Atth 2- JFSD200909 100 Drawings.pdf
PDF 13 MB Posted
- Attached to
- HVAC Repair Federal contract opportunity
- Solicitation number
- FA4659-10-R-0029
About this file
Drawings
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment 0001 - Change Site Visit Date 10-R-0029.doc | DOC document | |
| FA4659-10-R-0029.rtf | RTF text file | |
| Atth 5-Financial Institution Reference Sheet - Offeror.doc | DOC document | |
| Atth 1- JFSD200909 Specifications.pdf | ||
| Atth 4- Past and Present Past Performance Questionnaire 10-R-0029.doc | DOC document | |
| Atth 3- JFSD200909 Material Submittal Schedule.pdf | ||
| Atth 6 - Climatological Data.pdf | ||
| Solicitation Cover Letter R-10-0025.doc | DOC document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REPAIR HVAC - GROUND SOURCE HEAT PUMP
COMMUNICATION SQUADRON HEADQUARTERS
JFSD 200909
"ISSUED FOR BID/CONSTRUCTION"
NORTH DAKOTA
GRAND FORKS AIR FORCE BASE
18" Rcp Inv. 891.80
18" Rcp Inv. 891.81
Existing Antenna
Gas Meter
San Mh.
Toc. 894.90 Inv. 882.90
San Mh.
Toc. 894.18 Inv. 882.68
San Mh.
Toc. 894.13 Inv. 883.23 Existing Sanitary Sewer
Existing Sanitary Sewer
E xi st in g Sa ni ta ry S ew er
Benchmark Top Nut on Hydrant
Elev. 896.52
893 892
895 895
135.5
53.5
80.9
50.5
10.5
0.
.5
.5
Bituminous Pavement
Bituminous Pavement
B itum inous P avem ent
Concrete Sidewalk
Concrete Sidewalk
Concrete Sidewalk
C oncrete Sidew alk
MARK T.
JASTER
DATE
18" Rcp Inv. 891.80
18" Rcp Inv. 891.81
Existing Antenna
Gas Meter
San Mh.
Toc. 894.90 Inv. 882.90
San Mh.
Toc. 894.18 Inv. 882.68
San Mh.
Toc. 894.13 Inv. 883.23 Existing Sanitary Sewer
Existing Sanitary Sewer
E xi st in g Sa ni ta ry S ew er
Benchmark Top Nut on Hydrant
Elev. 896.52
135.5
53.5
80.9
50.5
10.5
0.
.5
.5
Bituminous Pavement
Bituminous Pavement
B itum inous P avem ent
Concrete Sidewalk
Concrete Sidewalk
Concrete Sidewalk
C oncrete Sidew alk
0-33.5 3/4" 0-3.5 33.6-67 1" 3.6-7.0 67-124 1-1/4" 7.1-13.0
125-209 1-1/2" 13.1-19.0 210-428 2" 19.1-45.0 429-665 2-1/2" 45.1-70.0 666-1235 3" 71-130
1236-2565 4" 131-270 2566-4750 5" 271-500 4751-7600 6" 501-800 7601-15675 8" 801-1650
NOTES:
(1) BASED ON TYPE L COPPER PIPE
(2) 20 DEG TEMPERATURE DROP
HOT WATER SIZING SCHEDULE
MBH SUPPLY AND
RETURN
GPM
EXPANSION TANK (ET) SCHEDULE
PLAN
DESIGNATION
SERVICE TYPE
BASIS OF
DESIGN
MANUFACTURER
BASIS OF
DESIGN
MODEL
TANK
VOLUME
(GAL)
ACCEPTANCE
VOLUME (GAL)
MAX SYSTEM
PRESSURE
(PSIG)
QTY NOTES
ET-1 GROUND LOOP BLADDER B&G B-200 53 53 125 1 (1)
