Atth 2- JFSD200909 100 Drawings.pdf

PDF 13 MB Posted

Attached to
HVAC Repair Federal contract opportunity
Solicitation number
FA4659-10-R-0029
Issued by
Department of the Air Force Air Mobility Command

About this file

Drawings

View the file

Other files for this federal contract opportunity

Other files attached to HVAC Repair, newest first.
File Type Posted
Amendment 0001 - Change Site Visit Date 10-R-0029.doc DOC document
FA4659-10-R-0029.rtf RTF text file
Atth 5-Financial Institution Reference Sheet - Offeror.doc DOC document
Atth 1- JFSD200909 Specifications.pdf PDF
Atth 4- Past and Present Past Performance Questionnaire 10-R-0029.doc DOC document
Atth 3- JFSD200909 Material Submittal Schedule.pdf PDF
Atth 6 - Climatological Data.pdf PDF
Solicitation Cover Letter R-10-0025.doc DOC document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REPAIR HVAC - GROUND SOURCE HEAT PUMP

COMMUNICATION SQUADRON HEADQUARTERS

JFSD 200909

"ISSUED FOR BID/CONSTRUCTION"

NORTH DAKOTA

GRAND FORKS AIR FORCE BASE

18" Rcp Inv. 891.80

18" Rcp Inv. 891.81

Existing Antenna

Gas Meter

San Mh.

Toc. 894.90 Inv. 882.90

San Mh.

Toc. 894.18 Inv. 882.68

San Mh.

Toc. 894.13 Inv. 883.23 Existing Sanitary Sewer

Existing Sanitary Sewer

E xi st in g Sa ni ta ry S ew er

Benchmark Top Nut on Hydrant

Elev. 896.52

893 892

895 895

135.5

53.5

80.9

50.5

10.5

0.

.5

.5

Bituminous Pavement

Bituminous Pavement

B itum inous P avem ent

Concrete Sidewalk

Concrete Sidewalk

Concrete Sidewalk

C oncrete Sidew alk

MARK T.

JASTER

DATE

18" Rcp Inv. 891.80

18" Rcp Inv. 891.81

Existing Antenna

Gas Meter

San Mh.

Toc. 894.90 Inv. 882.90

San Mh.

Toc. 894.18 Inv. 882.68

San Mh.

Toc. 894.13 Inv. 883.23 Existing Sanitary Sewer

Existing Sanitary Sewer

E xi st in g Sa ni ta ry S ew er

Benchmark Top Nut on Hydrant

Elev. 896.52

135.5

53.5

80.9

50.5

10.5

0.

.5

.5

Bituminous Pavement

Bituminous Pavement

B itum inous P avem ent

Concrete Sidewalk

Concrete Sidewalk

Concrete Sidewalk

C oncrete Sidew alk

0-33.5 3/4" 0-3.5 33.6-67 1" 3.6-7.0 67-124 1-1/4" 7.1-13.0

125-209 1-1/2" 13.1-19.0 210-428 2" 19.1-45.0 429-665 2-1/2" 45.1-70.0 666-1235 3" 71-130

1236-2565 4" 131-270 2566-4750 5" 271-500 4751-7600 6" 501-800 7601-15675 8" 801-1650

NOTES:

(1) BASED ON TYPE L COPPER PIPE

(2) 20 DEG TEMPERATURE DROP

HOT WATER SIZING SCHEDULE

MBH SUPPLY AND

RETURN

GPM

EXPANSION TANK (ET) SCHEDULE

PLAN

DESIGNATION

SERVICE TYPE

BASIS OF

DESIGN

MANUFACTURER

BASIS OF

DESIGN

MODEL

TANK

VOLUME

(GAL)

ACCEPTANCE

VOLUME (GAL)

MAX SYSTEM

PRESSURE

(PSIG)

QTY NOTES

ET-1 GROUND LOOP BLADDER B&G B-200 53 53 125 1 (1)

NOTES:

(1) SIZE TANK BASED ON 20% PROPYLENE GLYCOL

PLAN

DESIGNATION

SERVICE LOCATION

BASIS OF

DESIGN

MANUFACTURER

BASIS OF

DESIGN

MODEL

INLET

SIZE

OUTLET

SIZE

FLOW

RATE

(GPM)

PRESSURE

DROP (FT)

NOTES

AS-1 GROUND LOOP RM 160 SPIROVENT VDT600 6 6 330 1.25 (1)(2)

NOTES:

