17-R-0011_WAFB_CATM_Attch_6_100_prcnt_Design_Drawings_Full_Set.pdf
PDF 20 MB Posted
- Attached to
- CATM Remodel
- Solicitation number
- FA4625-17-R-0011
About this file
Attachment 6 - 100% Design Drawings
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ARCHITECT
FINKLE + WILLIAMS ARCHITECTURE
7007 College Blvd, Suite 415 Overland Park, Kansas 66210
PH. 913.498.1550 F. 913.498.1042
CIVIL
FOUNDATIONS
STRUCTURAL
MECHANICAL
ELECTRICAL
OLSSON ASSOCIATES
7301 W. 133rd Street, Suite 200 Overland Park, KS 66213 Ph. (913)381-1170
PMA ENGINEERING
6717 Shawnee Mission Parkway, Ste 100 Overland Park, KS 66202 Ph.(913)831-1262
PMA ENGINEERING
6717 Shawnee Mission Parkway, Ste 100 Overland Park, KS 66202 Ph.(913)831-1262
OLSSON ASSOCIATES
1251 NW Briarcliff Parkway, Ste. 50 Kansas City, MO 64116 Ph.(816)361-1177
OLSSON ASSOCIATES
1251 NW Briarcliff Parkway, Ste. 50 Kansas City, MO 64116 Ph.(816)361-1177
GENERAL BUILDING INFORMATION
GENERAL BUILDING LIMITATIONS
BUILDING AREA
OCCUPANCY CLASSIFICATIONS
EXITING INFORMATION
913.498.1550 Overland Park, Kansas 66211 7007 College Blvd, Suite 415
FINKLE + WILLIAMS
A R C H I T E C T U R E
DRAWING SYMBOLS LEGEND GENERAL NOTES BUILDING SUMMARYPROFESSIONAL SERVICES DISCLAIMER
SIGNAGE REQUIREMENTS
PERMANENT ROOMS AND SPACES
TYPICAL ABBREVIATIONS
APPLICABLE CODES &
TECHNICAL REFERENCES
BID ALTERNATE
913.498.1550 Overland Park, Kansas 66211 7007 College Blvd, Suite 415
FINKLE + WILLIAMS
A R C H I T E C T U R E
7007 College Blvd, Suite 415
FINKLE + WILLIAMS
A R C H I T E C T U R E
GENERAL DEMOLITION NOTES
DEMOLITION PLAN NOTES
7007 College Blvd, Suite 415
FINKLE + WILLIAMS
SHEET NOTES
FE
C
913.498.1550 Overland Park, Kansas 66211 7007 College Blvd, Suite 415
FE
C
913.498.1550 Overland Park, Kansas 66211 7007 College Blvd, Suite 415
7007 College Blvd, Suite 415
7007 College Blvd, Suite 415
7007 College Blvd, Suite 415
7007 College Blvd, Suite 415
7007 College Blvd, Suite 415
7007 College Blvd, Suite 415
7007 College Blvd, Suite 415
DOOR TYPES
FRAME TYPES
MATERIALS TYP. DOOR LOCATION PLAN
HARDWARE SETS
WINDOW TYPES
913.498.1550 Overland Park, Kansas 66211 7007 College Blvd, Suite 415
FINKLE + WILLIAMS
A R C H I T E C T U R E
DOOR SCHEDULE LEGENDROOM FINISH SCHEDULE
ROOM
FLR.
BASE WALLS CEILING
HT. REMARKSNO. NAME N E S W N E S W MAT.
DOOR AND FRAME SCHEDULE
DOOR FRAME
RATING
DETAILS
HARDWARE REMARKSNO.
SIZE
TYPE MAT. TYPE MAT. JAMB HEAD SILLW. H. Th.
Window Schedule
NO.
Size Type
Frame Material
Glass Material RemarksW. H.