NOTES:
(1) SIZE TANK BASED ON 20% PROPYLENE GLYCOL
PLAN
DESIGNATION
SERVICE LOCATION
BASIS OF
DESIGN
MANUFACTURER
BASIS OF
DESIGN
MODEL
INLET
SIZE
OUTLET
SIZE
FLOW
RATE
(GPM)
PRESSURE
DROP (FT)
NOTES
AS-1 GROUND LOOP RM 160 SPIROVENT VDT600 6 6 330 1.25 (1)(2)
NOTES:
(1) MAXIMUM WORKING PRESSURE 125 PSI
(2) BRACKET SUPPORTS
(3) SIZE TANK BASED ON 20% PROPYLENE GLYCOL
AIR SEPARATOR (AS) SCHEDULE
REHEAT COIL
HEATING
FLOW
RATE (CFM)
MINIMUM
COIL AREA
(ft2)
MAXIMUM FACE
VELOCITY
(FPM)
MINIMUM
ROWS
EAT
(°F) LAT (°F)
FLOW
RATE
(GPM)
EWT
(°F)
LWT
(°F) MBH COIL ACV TOTAL
VAV-1 RM 110 RM 110/110B HP-1 465 140 6 0.5 200 0.3 800 1 85.0 108.0 0.5 180 158 5.0 5.0 5.0 10.0 1.0 1,2,3 VAV-2 RM 110A RM 110A HP-1 140 45 6 0.5 140 0.2 800 1 85.0 112.0 0.3 180 153 4.1 5.0 5.0 10.0 1.0 1,2,3 VAV-3 RM 110C RM 110C HP-1 150 45 6 0.5 150 0.2 800 1 85.0 111.0 0.3 180 153 4.2 5.0 5.0 10.0 1.0 1,2,3 VAV-4 RM 112 RM 112 HP-1 355 105 6 0.5 150 0.2 800 1 85.0 114.0 0.5 180 161 4.7 5.0 5.0 10.0 1.0 1,2,3 VAV-5 RM 118 RM 114 HP-1 215 65 6 0.5 130 0.2 800 1 85.0 117.0 0.5 180 163 4.5 5.0 5.0 10.0 1.0 1,2,3 VAV-6 RM 118 RM 114A HP-1 165 50 6 0.5 165 0.2 800 1 85.0 112.0 0.5 180 161 4.8 5.0 5.0 10.0 1.0 1,2,3 VAV-7 RM 118 RM 118 HP-1 580 175 8 0.5 230 0.3 800 1 85.0 114.0 1.0 180 165 7.2 5.0 5.0 10.0 1.0 1,2,4 VAV-8 CORR 137A RM 121/RM C HP-1 295 90 6 0.5 265 0.3 800 2 85.0 116.0 0.5 180 167 8.9 5.0 5.0 10.0 1.0 1,2,3 VAV-9 CORR 137A CORR 137A HP-1 615 185 8 0.5 300 0.4 800 1 85.0 110.0 1.0 180 164 8.1 5.0 5.0 10.0 1.0 1,2,4 VAV-10 RM 117A RM 117A HP-1 350 110 6 0.5 180 0.2 800 1 85.0 111.0 0.5 180 160 5.1 5.0 5.0 10.0 1.0 1,2,3 VAV-11 RM 119 RM 119 HP-1 175 55 6 0.5 175 0.2 800 1 85.0 111.0 0.5 180 160 4.9 5.0 5.0 10.0 1.0 1,2,3 VAV-12 RM 117 RM 117 HP-1 395 120 6 0.5 190 0.2 800 1 85.0 110.0 0.5 180 160 5.2 5.0 5.0 10.0 1.0 1,2,3 VAV-13 RM 115A RM 115A HP-1 355 110 6 0.5 180 0.2 800 1 85.0 111.0 0.5 180 160 5.1 5.0 5.0 10.0 1.0 1,2,3 VAV-14 RM 115 RM 115 HP-1 265 80 6 0.5 155 0.2 800 1 85.0 110.0 0.5 180 153 4.2 5.0 5.0 10.0 1.0 1,2,3 VAV-15 RM 115B RM 115B HP-1 320 95 6 0.5 180 0.2 800 1 85.0 111.0 0.5 180 160 5.1 5.0 5.0 10.0 1.0 1,2,3 VAV-16 RM 115C RM 115C HP-1 355 110 6 0.5 180 0.2 800 1 85.0 111.0 0.5 180 160 5.1 5.0 5.0 10.0 1.0 1,2,3