(1) MAXIMUM WORKING PRESSURE 125 PSI

(2) BRACKET SUPPORTS

(3) SIZE TANK BASED ON 20% PROPYLENE GLYCOL

AIR SEPARATOR (AS) SCHEDULE

REHEAT COIL

HEATING

FLOW

RATE (CFM)

MINIMUM

COIL AREA

(ft2)

MAXIMUM FACE

VELOCITY

(FPM)

MINIMUM

ROWS

EAT

(°F) LAT (°F)

FLOW

RATE

(GPM)

EWT

(°F)

LWT

(°F) MBH COIL ACV TOTAL

VAV-1 RM 110 RM 110/110B HP-1 465 140 6 0.5 200 0.3 800 1 85.0 108.0 0.5 180 158 5.0 5.0 5.0 10.0 1.0 1,2,3 VAV-2 RM 110A RM 110A HP-1 140 45 6 0.5 140 0.2 800 1 85.0 112.0 0.3 180 153 4.1 5.0 5.0 10.0 1.0 1,2,3 VAV-3 RM 110C RM 110C HP-1 150 45 6 0.5 150 0.2 800 1 85.0 111.0 0.3 180 153 4.2 5.0 5.0 10.0 1.0 1,2,3 VAV-4 RM 112 RM 112 HP-1 355 105 6 0.5 150 0.2 800 1 85.0 114.0 0.5 180 161 4.7 5.0 5.0 10.0 1.0 1,2,3 VAV-5 RM 118 RM 114 HP-1 215 65 6 0.5 130 0.2 800 1 85.0 117.0 0.5 180 163 4.5 5.0 5.0 10.0 1.0 1,2,3 VAV-6 RM 118 RM 114A HP-1 165 50 6 0.5 165 0.2 800 1 85.0 112.0 0.5 180 161 4.8 5.0 5.0 10.0 1.0 1,2,3 VAV-7 RM 118 RM 118 HP-1 580 175 8 0.5 230 0.3 800 1 85.0 114.0 1.0 180 165 7.2 5.0 5.0 10.0 1.0 1,2,4 VAV-8 CORR 137A RM 121/RM C HP-1 295 90 6 0.5 265 0.3 800 2 85.0 116.0 0.5 180 167 8.9 5.0 5.0 10.0 1.0 1,2,3 VAV-9 CORR 137A CORR 137A HP-1 615 185 8 0.5 300 0.4 800 1 85.0 110.0 1.0 180 164 8.1 5.0 5.0 10.0 1.0 1,2,4 VAV-10 RM 117A RM 117A HP-1 350 110 6 0.5 180 0.2 800 1 85.0 111.0 0.5 180 160 5.1 5.0 5.0 10.0 1.0 1,2,3 VAV-11 RM 119 RM 119 HP-1 175 55 6 0.5 175 0.2 800 1 85.0 111.0 0.5 180 160 4.9 5.0 5.0 10.0 1.0 1,2,3 VAV-12 RM 117 RM 117 HP-1 395 120 6 0.5 190 0.2 800 1 85.0 110.0 0.5 180 160 5.2 5.0 5.0 10.0 1.0 1,2,3 VAV-13 RM 115A RM 115A HP-1 355 110 6 0.5 180 0.2 800 1 85.0 111.0 0.5 180 160 5.1 5.0 5.0 10.0 1.0 1,2,3 VAV-14 RM 115 RM 115 HP-1 265 80 6 0.5 155 0.2 800 1 85.0 110.0 0.5 180 153 4.2 5.0 5.0 10.0 1.0 1,2,3 VAV-15 RM 115B RM 115B HP-1 320 95 6 0.5 180 0.2 800 1 85.0 111.0 0.5 180 160 5.1 5.0 5.0 10.0 1.0 1,2,3 VAV-16 RM 115C RM 115C HP-1 355 110 6 0.5 180 0.2 800 1 85.0 111.0 0.5 180 160 5.1 5.0 5.0 10.0 1.0 1,2,3