7007 College Blvd, Suite 415
4" BENEATH FLOOR SLAB
ASTM C-33, #
57 STONE
65% OF RELATIVE
DENSITY
AS NECESSARY TO
OBTAIN DENSITY
NOTE:
TABLE INFORMATION FROM SECTION D.2 TABLE 1 OF GEOTECHNICAL REPORT REFERENCE IN NOTE 17 OF 1/S0.1.
18" BELOW THE BASE OF THE
GRANULAR LAYER
LL<50
PI<25
ON SITE / IMPORTED
COHESIVE
SOILS
0 TO +4 PERCENT
95%
95% OF STANDARD
PROCTOR
0 TO +4 PERCENT
MODOT TYPE
5 BASEROCK
95% AS NECESSARY TO
OBTAIN DENSITY
C :\P
- C
AT
M
R ep ai r 2
5_ dh ay w ar d.
rv t
15098 (P15179)
05.02.16
100% DESIGN SET
S0.1
GENERAL
NOTES
DO 5022 CATM
Range Repair
WHITEMAN AIR FORCE BASE
MISSOURI
1. BUILDING CODE - 2012 INTERNATIONAL BUILDING CODE
ETL 11-18: SMALL ARMS RANGE DESIGN & CONSTRUCTION
2. DESIGN LOADS:
A. FLOOR LIVE LOADS
a. FLOORS (NON-REDUCED) 100 PSF
b. CONCENTRATED LOAD ON ELEVATED FLRS 2000 LBS
c. CONCENTRATED LOAD ON STAIR TREADS 300 LBS
B. ROOF LIVE LOAD 20 PSF
C. ROOF SNOW LOAD
a. GROUND SNOW LOAD, Pg 20 PSF
b. FLAT ROOF SNOW LOAD, Pf 20 PSF
c. SNOW EXPOSURE FACTOR, Ce 1.0
d. RISK CATEGORY II
e. SNOW LOAD IMPORTANCE FACTOR, I 1.0
f. THERMAL FACTOR, Ct
UNHEATED STRUCTURE 1.2
g. DRIFTING PER CODE
D. WIND LOADS
a. BASIC WIND SPEED (3 SECOND GUST), V(ULTIMATE) 115 MPH
V(SERVICE) 90 MPH
b. RISK CATEGORY II
c. WIND EXPOSURE C
d. INTERNAL PRESSURE COEFFICIENT +/- 0.18
e. COMPONENT & CLADDING PRESSURE SEE TABLE 4/S0.2
E. SEISMIC LOADS
a. RISK CATEGORY II
b. SPECTRAL ACCELERATION Ss = 0.129g, S1 = 0.078g
c. SEISMIC IMPORTANCE FACTOR, I 1.0
d. SPECTRAL RESPONSE COEFFICIENTS
SDS 0.138
SD1 0.0125
e. SITE CLASS D
f. SEISMIC DESIGN CATEGORY B
g. BASIC SEISMIC-FORCE-RESISTING SYSTEM STEEL SYSTEM NOT SPECIFICALLY
DETAILED FOR SEISMIC & ORIDINARY REINFORCED CONCRETE WALLS
h. RESPONSE MODIFICATION FACTOR, R 3
i. SEISMIC RESPONSE COEFFICIENT, Cs 0.046
j. DESIGN BASE SHEAR 0.046W
l. ANALYSIS PROCEDURE EQUIVALENT LATERAL FORCE
F. DEAD LOADS
a. STRUCTURE ACTUAL WEIGHT
b. UNDERHUNG BAFFLE SYSTEM 25 PSF
c. ROOF STRUCTURE (LOW ROOF) 20 PSF
G. THE STRUCTURAL SYSTEMS SHOWN ON THESE DOCUMENTS HAVE BEEN DESIGNED FOR THE FINAL, IN PLACE USAGE OF THE STRUCTURE BASED ON THE INTENDED OCCUPANCY AND CODE REQUIREMENTS.