VAV-17 RM 141 RM 150 HP-2 1540 460 12 0.5 460 0.6 800 2 85.0 106.0 1.2 180 174 10.5 5.0 5.0 10.0 1.0 1,2,4 VAV-17A RM 141 RM 141 HP-2 660 200 8 0.5 350 0.4 800 1 85.0 111.0 3.1 180 140 9.9 5.0 5.0 10.0 1.0 1,2,4 VAV-18 RM 141 RM 150 HP-2 1540 460 12 0.5 460 0.6 800 2 85.0 106.0 1.2 180 155 10.5 5.0 5.0 10.0 1.0 1,2,4 VAV-19 RM 141 RM 141 HP-2 660 200 8 0.5 350 0.4 800 1 85.0 111.0 3.1 180 174 9.9 5.0 5.0 10.0 1.0 1,2,4 VAV-20 RM 142 RM 148A HP-2 350 105 6 0.5 180 0.2 800 1 85.0 111.0 0.5 180 160 5.1 5.0 5.0 10.0 1.0 1,2,3 VAV-21 CORR 136 CORR 136/RM142/RM 140 HP-2 805 245 8 0.5 270 0.3 800 1 85.0 114.0 2.0 180 172 8.5 5.0 5.0 10.0 1.0 1,2,4 VAV-22 CORR 136 RM 182 HP-2 1065 320 10 0.5 350 0.4 800 1 85.0 111.0 1.0 180 161 9.9 5.0 5.0 10.0 1.0 1,2,4 VAV-23 RM 143 RM 143 HP-2 570 170 8 0.5 200 0.3 800 1 85.0 113.0 0.5 180 156 6.1 5.0 5.0 10.0 1.0 1,2,3 VAV-24 CORR 136 RM F HP-2 845 255 8 0.5 255 0.3 800 1 85.0 109.0 0.5 180 154 6.6 5.0 5.0 10.0 1.0 1,2,3 VAV-25 CORR 136 RM 145 HP-2 495 150 6 0.5 195 0.2 800 1 85.0 109.0 0.5 180 160 5.1 5.0 5.0 10.0 1.0 1,2,3 VAV-26 CORR 136 RM 179/CORR 136 HP-2 615 125 8 0.5 235 0.3 800 1 85.0 100.0 0.5 180 154 3.8 5.0 5.0 10.0 1.0 1,2,3 VAV-27 CORR 132 RM 144 HP-2 160 50 6 0.5 160 0.2 800 1 85.0 113.0 0.5 180 161 4.9 5.0 5.0 10.0 1.0 1,2,3 VAV-28 CORR 132 RM 147/RM 147A HP-2 760 225 8 0.5 300 0.4 800 1 85.0 113.0 2.5 180 173 9.1 5.0 5.0 10.0 1.0 1,2,4 VAV-29 CORR 132 RM 146 HP-2 395 120 6 0.5 175 0.2 800 1 85.0 111.0 0.5 180 160 4.9 5.0 5.0 10.0 1.0 1,2,3 VAV-30 CORR 132 RM 149 HP-2 585 175 8 0.5 230 0.3 800 1 85.0 114.0 1.0 180 165 7.2 5.0 5.0 10.0 1.0 1,2,4 VAV-31 CORR 132 RM 148 HP-2 585 175 8 0.5 230 0.3 800 1 85.0 111.0 0.5 180 155 6.5 5.0 5.0 10.0 1.0 1,2,3 VAV-32 CORR 132 CORR B HP-2 665 200 8 0.5 300 0.4 800 1 85.0 110.0 1.0 180 164 8.1 5.0 5.0 10.0 1.0 1,2,4 VAV-33 CORR 132 RM 149A HP-2 150 45 6 0.5 150 0.2 800 1 85.0 114.0 0.5 180 161 4.7 5.0 5.0 10.0 1.0 1,2,3
VAV-34 CORR 132 RM 151 HP-3 1370 410 12 0.5 625 0.8 800 1 85.0 117.0 1.0 180 133 21.7 5.0 5.0 10.0 1.0 1,2,4 VAV-35 CORR 132 RM 151A HP-3 600 180 8 0.5 180 0.2 800 1 85.0 111.0 0.3 180 146 5.1 5.0 5.0 10.0 1.0 1,2,3 VAV-36 CORR 132 RM 151B HP-3 235 70 6 0.5 180 0.2 800 1 85.0 111.0 0.5 180 160 5.1 5.0 5.0 10.0 1.0 1,2,3 VAV-37 CORR 132 CORR 120/CORR 132 HP-3 830 250 8 0.5 650 0.8 800 3 85.0 117.0 0.9 180 134 22.6 5.0 5.0 10.0 1.0 1,2,3 VAV-38 CORR 132 RM 128/RM 129 HP-3 320 100 6 0.5 180 0.2 800 1 85.0 111.0 0.5 180 160 5.1 5.0 5.0 10.0 1.0 1,2,3 VAV-39 CORR 132 RM 122 HP-3 635 195 8 0.5 295 0.4 800 1 85.0 110.0 1.0 180 164 8.0 5.0 5.0 10.0 1.0 1,2,4 VAV-40 CORR 120 RM 133/RM 133A HP-3 1730 520 12 0.5 520 0.7 800 1 85.0 110.0 1.3 180 