VAV-17 RM 141 RM 150 HP-2 1540 460 12 0.5 460 0.6 800 2 85.0 106.0 1.2 180 174 10.5 5.0 5.0 10.0 1.0 1,2,4 VAV-17A RM 141 RM 141 HP-2 660 200 8 0.5 350 0.4 800 1 85.0 111.0 3.1 180 140 9.9 5.0 5.0 10.0 1.0 1,2,4 VAV-18 RM 141 RM 150 HP-2 1540 460 12 0.5 460 0.6 800 2 85.0 106.0 1.2 180 155 10.5 5.0 5.0 10.0 1.0 1,2,4 VAV-19 RM 141 RM 141 HP-2 660 200 8 0.5 350 0.4 800 1 85.0 111.0 3.1 180 174 9.9 5.0 5.0 10.0 1.0 1,2,4 VAV-20 RM 142 RM 148A HP-2 350 105 6 0.5 180 0.2 800 1 85.0 111.0 0.5 180 160 5.1 5.0 5.0 10.0 1.0 1,2,3 VAV-21 CORR 136 CORR 136/RM142/RM 140 HP-2 805 245 8 0.5 270 0.3 800 1 85.0 114.0 2.0 180 172 8.5 5.0 5.0 10.0 1.0 1,2,4 VAV-22 CORR 136 RM 182 HP-2 1065 320 10 0.5 350 0.4 800 1 85.0 111.0 1.0 180 161 9.9 5.0 5.0 10.0 1.0 1,2,4 VAV-23 RM 143 RM 143 HP-2 570 170 8 0.5 200 0.3 800 1 85.0 113.0 0.5 180 156 6.1 5.0 5.0 10.0 1.0 1,2,3 VAV-24 CORR 136 RM F HP-2 845 255 8 0.5 255 0.3 800 1 85.0 109.0 0.5 180 154 6.6 5.0 5.0 10.0 1.0 1,2,3 VAV-25 CORR 136 RM 145 HP-2 495 150 6 0.5 195 0.2 800 1 85.0 109.0 0.5 180 160 5.1 5.0 5.0 10.0 1.0 1,2,3 VAV-26 CORR 136 RM 179/CORR 136 HP-2 615 125 8 0.5 235 0.3 800 1 85.0 100.0 0.5 180 154 3.8 5.0 5.0 10.0 1.0 1,2,3 VAV-27 CORR 132 RM 144 HP-2 160 50 6 0.5 160 0.2 800 1 85.0 113.0 0.5 180 161 4.9 5.0 5.0 10.0 1.0 1,2,3 VAV-28 CORR 132 RM 147/RM 147A HP-2 760 225 8 0.5 300 0.4 800 1 85.0 113.0 2.5 180 173 9.1 5.0 5.0 10.0 1.0 1,2,4 VAV-29 CORR 132 RM 146 HP-2 395 120 6 0.5 175 0.2 800 1 85.0 111.0 0.5 180 160 4.9 5.0 5.0 10.0 1.0 1,2,3 VAV-30 CORR 132 RM 149 HP-2 585 175 8 0.5 230 0.3 800 1 85.0 114.0 1.0 180 165 7.2 5.0 5.0 10.0 1.0 1,2,4 VAV-31 CORR 132 RM 148 HP-2 585 175 8 0.5 230 0.3 800 1 85.0 111.0 0.5 180 155 6.5 5.0 5.0 10.0 1.0 1,2,3 VAV-32 CORR 132 CORR B HP-2 665 200 8 0.5 300 0.4 800 1 85.0 110.0 1.0 180 164 8.1 5.0 5.0 10.0 1.0 1,2,4 VAV-33 CORR 132 RM 149A HP-2 150 45 6 0.5 150 0.2 800 1 85.0 114.0 0.5 180 161 4.7 5.0 5.0 10.0 1.0 1,2,3

