACE 2 - 32W T8 (48") NOTE 1

2. PROVIDE WITH LITHONIA PSL600 (900-1325 LUMEN) EMERGENCY BATTERY PACK FOR ONE

(1) LAMP EMERGENCY OPERATION. BATTERY PACK SHALL PROVIDE A MINIMUM OF 90

MINUTES OF ILLUMINATION UPON LOSS OF NORMAL POWER. PROVIDE WITH ELA RTS3

REMOTE TEST SWITCH AND PILOT LIGHT.

72 / 3 30 3. PROVIDE WITH NICKEL CADMIUM BATTERY BACKUP - OPERATION ON LOSS OF POWER.

50 /

34 / 3

4. PROVIDE WITH PHOTOELECTRIC CELL - BUTTON TYPE.

5. ADJUSTABLE FOR SLOPED CEILING IN T-BAR CEILING SYSTEM. 75 WATT PAR30 FLOODLIGHT.

6. ADJUSTABLE FOR SLOPED CEILING IN T-BAR CEILING SYSTEM. 75 WATT PAR30 SPOTLIGHT.

7. UL LISTED FOR WET LOCATIONS.

8. UL LISTED FOR DAMP LOCATIONS.

illl'm'1J11�

= BACKFILL ACCORDANCE

y� WITH SPECIFICATIONS

....--NOTE 3

-'-+-----.L/ 1 _,....-PVC CONDUIT BASE

� V SPACER, TYPICAL

§i.i j/"�0-/

I

CONCRETE

"¾ �� ENCASEMENT

>-------+---'-' •--� DUCT LINE NOTES:

1" 1. PROVIDE 2" CONDUIT EXCEPT WHERE OTHER SIZE IS

r-:J L7 !£ SPECIFICALLY INDICATED. WHERE OTHER SIZE IS

· (1,:----...J

INDICATED, PROVIDE PVC CONDUIT SPACERS FOR

2" PVC CONDUIT ---di, I)-- CONDUIT OF THE SIZE INDICATED. ENCASEMENT REFER TO NOTE 1-----t--f-:' 1o DIMENSIONS OUTSIDE SPACERS TO REMAIN THE

2-112"J t:::i 2::J . � SAME REGARDLESS OF CONDUIT AND SPACER SIZES.

1i�l�-

1•112" L2-112"

2. NOT USED

3. CONTINUOUS 5 MIL PLASTIC MARKER TAPE; REFER

TO SPECIFICATIONS.

DETAIL

1 WAY DUCT LINE

4. CONDUIT SPACERS TO BE MAX. 5'-0" 0.C.

SCALE: NONE

r I "AS BUil TS"

I

VOLTAGE

Sequeo:eKlllllOO"

DYESS

Air Force Base

TEXAS

APPROVED

SIGNATURE OFFICE

BASE CIVIL

ENGINE.ER

CHIEF OF

ENGINEERING

CHIEF OF

DESIGN

COORDINATION

CEO

GROUND

SAFETY

COMMUNICATIONS

BIOENVIRONMENTAL

ENGINEER

SECURITY

POLICE

FIRE CHIEF

CONSTRUCTION

MANAGEMENT

CORROSION

ENGINEER

<El

USING

AGENCY

USING

AGENCY

USING

AGENCY

DESIGN FIRM

WTA, INC.

CONSUL TING ENGINEERS

FIRM REG. NO. F-3651

THE ORIGINAL SIGNED AND

SEALED COPY OF THIS DRAWING

IS ON FILE AT THE OFFICES OF

WTA, INC.,

ONE VILLA GE DRIVE, SUITE 500,

ABILENE, TEXAS, 79606

THIS ELECTRONIC COPY IS

RELEASED FOR USE ON THE

REFERENCED PROJECT ONLY,

UNDER THE AUTHORITY OF LLOYD

G. TURNER, TEXAS P.E. #44724 ON

20 APRIL, 2012, USE OF THIS

DOCUMENT OR REPRODUCTION

OF THIS DOCUMENT FOR OTHER

PROJECTS WITHOUT THE

CONSENT OF LLOYD G. TURNER,

P.E. IS PROHIBITED AND IS A

VIOLATION OF THE ENGINEERING

PRACTICE ACT.

WTA11089

GJH

Project Manager

LGT

GJH 04-20-12

REVISION BY/DATE

SHEET TITLE

ELECTRICAL SINGLE LINE

DIAGRAM AND DETAILS

SHEET

E-4

OF

PROJECT TITLE

CONSTRUCT ADDITION

TO CHAPEL ANNEX,

BLDG. 6220

l'rojoj N,mm

Drawing Nlllllher

FNWZ 08-0083A

FNWZ 08-0083B

Facility NIDllber

E-2.2
E-2.3
E-4

File details come from the government source that posted it. Updated .