WHILE GENERAL CONSTRUCTABILITY HAS BEEN CONSIDERED, THE STRUCTURAL SYSTEMS HAVE NOT BEEN DESIGNED TO ACCOMMODATE SPECIFIC CONSTRUCTION MEANS AND METHODS THAT MIGHT BE
UTILIZED BY THE CONTRACTOR.
3. SPECIAL INSPECTIONS
A. THE FOLLOWING ITEMS REQUIRE SPECIAL INSPECTION IN ACCORDANCE WITH THE BUILDING CODE.
a. CONCRETE DESIGN MIX
b. PLACING OF CONCRETE AND REINFORCING STEEL
c. BOLTS & ANCHORS EMBEDDED IN CONCRETE
d. STRUCTURAL STEEL FABRICATIONS
e. STRUCTURAL STEEL BOLTING & WELDING
f. INSPECTION OF ROOF DECK ATTACHMENT
g. IN-SITU STRUCTURAL FRAMING
h. POST INSTALLED ANCHORS IN CONCRETE
i. IN-SITU SOILS, EXCAVATIONS, FILLING & COMPACTION
B. THE CONTRACTOR SHALL REQUEST SPECIAL INSPECTION OF THE ITEMS LISTED ABOVE PRIOR TO THOSE ITEMS BECOMING INACCESSIBLE AND UNOBSERVABLE DUE TO PROGRESSION OF THE WORK.
4. STRUCTURAL ENGINEER SITE OBSERVATIONS
A. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED
STRUCTURE, AND, EXCEPT WHERE SPECIFICALLY SHOWN, DO NOT INDICATE THE METHOD OR MEANS
OF CONSTRUCTION. THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK AND SHALL BE
SOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS, PROCEDURES, TECHNIQUES, AND
SEQUENCE.
B. THE ENGINEER SHALL NOT HAVE CONTROL NOR CHARGE OF, AND SHALL NOT BE RESPONSIBLE FOR, CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES, OR PROCEDURES, FOR SAFETY
PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK, FOR THE ACTS OR OMISSION OF THE CONTRACTOR, SUBCONTRACTOR, OR ANY OTHER PERSONS PERFORMING ANY OF THE WORK, OR FOR
THE FAILURE OF ANY OF THEM TO CARRY OUT THE WORK IN ACCORDANCE WITH THE CONTRACT
DOCUMENTS.
5. CONDITIONS AND DIMENSIONS SHOWN HAVE BEEN TAKEN FROM EXISTING DRAWINGS, FIELD MEASUREMENTS AND FIELD OBSERVATIONS. DETAILS HAVE BEEN DEVELOPED BASED ON THE BEST AVAILABLE INFORMATION.
CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND DIMENSIONS SHOWN PRIOR TO FABRICATION, AND IF THE AS-BUILT CONDITION IS DIFFERENT THAN REPRESENTED IN THESE DOCUMENTS, SHALL NOTIFY THE
ENGINEER PRIOR TO PROCEEDING WITH THE WORK.
6. REFERENCE THE SPECIFICATION FOR ADDITIONAL REQUIREMENTS.
7. SEE ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND CIVIL DRAWINGS FOR OTHER PERTINENT INFORMATION RELATED TO THE STRUCTURAL WORK AND COORDINATE AS REQUIRED. THESE STRUCTURAL DRAWINGS ARE INTENDED TO BE UTILIZED AS A COMPLETE SET OF DOCUMENTS THAT REPRESENT THE BUILDINGS STRUCTURAL SYSTEMS. NO SINGLE SHEET OR SERIES OF SHEETS IS INTENDED TO “STAND ALONE”. THESE STRUCTURAL DRAWINGS ARE INTENDED TO BE INCLUDED IN A COMPLETE SET OF CONSTRUCTION DOCUMENTS, INCLUDING BUT NOT LIMITED TO: ARCHITECTURAL DRAWINGS, CIVIL DRAWINGS, AND MECHANICAL/ ELECTRICAL/ PLUMBING DRAWINGS. CONTRACTOR SHALL VERIFY COORDINATION OF THESE DRAWINGS WITH CONTENTS OF ABOVE DRAWING SETS SPECIFIED AND ONLY PROCEED WITH BIDDING AND
CONSTRUCTION AFTER SUCH HAS TAKEN PLACE.