VAV-34 CORR 132 RM 151 HP-3 1370 410 12 0.5 625 0.8 800 1 85.0 117.0 1.0 180 133 21.7 5.0 5.0 10.0 1.0 1,2,4 VAV-35 CORR 132 RM 151A HP-3 600 180 8 0.5 180 0.2 800 1 85.0 111.0 0.3 180 146 5.1 5.0 5.0 10.0 1.0 1,2,3 VAV-36 CORR 132 RM 151B HP-3 235 70 6 0.5 180 0.2 800 1 85.0 111.0 0.5 180 160 5.1 5.0 5.0 10.0 1.0 1,2,3 VAV-37 CORR 132 CORR 120/CORR 132 HP-3 830 250 8 0.5 650 0.8 800 3 85.0 117.0 0.9 180 134 22.6 5.0 5.0 10.0 1.0 1,2,3 VAV-38 CORR 132 RM 128/RM 129 HP-3 320 100 6 0.5 180 0.2 800 1 85.0 111.0 0.5 180 160 5.1 5.0 5.0 10.0 1.0 1,2,3 VAV-39 CORR 132 RM 122 HP-3 635 195 8 0.5 295 0.4 800 1 85.0 110.0 1.0 180 164 8.0 5.0 5.0 10.0 1.0 1,2,4 VAV-40 CORR 120 RM 133/RM 133A HP-3 1730 520 12 0.5 520 0.7 800 1 85.0 110.0 1.3 180 159 14.1 5.0 5.0 10.0 1.0 1,2,4 VAV-41 CORR 120 RM 125/RM 130/RM 130A HP-3 815 250 8 0.5 250 0.3 800 1 85.0 110.0 0.6 180 157 6.8 5.0 5.0 10.0 1.0 1,2,3 VAV-42 RM 104 RM 102/RM 103/RM 104 HP-3 630 195 8 0.5 225 0.3 800 1 85.0 110.0 0.4 180 152 6.1 5.0 5.0 10.0 1.0 1,2,3 VAV-43 RM E RM D/RM E HP-3 430 100 6 0.5 225 0.3 800 1 85.0 110.0 0.9 180 167 6.1 5.0 5.0 10.0 1.0 1,2,3 VAV-44 RM 105 RM 105 HP-3 1075 325 10 0.5 325 0.4 800 1 85.0 110.0 0.7 180 156 8.8 5.0 5.0 10.0 1.0 1,2,3 VAV-45 RM 106 RM 101 HP-3 535 160 8 0.5 230 0.3 800 1 85.0 111.0 0.5 180 156 6.5 5.0 5.0 10.0 1.0 1,2,3 VAV-46 RM 106 CORR 120/RM A/RM 107/RM 108/RM 109 HP-3 1400 420 10 0.5 500 0.6 800 1 85.0 110.0 3.0 180 171 13.6 5.0 5.0 10.0 1.0 1,2,4 VAV-47 RM 106 RM 106 HP-3 355 110 6 0.5 175 0.2 800 1 85.0 111.0 0.5 180 161 4.9 5.0 5.0 10.0 1.0 1,2,3

VAV-48 RM 170 RM 170 HP-4 315 95 6 0.5 180 0.2 800 1 85.0 111.0 0.5 180 160 5.1 5.0 5.0 10.0 1.0 1,2,3 VAV-49 RM 173 RM 173 HP-4 380 115 6 0.5 190 0.2 800 1 85.0 110.0 0.6 180 161 5.2 5.0 5.0 10.0 1.0 1,2,3 VAV-50 RM 173 RM 173B HP-4 150 45 6 0.5 150 0.2 800 1 85.0 111.0 0.3 180 153 4.2 5.0 5.0 10.0 1.0 1,2,3 VAV-51 RM 173C RM 173C HP-4 130 40 6 0.5 130 0.2 800 1 85.0 111.0 0.3 180 154 3.7 5.0 5.0 10.0 1.0 1,2,3 VAV-52 RM 178 RM 183 HP-4 1110 335 10 0.5 335 0.4 800 1 85.0 110.0 0.8 180 157 9.1 5.0 5.0 10.0 1.0 1,2,3 VAV-53 RM 177 RM 177/RM 177B HP-4 300 90 6 0.5 175 0.2 800 1 85.0 111.0 0.5 180 161 4.9 5.0 5.0 10.0 1.0 1,2,3 VAV-54 RM 178A RM 178B HP-4 2000 600 12 0.5 600 0.8 800 1 85.0 110.0 2.1 180 164 16.3 5.0 5.0 10.0 1.0 1,2,4 VAV-55 RM 178A RM 178A HP-4 275 85 6 0.5 150 0.2 800 1 85.0 111.0 0.3 180 153 4.2 5.0 5.0 10.0 1.0 1,2,3 VAV-56 RM 178 RM 178 HP-4 1100 330 10 0.5 700 0.9 800 2 85.0 111.0 0.9 180 134 19.7 5.0 5.0 10.0 1.0 1,2,3 VAV-57 RM 178 RM 178C HP-4 950 285 10 0.5 285 0.4 800 1 85.0 111.0 0.6 180 154 8.0 5.0 5.0 10.0 1.0 1,2,3 VAV-58 RM 187A RM 186/RM 187B HP-4 555 170 8 0.5 225 0.3 800 1 85.0 110.0 0.4 180 152 6.1 5.0 5.0 10.0 1.0 1,2,3 VAV-59 RM 187A RM 187/RM 187A HP-4 555 170 8 0.5 225 0.3 800 1 85.0 110.0 0.4 180 152 6.1 5.0 5.0 10.0 1.0 1,2,3 VAV-60 WEST MECH RM 190 HP-4 3060 920 16 0.5 1200 1.5 800 1 85.0 110.0 5.4 180 168 32.6 5.0 5.0 10.0 1.0 1,2,4