159 14.1 5.0 5.0 10.0 1.0 1,2,4 VAV-41 CORR 120 RM 125/RM 130/RM 130A HP-3 815 250 8 0.5 250 0.3 800 1 85.0 110.0 0.6 180 157 6.8 5.0 5.0 10.0 1.0 1,2,3 VAV-42 RM 104 RM 102/RM 103/RM 104 HP-3 630 195 8 0.5 225 0.3 800 1 85.0 110.0 0.4 180 152 6.1 5.0 5.0 10.0 1.0 1,2,3 VAV-43 RM E RM D/RM E HP-3 430 100 6 0.5 225 0.3 800 1 85.0 110.0 0.9 180 167 6.1 5.0 5.0 10.0 1.0 1,2,3 VAV-44 RM 105 RM 105 HP-3 1075 325 10 0.5 325 0.4 800 1 85.0 110.0 0.7 180 156 8.8 5.0 5.0 10.0 1.0 1,2,3 VAV-45 RM 106 RM 101 HP-3 535 160 8 0.5 230 0.3 800 1 85.0 111.0 0.5 180 156 6.5 5.0 5.0 10.0 1.0 1,2,3 VAV-46 RM 106 CORR 120/RM A/RM 107/RM 108/RM 109 HP-3 1400 420 10 0.5 500 0.6 800 1 85.0 110.0 3.0 180 171 13.6 5.0 5.0 10.0 1.0 1,2,4 VAV-47 RM 106 RM 106 HP-3 355 110 6 0.5 175 0.2 800 1 85.0 111.0 0.5 180 161 4.9 5.0 5.0 10.0 1.0 1,2,3
VAV-48 RM 170 RM 170 HP-4 315 95 6 0.5 180 0.2 800 1 85.0 111.0 0.5 180 160 5.1 5.0 5.0 10.0 1.0 1,2,3 VAV-49 RM 173 RM 173 HP-4 380 115 6 0.5 190 0.2 800 1 85.0 110.0 0.6 180 161 5.2 5.0 5.0 10.0 1.0 1,2,3 VAV-50 RM 173 RM 173B HP-4 150 45 6 0.5 150 0.2 800 1 85.0 111.0 0.3 180 153 4.2 5.0 5.0 10.0 1.0 1,2,3 VAV-51 RM 173C RM 173C HP-4 130 40 6 0.5 130 0.2 800 1 85.0 111.0 0.3 180 154 3.7 5.0 5.0 10.0 1.0 1,2,3 VAV-52 RM 178 RM 183 HP-4 1110 335 10 0.5 335 0.4 800 1 85.0 110.0 0.8 180 157 9.1 5.0 5.0 10.0 1.0 1,2,3 VAV-53 RM 177 RM 177/RM 177B HP-4 300 90 6 0.5 175 0.2 800 1 85.0 111.0 0.5 180 161 4.9 5.0 5.0 10.0 1.0 1,2,3 VAV-54 RM 178A RM 178B HP-4 2000 600 12 0.5 600 0.8 800 1 85.0 110.0 2.1 180 164 16.3 5.0 5.0 10.0 1.0 1,2,4 VAV-55 RM 178A RM 178A HP-4 275 85 6 0.5 150 0.2 800 1 85.0 111.0 0.3 180 153 4.2 5.0 5.0 10.0 1.0 1,2,3 VAV-56 RM 178 RM 178 HP-4 1100 330 10 0.5 700 0.9 800 2 85.0 111.0 0.9 180 134 19.7 5.0 5.0 10.0 1.0 1,2,3 VAV-57 RM 178 RM 178C HP-4 950 285 10 0.5 285 0.4 800 1 85.0 111.0 0.6 180 154 8.0 5.0 5.0 10.0 1.0 1,2,3 VAV-58 RM 187A RM 186/RM 187B HP-4 555 170 8 0.5 225 0.3 800 1 85.0 110.0 0.4 180 152 6.1 5.0 5.0 10.0 1.0 1,2,3 VAV-59 RM 187A RM 187/RM 187A HP-4 555 170 8 0.5 225 0.3 800 1 85.0 110.0 0.4 180 152 6.1 5.0 5.0 10.0 1.0 1,2,3 VAV-60 WEST MECH RM 190 HP-4 3060 920 16 0.5 1200 1.5 800 1 85.0 110.0 5.4 180 168 32.6 5.0 5.0 10.0 1.0 1,2,4
NOTES:
(1) PRESSURE INDEPENDENT VOLUME CONTROL UNIT
(2) CONTROLLED BY OCCUPANCY SENSOR
(3) 2-WAY VALVE
(4) 3-WAY VALVE
LOCATION SERVICE SERVED FROM
VARIABLE AIR VOLUME BOX (VAV) WITH WATER REHEAT SCHEDULE
MAXIMUM AIR
PRESSURE DROP
(in. w.g.)