8. DETAILS LABELED “TYP” OR “TYPICAL” ARE TO BE APPLIED AT LOCATIONS THAT ARE SAME OR SIMILAR TO THOSE SPECIFICALLY INDICATED. WHERE A DETAIL IS NOT INDICATED, THE DETAIL SHALL BE THE SAME AS
FOR SIMILAR CONDITIONS OR AS SHOWN IN THE “TYPICAL DETAILS”.
9. THE BUILDING IS NOT STRUCTURALLY STABLE UNTIL ALL CONNECTIONS, FRAMING, SHEAR WALLS, DIAPHRAGMS, PERMANENT BRACING, METAL DECKING, AND EXTERIOR LOAD-BEARING WALLS ARE COMPLETE AND HAVE ACHIEVED THEIR DESIGN STRENGTH. CONTRACTOR IS SOLELY RESPONSIBLE FOR MAINTAINING STRUCTURAL STABILITY DURING ERECTION AND CONSTRUCTION. TEMPORARY BRACING SYSTEMS ARE NOT
TO BE REMOVED UNTIL STRUCTURAL WORK IS COMPLETE.
10. REINFORCING STEEL:
A. ALL REINFORCING STEEL SHALL BE ASTM A615 GRADE 60, EXCEPT WELDED REINFORCING WHICH
SHALL BE ASTM A706 GRADE 60.
B. ALL WELDED WIRE FABRIC SHALL BE ASTM A185 AND A82 COLD DRAWN WIRE.
C. ALL ACCESSORIES FOR SUPPORTING REINFORCING SHALL BE GALVANIZED OR HAVE
PLASTIC-COATED FEET.
D. PROVIDE CORNER BARS AT THE EXTERIOR FACE OF ALL WALL AND FOOTING CORNERS EQUAL TO
HORIZONTAL BARS.
E. PROVIDE AT LEAST TWO VERTICAL #5 BARS AT ALL STEPS IN FOUNDATION WALLS, FOOTINGS, AND
GRADE BEAMS.
F. REINFORCING SHALL BE DETAILED, FABRICATED, PLACED, AND SUPPORTED IN ACCORDANCE WITH
ACI 315, LATEST EDITION.
G. THE FOLLOWING ADDITIONAL REINFORCING STEEL SHALL BE PROVIDED IN STOCK LENGTHS FOR
GENERAL JOB USE AS DIRECTED BY THE ENGINEER.
5 - #4X30-0
H. STANDARD COVERAGE OF REINFORCING, UNLESS OTHERWISE SHOWN, SHALL BE AS FOLLOWS:
CAST AGAINST EARTH, PERMANENTLY EXPOSED TO WEATHER 3"
EXPOSED TO EARTH & WEATHER (FORMED) 2"