NOTES:

(1) PRESSURE INDEPENDENT VOLUME CONTROL UNIT

(2) CONTROLLED BY OCCUPANCY SENSOR

(3) 2-WAY VALVE

(4) 3-WAY VALVE

LOCATION SERVICE SERVED FROM

VARIABLE AIR VOLUME BOX (VAV) WITH WATER REHEAT SCHEDULE

MAXIMUM AIR

PRESSURE DROP

(in. w.g.)

MAXIMUM PRESSURE DROP (ft)

QTY. NOTES

MAXIMUM

FLOW RATE

(CFM)

MINIMUM

FLOW RATE

(CFM)

INLET

CONNECTION

DIAMETER (IN)

PLAN

DESIGNATION

RELIEF HOOD (RH) SCHEDULE

FACE DIMENSIONS

LENGTH

(in)

HEIGHT

(in)

RH-3 NORTH MECH RM HP-1 PENTHOUSE RUSKIN PH811 5,330 710 7.5 0.1 30 36 1 (1)

RH-4 WEST MECH RM HP-4 PENTHOUSE RUSKIN PH811 10,880 725 15.0 0.1 36 60 1 (1)

NOTES:

(1) PROVIDE BIRD SCREEN AS SPECIFIED

PLAN

DESIGNATION LOCATION SERVICE BASIS OF DESIGN

MANUFACTURERTYPE MAXIMUM PRESSURE

DROP (in. w.g.) NOTESQTY.BASIS OF

DESIGN MODEL

FLOW RATE

(CFM)

MAXIMUM FREE

AREA VELOCITY

(FPM)

MINIMUM FREE

AREA (ft2)

PUMP SCHEDULE

PLAN

DESIGNATION TYPE SERVICE

BASIS OF

DESIGN

MANUFACTURER

BASIS OF

DESIGN

MODEL

BASIS OF

DESIGN

SIZE

FLOW RATE

(GPM)

OPERATING

HEAD (FT)

NPSHR

(FT)

MINIMUM

OPERATING

EFFICIENCY

IMPELLER

DIA (IN) RPM

BRAKE

POWER

(hp)

MOTOR

POWER

(hp)

ELECTRICAL

(V/Hz/PHASE)

DISCHARGE

SIZE (IN)

SUCTION

SIZE (IN) QTY NOTES

P-1 BASE MOUNTED HWS B&G 1510 2BC 120 70 4.62 66.82 8.375 1750 4.8 5.00 460/60/3 2 2.5 1 P-2 BASE MOUNTED HWS B&G 1510 2BC 120 70 4.62 66.82 8.375 1750 4.8 5.00 460/60/3 2 2.5 1 P-3 BASE MOUNTED GHWS B&G 1510 2BC 115 60 4.53 65.37 7.875 1750 4.1 5.00 460/60/3 2 2.5 1 (2) P-4 BASE MOUNTED GHWS B&G 1510 2BC 115 60 4.53 65.37 7.875 1750 4.1 5.00 460/60/3 2 2.5 1 (2) P-5 BASE MOUNTED GROUND LOOP B&G 1510 2G 165 165 5.15 58.22 12.625 1750 16.74 20.00 460/60/3 2 3 1 (1) P-6 BASE MOUNTED GROUND LOOP B&G 1510 2G 165 165 5.15 58.22 12.625 1750 16.74 20.00 460/60/3 2 3 1 (1) P-7 BASE MOUNTED GROUND LOOP B&G 1510 2G 165 165 5.15 58.22 12.625 1750 16.74 20.00 460/60/3 2 3 1 (1)

NOTES:

(1) FLUID PUMPED IS 20% PROPYLENE GLYCOL

(2) FLUID PUMPED IS 40% ETHYLENE GLYCOL

H-1 HP-1 ARMSTRONG EHU-701 CM 32 5,330 27 80/29 80/50 22 30 D-2 24 2 208/60/3 1 (1) (2) (3) H-2 HP-2 ARMSTRONG EHU-703 CM 32 12,185 62 80/29 80/50 30 40 D-3 36 2 460/60/3 1 (1) (2) (3) H-3 HP-3 ARMSTRONG EHU-703 CM 32 10,650 68 80/28 80/50 30 40 D-3 36 2 460/60/3 1 (1) (2) (3) H-4 HP-4 ARMSTRONG EHU-704 CM 40 10,880 168 80/17 80/50 20 46 D-3 36 2 460/60/3 1 (1) (2) (3) H-6 HP-6 ARMSTRONG EHU-701 CM 12 2,000 28 70/30 70/50 18 24 D-2 24 2 460/60/3 1 (1) (2) (3)