MAXIMUM PRESSURE DROP (ft)
QTY. NOTES
MAXIMUM
FLOW RATE
(CFM)
MINIMUM
FLOW RATE
(CFM)
INLET
CONNECTION
DIAMETER (IN)
PLAN
DESIGNATION
RELIEF HOOD (RH) SCHEDULE
FACE DIMENSIONS
LENGTH
(in)
HEIGHT
(in)
RH-3 NORTH MECH RM HP-1 PENTHOUSE RUSKIN PH811 5,330 710 7.5 0.1 30 36 1 (1)
RH-4 WEST MECH RM HP-4 PENTHOUSE RUSKIN PH811 10,880 725 15.0 0.1 36 60 1 (1)
NOTES:
(1) PROVIDE BIRD SCREEN AS SPECIFIED
PLAN
DESIGNATION LOCATION SERVICE BASIS OF DESIGN
MANUFACTURERTYPE MAXIMUM PRESSURE
DROP (in. w.g.) NOTESQTY.BASIS OF
DESIGN MODEL
FLOW RATE
(CFM)
MAXIMUM FREE
AREA VELOCITY
(FPM)
MINIMUM FREE
AREA (ft2)
PUMP SCHEDULE
PLAN
DESIGNATION TYPE SERVICE
BASIS OF
DESIGN
MANUFACTURER
BASIS OF
DESIGN
MODEL
BASIS OF
DESIGN
SIZE
FLOW RATE
(GPM)
OPERATING
HEAD (FT)
NPSHR
(FT)
MINIMUM
OPERATING
EFFICIENCY
IMPELLER
DIA (IN) RPM
BRAKE
POWER
(hp)
MOTOR
POWER
(hp)
ELECTRICAL
(V/Hz/PHASE)
DISCHARGE
SIZE (IN)
SUCTION
SIZE (IN) QTY NOTES
P-1 BASE MOUNTED HWS B&G 1510 2BC 120 70 4.62 66.82 8.375 1750 4.8 5.00 460/60/3 2 2.5 1 P-2 BASE MOUNTED HWS B&G 1510 2BC 120 70 4.62 66.82 8.375 1750 4.8 5.00 460/60/3 2 2.5 1 P-3 BASE MOUNTED GHWS B&G 1510 2BC 115 60 4.53 65.37 7.875 1750 4.1 5.00 460/60/3 2 2.5 1 (2) P-4 BASE MOUNTED GHWS B&G 1510 2BC 115 60 4.53 65.37 7.875 1750 4.1 5.00 460/60/3 2 2.5 1 (2) P-5 BASE MOUNTED GROUND LOOP B&G 1510 2G 165 165 5.15 58.22 12.625 1750 16.74 20.00 460/60/3 2 3 1 (1) P-6 BASE MOUNTED GROUND LOOP B&G 1510 2G 165 165 5.15 58.22 12.625 1750 16.74 20.00 460/60/3 2 3 1 (1) P-7 BASE MOUNTED GROUND LOOP B&G 1510 2G 165 165 5.15 58.22 12.625 1750 16.74 20.00 460/60/3 2 3 1 (1)
NOTES:
(1) FLUID PUMPED IS 20% PROPYLENE GLYCOL
(2) FLUID PUMPED IS 40% ETHYLENE GLYCOL
H-1 HP-1 ARMSTRONG EHU-701 CM 32 5,330 27 80/29 80/50 22 30 D-2 24 2 208/60/3 1 (1) (2) (3) H-2 HP-2 ARMSTRONG EHU-703 CM 32 12,185 62 80/29 80/50 30 40 D-3 36 2 460/60/3 1 (1) (2) (3) H-3 HP-3 ARMSTRONG EHU-703 CM 32 10,650 68 80/28 80/50 30 40 D-3 36 2 460/60/3 1 (1) (2) (3) H-4 HP-4 ARMSTRONG EHU-704 CM 40 10,880 168 80/17 80/50 20 46 D-3 36 2 460/60/3 1 (1) (2) (3) H-6 HP-6 ARMSTRONG EHU-701 CM 12 2,000 28 70/30 70/50 18 24 D-2 24 2 460/60/3 1 (1) (2) (3)
NOTES:
(1) HUMIDISTAT DUCT-MOUNTED
(2) INSTALL PER MANUFACTURERS RECOMMENDATIONS
(3) HIGH LIMIT HUMIDISTAT
HUMIDIFIER (H) SCHEDULE
NOTESQTY.BASIS OF DESIGN MODEL FLOW RATE
(CFM) LBS/HR VAPOR TRAIL
(FT)
MANIFOLD
LENGTH (IN)