I. ALL LAP SPLICES SHALL BE CLASS B UNLESS NOTED OTHERWISE.
J. FOR REINFORCING BAR LAP LENGTHS IN CONCRETE, SEE TABLE 2/S0.2.
11. CONCRETE:
A. CAST-IN-PLACE CONCRETE CONSTRUCTION SHALL COMPLY WITH THE APPLICABLE BUILDING
CODE REQUIREMENTS, INDUSTRY GUIDES AND REFERENCE STANDARDS INCLUDING, BUT NOT
LIMITED TO:
a. ACI 301 - SPECIFICATIONS FOR STRUCTURAL CONCRETE
b. ACI 305R - GUIDE TO HOT WEATHER CONCRETING
c. ACI 306R - GUIDE TO COLD WEATHER CONCRETING
d. ACI 318 - STRUCTURAL CONCRETE BUILDING CODE
e. ACI 347 - GUIDE TO FORMWORK FOR CONCRETE
f. ACI SP-66 - ACI DETAILING MANUAL
g. AWS D1.4 - STRUCTURAL WELDING CODE - REINFORCING STEEL
h. CRSI - MANUAL OF STANDARD PRACTICE
B. ALL CONCRETE, UNLESS OTHERWISE NOTED, SHALL DEVELOP A 28 DAY COMPRESSIVE STRENGTH
OF 4.500 PSI AND HAVE MAXIMUM WATER/CEMENT RATIO OF 0.45.
C. CONCRETE EXPOSED TO WEATHER, VEHICLES AND/OR DEICING CHEMICALS SHALL BE
AIR-ENTRAINED WITH 6% (+/-) 1.5% ENTRAINED AIR BY VOLUME AT POINT OF DISCHARGE. DO NOT
ALLOW AIR CONTENT OF TROWELED FINISHED FLOORS TO EXCEED 3%.
D. IT IS THE INTENT OF THESE CONCRETE SPECIFICATIONS THAT THE CONTRACTOR SUPPLY
CONCRETE MIXES WITH A MINIMUM AMOUNT OF WATER IN ORDER TO LIMIT PLASTIC SHRINKAGE CRACKING IN FRESHLY PLACED CONCRETE. IT IS EXPECTED THAT PRODUCING WORKABILITY FOR CONCRETE MIXES WILL REQUIRE THE ADDITION OF WATER-REDUCING AND/OR SUPER-PLASTICIZING
CHEMICAL ADMIXTURES.
E. CONCRETE SLUMP SHALL BE A MAXIMUM OF 4" +/- 1" (ASTM C-143) AS DELIVERED IN THE FIELD.
CONTRACTOR MAY USE CHEMICAL ADMIXTURES TO ATTAIN A MAXIMUM SLUMP OF 8" FOR
WORKABILITY.
F. NO WATER MAY BE ADDED TO THE CONCRETE MIX ON SITE.
G. FLY ASH MAY BE USED AT A RATE NOT TO EXCEED 25% OF THE TOTAL CEMENT CONTENT.
H. CHAMFER ALL EXPOSED CORNERS OF CONCRETE WALLS, BEAMS, AND COLUMNS 3/4".
I. ALL CONTROL JOINTS IN CONCRETE SLABS-ON-GRADE SHALL BE CUT TO 1/3 OF THE DEPTH. CUT
JOINTS AS SOON AS POSSIBLE AFTER CONCRETE HAS BEEN PLACED WITHOUT DISLODGING
AGGREGATE, OR USE KEYED COLD JOINT.
J. THE UNIT POUR FOR SLABS AND WALLS SHALL NOT EXCEED 100 LINEAL FEET IN ANY ONE
DIRECTION. CUT SLABS TO 1/3 THE DEPTH ON GRID LINES INTO AREAS OF ABOUT 150 SQUARE
FEET.
K. PRIOR TO PLACING CONCRETE IN ANY LOCATION, IT IS THE RESPONSIBILITY OF THE GENERAL
CONTRACTOR TO HAVE THOROUGHLY CHECKED AND COORDINATED ALL DIMENSIONS,
ELEVATIONS, OPENINGS, RECESSES, AND BLOCKOUTS SHOWN ON THE ARCHITECTURAL,
STRUCTURAL, AND MECHANICAL DRAWINGS. IN THE EVENT ERRORS, CONFLICTS, OR OMISSIONS
EXIST, IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO CONTACT THE CONTRACTING
OFFICER FOR NECESSARY CORRECTIVE ACTION.
L. EMBEDDED ITEMS ARE TO BE FURNISHED AND INSTALLED BY THE CONTRACTOR PRIOR TO
PLACING CONCRETE.