NOTES:

(1) HUMIDISTAT DUCT-MOUNTED

(2) INSTALL PER MANUFACTURERS RECOMMENDATIONS

(3) HIGH LIMIT HUMIDISTAT

HUMIDIFIER (H) SCHEDULE

NOTESQTY.BASIS OF DESIGN MODEL FLOW RATE

(CFM) LBS/HR VAPOR TRAIL

(FT)

MANIFOLD

LENGTH (IN)

EAT (F)/RELATIVE

HUMIDITY

ELECTRICAL

(V/HZ/PH)MANIFOLD MODEL #PLAN

DESIGNATION SERVES BASIS OF DESIGN

MANUFACTURER

LAT (F)/RELATIVE

HUMIDITY DUCT HEIGHT DUCT WIDTH

GRILLE, REGISTER, AND DIFFUSER SCHEDULE

SD-1 SUPPLY DIFFUSER 30 0 240 6" DIA LAY IN STEEL (1)

SD-2 SUPPLY DIFFUSER 30 240 350 8" DIA LAY IN STEEL (1)

SD-3 SUPPLY DIFFUSER 30 600 1,075 14" DIA LAY IN STEEL (1)

SG-1 SUPPLY GRILLE 30 350 850 14"x14" SURFACE MOUNTED (1) (5) RG-1 RETURN EGGCRATE 30 0 350 12"x 6" LAY IN ALUMINUM (1) (4) RG-2 RETURN EGGCRATE 30 350 750 12"x 12" LAY IN ALUMINUM (1) (4) RG-3 RETURN EGGCRATE 30 600 1,000 22"x 10" LAY IN ALUMINUM (1) (3) EG-1 EXHAUST GRILLE 30 0 170 6"x 6" SURFACE STEEL (1) (3) EG-3 EXHAUST GRILLE 30 300 600 12"x 12" SURFACE STEEL (1) (3)

NOTES:

(1) WHITE FINISH

(2) CONCEALED MOUNTING

(3) 35° BLADES 3/4" SPACING

(4) 1/2"x1/2"x1/2" GRID CORE

(5) PROVIDE OPPOSED BLADE DAMPER

NOTES

MINIMUM

FLOW RATE

(CFM)

MAXIMUM

FLOW RATE

(CFM)

MAXIMUM

NC LEVEL

PLAN

DESIGNATIO

N

TYPE NECK SIZE

MOUNTING/

CONSTRUCTION

WATER SOURCE HEAT PUMP (HP) SCHEDULE

AIRFLOW

(CFM)

MIN. O. A.

(CFM)

E.S.P.

(IN. WG) QUANTITY

MOTOR

POWER

EACH

(HP)

EAT DB

(° F)

EAT WB

(° F)

LAT DB

(° F)

LAT WB

(° F)

EWT

(° F)

MIN. EER @

ACTUAL

CONDITIONS

EAT DB

(° F)

LAT DB

(° F)

EWT

(° F)