EAT (F)/RELATIVE
HUMIDITY
ELECTRICAL
(V/HZ/PH)MANIFOLD MODEL #PLAN
DESIGNATION SERVES BASIS OF DESIGN
MANUFACTURER
LAT (F)/RELATIVE
HUMIDITY DUCT HEIGHT DUCT WIDTH
GRILLE, REGISTER, AND DIFFUSER SCHEDULE
SD-1 SUPPLY DIFFUSER 30 0 240 6" DIA LAY IN STEEL (1)
SD-2 SUPPLY DIFFUSER 30 240 350 8" DIA LAY IN STEEL (1)
SD-3 SUPPLY DIFFUSER 30 600 1,075 14" DIA LAY IN STEEL (1)
SG-1 SUPPLY GRILLE 30 350 850 14"x14" SURFACE MOUNTED (1) (5) RG-1 RETURN EGGCRATE 30 0 350 12"x 6" LAY IN ALUMINUM (1) (4) RG-2 RETURN EGGCRATE 30 350 750 12"x 12" LAY IN ALUMINUM (1) (4) RG-3 RETURN EGGCRATE 30 600 1,000 22"x 10" LAY IN ALUMINUM (1) (3) EG-1 EXHAUST GRILLE 30 0 170 6"x 6" SURFACE STEEL (1) (3) EG-3 EXHAUST GRILLE 30 300 600 12"x 12" SURFACE STEEL (1) (3)
NOTES:
(1) WHITE FINISH
(2) CONCEALED MOUNTING
(3) 35° BLADES 3/4" SPACING
(4) 1/2"x1/2"x1/2" GRID CORE
(5) PROVIDE OPPOSED BLADE DAMPER
NOTES
MINIMUM
FLOW RATE
(CFM)
MAXIMUM
FLOW RATE
(CFM)
MAXIMUM
NC LEVEL
PLAN
DESIGNATIO
N
TYPE NECK SIZE
MOUNTING/
CONSTRUCTION
WATER SOURCE HEAT PUMP (HP) SCHEDULE
AIRFLOW
(CFM)
MIN. O. A.
(CFM)
E.S.P.
(IN. WG) QUANTITY
MOTOR
POWER
EACH
(HP)
EAT DB
(° F)
EAT WB
(° F)
LAT DB
(° F)
LAT WB
(° F)
EWT
(° F)
MIN. EER @
ACTUAL
CONDITIONS
EAT DB
(° F)
LAT DB
(° F)
EWT
(° F)
MIN. COP @
ACTUAL
CONDITIONS
QUANTIT
Y
RLA
EACH
LRA
EACH
HP-1 NORTH MECH RM FHP EC1515-4VTC-FBF 5330 795 1.40 1.00 3 74.0 61.0 55.0 54.0 90 13.2 56.0 85.0 30 4.1 2 9.1 62.0 40.0 17.20 EC EC VFD 208/60/3 (1) (2) (3) (4) HP-2 MECH RM 141B FHP EC360-4VTC-FBF 12185 1540 1.40 2.00 5 74.0 61.0 55.0 54.0 90 11.8 57.0 85.0 30 3.3 2 26.4 187.0 100.0 41.70 EC EC VFD 460/60/3 (1) (2) (3) (4) HP-3 MECH RM 160 FHP EC360-4VTC-FBF 10650 1715 1.00 2.00 5 74.0 61.0 55.0 54.0 90 11.1 55.0 85.0 30 3.2 2 26.4 187.0 65.0 19.20 EC EC VFD 460/60/3 (1) (2) (3) (4) HP-4 WEST MECH RM FHP EC360-4VTC-FBF 10880 1060 1.40 2.00 5 74.0 61.0 55.0 54.0 90 10.9 60.0 85.0 30 3.3 2 26.4 187.0 90.0 28.40 EC EC VFD 460/60/3 (1) (2) (3) (4) HP-5 RM 141A FHP EC072-4VTC-FBT 2000 0 0.50 1.00 1 80.0 60.0 55.0 54.0 90 10.8 80.0 70.0 30 3.1 2 5.4 40.0 17.0 23.30 EC EC VFD 460/60/3 (1) (2) (3) (4) HP-6 RM 150 FHP EC072-4HZC-FBT 2000 0 0.50 1.00 1 80.0 60.0 55.0 54.0 90 10.8 80.0 70.0 30 3.1 2 5.4 40.0 17.0 23.30 EC EC VFD 460/60/3 (1) (2) (3) (4)
NOTES:
(1) EXTERNAL STATIC PRESSURE INCLUDES DUCTWORK, FILTERS, AND COILS NOT IN HP CASING.