M. ANCHOR RODS SHALL BE HELD IN PLACE WITH A RIGID TEMPLATE.
N. CAST-IN-PLACE CONCRETE REPAIRS - (THIN PATCHES - 3" MAX SURFACE DEPTH):
WHERE CONCRETE MATERIAL HAS BEEN REMOVED TO A MAXIMUM DEPTH OF 1 1/2" THE PATCH
SHALL BE FILLED WITH A CEMENTITIOUS REPAIR MORTAR AS SPECIFIED BELOW.
CONTRACTOR SHALL REMOVE LOOSE CONCRETE WITHOUT DAMAGING THE EXISTING REINFORCING
BARS AND WIRE MESH WHILE MINIMIZING MICROCRACKING IN THE SURROUNDING CONCRETE
MATERIAL. USE HAND TOOLS OR PNEUMATIC TOOLS THAT DELIVER NO MORE THAN 15 FT/LBS OF
IMPACT TO REMOVE LOOSE SPALLING OR DETERIORATED SURFACE CONCRETE. REMOVE TO A
DEPTH WHERE SOUND CONCRETE IS ENCOUNTERED. PATCH DEPTH SHALL NOT BE LESS THAN
3/8" AT ANY LOCATION.
EXISTING REINFORCING BARS AND WIRE REINFORCING MESH SHALL REMAIN IN PLACE. DO NOT
CUT OUT EXISTING REINFORCING BARS DURING CONCRETE REMOVAL OPERATIONS.
AREA TO BE PATCHED, INCLUDING EXPOSED REINFORCING BARS, SHALL BE SANDBLASTED OR
SHOT BLASTED TO REMOVE RUST, CONCRETE RESIDUE, AND OTHER CONTAMINANTS SUCH AS OIL, RUST, DIRT, EFFLORESCENCE, ETC. PROVIDE 1/4" PROFILE AMPLITUDE TO THE CONCRETE SUBSTRATE.
PRIME COAT ALL EXISTING EXPOSED REINFORCING STEEL BARS AND WIRE MESH AND EXPOSED
CONCRETE SURFACES WITH SIKA ARMATEC 110 EPOCEM BONDING AGENT AND ANTI-CORROSION
PROTECTION COATING OR EQUAL. APPLY PER MANUFACTURER'S SPECIFICATIONS.
REBUILD CONCRETE SURFACE TO MATCH ORIGINAL SHAPE WITH AN APPROVED CEMENTITIOUS
REPAIR MORTAR OR GROUT OF 3500 PSI MINIMUM. APPLY PER MANUFACTURER'S SPECIFICATIONS.
PATCH AREA SHALL BE HAND TROWELED TO MATCH THE ORIGINAL MEMBER DIMENSIONS AND
SURFACE PROFILE AS CLOSELY AS POSSIBLE.
12. STRUCTURAL STEEL:
A. ALL STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED, AND ERECTED IN ACCORDANCE WITH
AISC SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS ALLOWABLE STRESS DESIGN AND
PLASTIC DESIGN, LATEST EDITION AND AISC CODE OF STANDARD PRACTICE.
B. ALL STRUCTURAL STEEL FOR WIDE FLANGE & WT SHAPES SHALL BE A992 GRADE 50 UNLESS
NOTED OTHERWISE ON THE PLANS. ALL ANGLES, PLATES, AND CHANNELS AND SHALL BE ASTM
A36 UNLESS NOTED OTHERWISE. ALL RECTANGULAR AND ROUND HSS SHAPES SHALL BE ASTM
A500, GRADE B.
C. ALL BEAM CONNECTIONS SHALL BE DESIGNED AS SIMPLY SUPPORTED BEAMS BY THE STEEL
FABRICATOR FOR THE LOADS SHOWN ON THESE DOCUMENTS. LOADS AND REACTIONS SHOWN
ON THESE DOCUMENTS ARE NON-FACTORED, WORKING STRESS VALUES (ASD). CONNECTIONS
MAY BE BOLTED OR WELDED.