MIN. COP @

ACTUAL

CONDITIONS

QUANTIT

Y

RLA

EACH

LRA

EACH

HP-1 NORTH MECH RM FHP EC1515-4VTC-FBF 5330 795 1.40 1.00 3 74.0 61.0 55.0 54.0 90 13.2 56.0 85.0 30 4.1 2 9.1 62.0 40.0 17.20 EC EC VFD 208/60/3 (1) (2) (3) (4) HP-2 MECH RM 141B FHP EC360-4VTC-FBF 12185 1540 1.40 2.00 5 74.0 61.0 55.0 54.0 90 11.8 57.0 85.0 30 3.3 2 26.4 187.0 100.0 41.70 EC EC VFD 460/60/3 (1) (2) (3) (4) HP-3 MECH RM 160 FHP EC360-4VTC-FBF 10650 1715 1.00 2.00 5 74.0 61.0 55.0 54.0 90 11.1 55.0 85.0 30 3.2 2 26.4 187.0 65.0 19.20 EC EC VFD 460/60/3 (1) (2) (3) (4) HP-4 WEST MECH RM FHP EC360-4VTC-FBF 10880 1060 1.40 2.00 5 74.0 61.0 55.0 54.0 90 10.9 60.0 85.0 30 3.3 2 26.4 187.0 90.0 28.40 EC EC VFD 460/60/3 (1) (2) (3) (4) HP-5 RM 141A FHP EC072-4VTC-FBT 2000 0 0.50 1.00 1 80.0 60.0 55.0 54.0 90 10.8 80.0 70.0 30 3.1 2 5.4 40.0 17.0 23.30 EC EC VFD 460/60/3 (1) (2) (3) (4) HP-6 RM 150 FHP EC072-4HZC-FBT 2000 0 0.50 1.00 1 80.0 60.0 55.0 54.0 90 10.8 80.0 70.0 30 3.1 2 5.4 40.0 17.0 23.30 EC EC VFD 460/60/3 (1) (2) (3) (4)

NOTES:

(1) EXTERNAL STATIC PRESSURE INCLUDES DUCTWORK, FILTERS, AND COILS NOT IN HP CASING.

(2) PROVIDE UNITS SUITABLE FOR USE WITH 20% PROPLEYENE GLYCOL SOLUTION.

(3) PROVIDE UNITS WITH HOSE KITS. HOSE KITS SHALL INCLUDE STAINLESS STEEL BRAID HOSES WITH SWIVEL CONNECTIONS, BALL VALVES, AUTOMATIC FLOW CONTROL VALVE, Y-STRAINER WITH PT TEST PORT, AND HONEYWELL 2 WAY 2 POSITION 24 VOLT VC SERIES CONTROL VALVE.

(4) PROVIDE SINGLE POINT ELECTRICAL CONNECTION TO UNIT.

LOCATIONPLAN

DESIGNATION

BASIS OF DESIGN

MANUFACTURER MODEL WATER PRESSURE

DROP (FT W.G.)

VOLTS/HZ/

PHASE

Disconnect by MC or

EC

Starter by MC or EC

NOTES

COMPRESSORHEATING PERFOMANCE

WATER

FLOW RATE

(GPM)

SUPPLY FAN COOLING PERFOMANCE

VFD or ATL

CHAD B.

WESTBROOK

WESTBROOK

DATE

PANEL 'HN1 (EXST)' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.

480Y/277-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: WESTINGHOUSE

100-AMP, MAIN LUGS ONLY MOUNTING: SURFACE

CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO

1 LN1 (VIA T1) 45 3 0.0 20 1 LTG. 147,149,151 2

3 --- ** * 0.0 20 1 LTG. 135,138,145,179 4

5 --- ** * 0.0 20 1 LTG. 102,133,134,139 6

7 EGRESS LTG. 20 1 0.0 15 3 EF 11 (RM 131) 8

9 SPACE 0.0 ** * --- 10

11 SPACE 0.0 ** * --- 12

13 SPACE 0.0 SPACE 14

15 SPACE 0.0 SPACE 16

17 SPACE 0.0 SPACE 18

19 SPACE 0.0 SPACE 20

21 SPACE 0.0 SPACE 22

23 SPACE 0.0 SPACE 24

25 SPACE 0.0 SPACE 26

27 SPACE 0.0 SPACE 28

29 SPACE 0.0 SPACE 30

PROJECT #JFSD200909E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 03/23/10

PANEL 'HN2 SECT1 (EXST) ' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.

480Y/277-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: WESTINGHOUSE

600-AMP, MAIN LUGS ONLY MOUNTING: SURFACE

CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO

1 SPACE 0.0 SPACE 2

3 RM 126 TEST BENCH 60 3 0.0 SPACE 4

5 --- ** * 0.0 15 3 SPARE 6

7 --- ** * 0.0 ** * --- 8

9 E.F. 8,9 15 3 0.0 ** * --- 10

11 --- ** * 0.0 15 3 AHU-2 12

13 --- ** * 0.0 ** * --- 14

15 LTG. 124, 164 20 1 0.0 ** * --- 16

17 LTG. 126, 165, 166 20 1 0.0 60 3 PUMP 6 18

19 PUMP 5 60 3 0.0 ** * --- 20

21 --- ** * 0.0 ** * --- 22

23 --- ** * 0.0 20 1 EGRESS LTG 24

25 HP-3 90 3 0.0 50 3 WH-2 26

27 --- ** * 0.0 ** * --- 28

29 --- ** * 0.0 ** * --- 30

PROJECT #JFSD200909E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 03/23/10

PANEL 'HN2 SECT2 (EXST)' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.