(2) PROVIDE UNITS SUITABLE FOR USE WITH 20% PROPLEYENE GLYCOL SOLUTION.
(3) PROVIDE UNITS WITH HOSE KITS. HOSE KITS SHALL INCLUDE STAINLESS STEEL BRAID HOSES WITH SWIVEL CONNECTIONS, BALL VALVES, AUTOMATIC FLOW CONTROL VALVE, Y-STRAINER WITH PT TEST PORT, AND HONEYWELL 2 WAY 2 POSITION 24 VOLT VC SERIES CONTROL VALVE.
(4) PROVIDE SINGLE POINT ELECTRICAL CONNECTION TO UNIT.
LOCATIONPLAN
DESIGNATION
BASIS OF DESIGN
MANUFACTURER MODEL WATER PRESSURE
DROP (FT W.G.)
VOLTS/HZ/
PHASE
Disconnect by MC or
EC
Starter by MC or EC
NOTES
COMPRESSORHEATING PERFOMANCE
WATER
FLOW RATE
(GPM)
SUPPLY FAN COOLING PERFOMANCE
VFD or ATL
CHAD B.
WESTBROOK
WESTBROOK
DATE
PANEL 'HN1 (EXST)' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.
480Y/277-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: WESTINGHOUSE
100-AMP, MAIN LUGS ONLY MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
1 LN1 (VIA T1) 45 3 0.0 20 1 LTG. 147,149,151 2
3 --- ** * 0.0 20 1 LTG. 135,138,145,179 4
5 --- ** * 0.0 20 1 LTG. 102,133,134,139 6
7 EGRESS LTG. 20 1 0.0 15 3 EF 11 (RM 131) 8
9 SPACE 0.0 ** * --- 10
11 SPACE 0.0 ** * --- 12
13 SPACE 0.0 SPACE 14
15 SPACE 0.0 SPACE 16
17 SPACE 0.0 SPACE 18
19 SPACE 0.0 SPACE 20
21 SPACE 0.0 SPACE 22
23 SPACE 0.0 SPACE 24
25 SPACE 0.0 SPACE 26
27 SPACE 0.0 SPACE 28
29 SPACE 0.0 SPACE 30
PROJECT #JFSD200909E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 03/23/10
PANEL 'HN2 SECT1 (EXST) ' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.
480Y/277-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: WESTINGHOUSE
600-AMP, MAIN LUGS ONLY MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
1 SPACE 0.0 SPACE 2
3 RM 126 TEST BENCH 60 3 0.0 SPACE 4
5 --- ** * 0.0 15 3 SPARE 6
7 --- ** * 0.0 ** * --- 8
9 E.F. 8,9 15 3 0.0 ** * --- 10
11 --- ** * 0.0 15 3 AHU-2 12
13 --- ** * 0.0 ** * --- 14
15 LTG. 124, 164 20 1 0.0 ** * --- 16
17 LTG. 126, 165, 166 20 1 0.0 60 3 PUMP 6 18
19 PUMP 5 60 3 0.0 ** * --- 20
21 --- ** * 0.0 ** * --- 22
23 --- ** * 0.0 20 1 EGRESS LTG 24
25 HP-3 90 3 0.0 50 3 WH-2 26
27 --- ** * 0.0 ** * --- 28
29 --- ** * 0.0 ** * --- 30
PROJECT #JFSD200909E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 03/23/10
PANEL 'HN2 SECT2 (EXST)' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.