D. ALL BOLTS SHALL BE 3/4" DIAMETER MINIMUM UNLESS NOTED OTHERWISE ON DRAWINGS.
a. SLIP CRITICAL CONNECTIONS OF A325SC OR A490SC BOLTS SHALL BE USED FOR ALL
BOLTED CONNECTIONS OF BRACING MEMBERS, MOMENT CONNECTIONS, CANTILEVERS,
AND AS SHOWN ON THESE DOCUMENTS.
b. ALL OTHER CONNECTIONS SHALL BE SNUG-TIGHTENED BEARING TYPE USING A MINIMUM
OF TWO A325N OR A490N BOLTS.
E. ALL STRUCTURAL STEEL WELDS IN THE SHOP OR THE FIELD SHALL BE PERFORMED BY A
QUALIFIED WELDER AND SHALL CONFORM TO THE CURRENT REQUIREMENTS OF A.W.S.
F. SHOP WELDED AND FIELD BOLTED CONNECTIONS ARE PREFERRED, UNLESS OTHERWISE SHOWN.
G. FILLET WELDS NOT SPECIFICALLY SIZED IN THESE DOCUMENTS SHALL BE THE MINIMUM SIZE IN ACCORDANCE WITH AWS D1.1 LATEST EDITION, DEPENDENT ON THE THINNER PART JOINED, BUT
NO LESS THAN 3/16”.
H. WELDING ELECTRODES SHALL BE E70XX.
I. STEEL JOISTS SHALL BE FABRICATED AND ERECTED (INCLUDING BRIDGING) IN ACCORDANCE WITH THE LATEST SPECIFICATIONS OF THE STEEL JOIST INSTITUTE AND ALL OSHA REQUIREMENTS.
JOISTS SHALL HAVE 2-1/2" BEARING DEPTH FOR K SERIES JOISTS. DESIGN AND WELD JOISTS FOR THE FOLLOWING NOMINAL WIND PRESSURES AT ULTIMATE LOAD LEVEL (LRFD): 27.5 PSF NET UPLIFT IN FIELD, 32.5 NET UPLIFT WITHIN 7.5 FEET OF EDGES AND 32.5 PSF NET UPLIFT WITHIN 7.5 FEET OF CORNERS. AT A MINIMUM, ENDS OF BRIDGING SHALL HAVE DIAGONAL CROSS BRACING BETWEEN
THE LAST TWO JOISTS IN ADDITION TO HORIZONTAL BRIDGING.
J. STEEL ROOF DECK SHALL BE AS NOTED ON PLAN, WITH NESTED SIDELAPS, ATTACHED TO
SUPPORTS IN A PATTERN TO RESIST THE FOLLOWING NOMINAL WIND PRESSURES AT ULTIMATE
LOAD LEVEL (LRFD): 30 PSF NET UPLIFT IN FIELD, 51 PSF NET UPLIFT WITHIN 7.5 FEET OF EDGES AND 51 PSF NET UPLIFT WITHIN 7.5 FEET OF CORNERS. IN ADDITION TO THE NET UPLIFT PRESSURES, ROOF DECK SHALL BE ATTACHED TO SUPPORTS FOR DIAPHRAGM SHEAR AS SHOWN ON THE PLAN
DOCUMENTS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. ROOF DECK
ATTACHMENT SHALL BE DESIGNED FOR THE COMBINED EFFECTS OF UPLIFT AND DIAPHRAGM
SHEAR INTERACTION.
K. ALL OPENINGS IN ROOF OVER 8" IN ANY DIRECTION SHALL HAVE A 3 X 3 X 1/4 ANGLE FRAME
(4 SIDES) BETWEEN JOISTS, UNLESS OTHERWISE NOTED ON DRAWINGS.
L. ROOF EDGE ANGLES AND BENT PLATES INDICATED IN THESE DOCUMENTS TO BE CONTINUOUS
SHALL BE FIELD SPLICED AS SHOWN IN THE DETAILS.