480Y/277-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: WESTINGHOUSE

100-AMP, MAIN LUGS ONLY MOUNTING: SURFACE

CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO

1 SPACE 0.0 SPACE 2

3 SPACE 0.0 SPACE 4

5 AC-1 15 3 0.0 60 3 PUMP 7 6

7 --- ** * 0.0 ** * --- 8

9 --- ** * 0.0 ** * --- 10

11 AC-2 15 3 0.0 40 3 HUM-3 12

13 --- ** * 0.0 ** * --- 14

15 --- ** * 0.0 ** * --- 16

17 LTG 116, 118, 126, 160, 162 20 1 0.0 20 1 LTG 106, 109, 112, 130 18

19 LTG 119, 120, 122, 123 20 1 0.0 20 1 LTG 103, 105, 108, 113, 115 20

21 LTG 127, 129 20 1 0.0 20 1 LTG 131, 132, 150, 152 22

23 CHILLER TEST BENCH 80 3 0.0 50 3 D-1,2,3,4 24

25 --- ** * 0.0 ** * --- 26

27 --- ** * 0.0 ** * --- 28

PROJECT #JFSD200909E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 03/23/10

PANEL 'HN3 (EXST)' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.

480Y/277-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: WESTINGHOUSEWESTINGHOUSE

400-AMP, MAIN LUGS ONLY MOUNTING: SURFACE

CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO

1 WH-4 50 3 0.0 30 3 AHU-1 2

3 --- ** * 0.0 ** * --- 4

5 --- ** * 0.0 ** * --- 6

7 HP-4 90 3 0.0 20 3 SUMP PIT FOR WEST SIDE 8

9 --- ** * 0.0 ** * --- 10

11 --- ** * 0.0 ** * --- 12

13 LTG C - 146 20 1 0.0 20 1 LTG 177, 178 14

15 --- 20 1 0.0 20 1 LTG 170, 171 173 176 16

17 --- 20 1 0.0 20 1 EXT LTG (WALL PACK) 18

19 SPARE 40 3 0.0 15 3 E.F. 6 20

21 --- ** * 0.0 ** * --- 22

23 --- ** * 0.0 ** * --- 24

25 HUM-4 50 3 0.0 15 3 E.F.7 26

27 --- ** * 0.0 ** * --- 28

29 --- ** * 0.0 ** * --- 30

31 SPARE 15 3 0.0 15 3 E.F. 4 32

33 --- ** * 0.0 ** * --- 34

35 --- ** * 0.0 ** * --- 36

37 TRANSFORMER 60 3 0.0 20 1 EGRESS LTG 38

39 --- ** * 0.0 SPACE 40

41 --- ** * 0.0 SPACE 42

PROJECT #JFSD200909E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 03/23/10

PANEL 'HE (EXST)' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.

480Y/277-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: WESTINGHOUSEWESTINGHOUSE

400-AMP, MAIN LUGS ONLY MOUNTING: SURFACE

CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO

1 75 KVA XFMR PANEL LE 150 3 0.0 20 3 HP-5 2

3 --- ** * 0.0 ** * --- 4

5 --- ** * 0.0 ** * --- 6

7 HP-2 90 3 0.0 125 3 SPARE 8

9 --- ** * 0.0 ** * --- 10

11 --- ** * 0.0 ** * --- 12

13 HUM-6 20 3 0.0 20 1 LTG 141A, 141B 14

15 --- ** * 0.0 20 1 LTG 122 16

17 --- ** * 0.0 20 1 SPARE 18

19 LTG RM 141 20 1 0.0 20 3 HP-6 20

21 LTG RM 141 20 1 0.0 ** * --- 22

23 LTG 142, 142, 144 20 1 0.0 ** * --- 24

25 CU-2 100 3 0.0 100 3 COMSES DISINTEGRATOR 26

27 --- ** * 0.0 ** * --- 28

29 --- ** * 0.0 ** * --- 30

31 HUM-2 40 3 0.0 50 3 UNKNOWN 32

33 --- ** * 0.0 ** * --- 34

35 --- ** * 0.0 ** * --- 36

37 SPACE 0.0 20 1 SPACE 38

39 SPACE 0.0 SPACE 40

41 SPACE 0.0 SPACE 42

PROJECT #JFSD200909E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 03/23/10