480Y/277-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: WESTINGHOUSE
100-AMP, MAIN LUGS ONLY MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
1 SPACE 0.0 SPACE 2
3 SPACE 0.0 SPACE 4
5 AC-1 15 3 0.0 60 3 PUMP 7 6
7 --- ** * 0.0 ** * --- 8
9 --- ** * 0.0 ** * --- 10
11 AC-2 15 3 0.0 40 3 HUM-3 12
13 --- ** * 0.0 ** * --- 14
15 --- ** * 0.0 ** * --- 16
17 LTG 116, 118, 126, 160, 162 20 1 0.0 20 1 LTG 106, 109, 112, 130 18
19 LTG 119, 120, 122, 123 20 1 0.0 20 1 LTG 103, 105, 108, 113, 115 20
21 LTG 127, 129 20 1 0.0 20 1 LTG 131, 132, 150, 152 22
23 CHILLER TEST BENCH 80 3 0.0 50 3 D-1,2,3,4 24
25 --- ** * 0.0 ** * --- 26
27 --- ** * 0.0 ** * --- 28
PROJECT #JFSD200909E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 03/23/10
PANEL 'HN3 (EXST)' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.
480Y/277-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: WESTINGHOUSEWESTINGHOUSE
400-AMP, MAIN LUGS ONLY MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
1 WH-4 50 3 0.0 30 3 AHU-1 2
3 --- ** * 0.0 ** * --- 4
5 --- ** * 0.0 ** * --- 6
7 HP-4 90 3 0.0 20 3 SUMP PIT FOR WEST SIDE 8
9 --- ** * 0.0 ** * --- 10
11 --- ** * 0.0 ** * --- 12
13 LTG C - 146 20 1 0.0 20 1 LTG 177, 178 14
15 --- 20 1 0.0 20 1 LTG 170, 171 173 176 16
17 --- 20 1 0.0 20 1 EXT LTG (WALL PACK) 18
19 SPARE 40 3 0.0 15 3 E.F. 6 20
21 --- ** * 0.0 ** * --- 22
23 --- ** * 0.0 ** * --- 24
25 HUM-4 50 3 0.0 15 3 E.F.7 26
27 --- ** * 0.0 ** * --- 28
29 --- ** * 0.0 ** * --- 30
31 SPARE 15 3 0.0 15 3 E.F. 4 32
33 --- ** * 0.0 ** * --- 34
35 --- ** * 0.0 ** * --- 36
37 TRANSFORMER 60 3 0.0 20 1 EGRESS LTG 38
39 --- ** * 0.0 SPACE 40
41 --- ** * 0.0 SPACE 42
PROJECT #JFSD200909E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 03/23/10
PANEL 'HE (EXST)' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.
480Y/277-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: WESTINGHOUSEWESTINGHOUSE
400-AMP, MAIN LUGS ONLY MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
1 75 KVA XFMR PANEL LE 150 3 0.0 20 3 HP-5 2
3 --- ** * 0.0 ** * --- 4
5 --- ** * 0.0 ** * --- 6
7 HP-2 90 3 0.0 125 3 SPARE 8
9 --- ** * 0.0 ** * --- 10
11 --- ** * 0.0 ** * --- 12
13 HUM-6 20 3 0.0 20 1 LTG 141A, 141B 14
15 --- ** * 0.0 20 1 LTG 122 16
17 --- ** * 0.0 20 1 SPARE 18
19 LTG RM 141 20 1 0.0 20 3 HP-6 20
21 LTG RM 141 20 1 0.0 ** * --- 22
23 LTG 142, 142, 144 20 1 0.0 ** * --- 24
25 CU-2 100 3 0.0 100 3 COMSES DISINTEGRATOR 26
27 --- ** * 0.0 ** * --- 28
29 --- ** * 0.0 ** * --- 30
31 HUM-2 40 3 0.0 50 3 UNKNOWN 32
33 --- ** * 0.0 ** * --- 34
35 --- ** * 0.0 ** * --- 36
37 SPACE 0.0 20 1 SPACE 38
39 SPACE 0.0 SPACE 40
41 SPACE 0.0 SPACE 42
PROJECT #JFSD200909E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 03/23/10
File details come from the government source that posted it. Updated .