M. THE CONTRACTOR SHALL PROVIDE SHELF ANGLES, GLASS SUPPORTS, LINTELS AND OTHER
MISCELLANEOUS STEEL, AS SHOWN ON THE DRAWINGS AND AS REQUIRED TO PROVIDE SUPPORT
(STABILIZATION) AROUND AND THROUGHOUT THE BUILDING. NOT EVERY DETAIL IS SHOWN. SEE
ARCHITECTURAL DRAWINGS FOR ADDITIONAL MISCELLANEOUS STEEL DETAILS.
13. POST-INSTALLED ANCHORAGE:
A. DESIGN OF ALL POST-INSTALLED ANCHORAGE SHALL BE IN ACCORDANCE WITH ACI-318 APPENDIX
D AND SHALL CONSIDER CRACKED CONCRETE CONDITIONS.
B. ALL POST-INSTALLED ANCHORS SHALL BE INSTALLED BY TRAINED PERSONNEL PER THE
MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS (MPII) AS SHOWN IN THE CORRESPONDING
ICC-ESR REPORT AND INCLUDED IN THE ANCHOR PACKAGING
C. THE CONTRACTOR SHALL ARRANGE AN ANCHOR MANUFACTURER'S REPRESENTATIVE TO PROVIDE
ONSITE INSTALLATION TRAINING FOR ALL OF THEIR ANCHORING PRODUCTS SPECIFIED. THE
CONTRACTING OFFICER MUST RECEIVE DOCUMENTED CONFIRMATION THAT ALL OF THE
CONTRACTOR'S PERSONNEL WHO INSTALL POST-INSTALLED ANCHORAGE ARE TRAINED PRIOR TO
THE COMMENCEMENT OF INSTALLING ANCHORS.
D. ADHESIVE ANCHORS SUPPORTING SUSTAINED TENSION LOADS THAT ARE ORIENTED HORIZONTALLY
OR UPWARDLY INCLINED SHALL BE INSTALLED BY PERSONNEL CERTIFIED BY AN APPLICABLE
CERTIFICATION PROGRAM SUCH AS THE ACI/CRSI ADHESIVE ANCHOR INSTALLER CERTIFICATION
PROGRAM. AN APPLICABLE CERTIFICATION PROGRAM SHALL INCLUDE WRITTEN AND
PERFORMANCE TESTS IN ACCORDANCE WITH THE ACI/CRSI CERTIFICATION PROGRAM AND SHALL
BE SUBMITTED TO THE CONTRACTING OFFICER FOR APPROVAL PRIOR TO INSTALLATION.
E. THE CONTRACTOR SHALL SUBMIT PRODUCT SPECIFICATIONS WITH RECOMMENDED DESIGN VALUES
AND PHYSICAL CHARACTERISTICS FOR ADHESIVE AND MECHANICAL ANCHORS.
F. THE CONTRACTOR SHALL SUBMIT CERTIFIED TEST REPORTS (ICC ES EVALUATION REPORT)
SHOWING COMPLIANCE WITH SPECIFIED PERFORMANCE CHARACTERISTICS AND PHYSICAL
PROPERTIES.
G. EXISTING REINFORCING BARS IN THE CONCRETE STRUCTURE MAY CONFLICT WITH SPECIFIC ANCHOR LOCATIONS. EXISTING REINFORCING BARS SHALL NOT BE CUT UNLESS NOTED OTHERWISE ON THE DRAWINGS. THE CONTRACTOR SHALL REVIEW THE EXISTING STRUCTURAL DRAWINGS AND SHALL UNDERTAKE TO LOCATE THE POSITION OF THE REINFORCING BARS AT THE LOCATIONS OF THE CONCRETE ANCHORS BY FERROSCAN, GPR, X-RAY OR OTHER MEANS PRIOR TO INSTALLATION
OF ANCHORS.
H. ANCHOR CAPACITY IS DEPENDANT UPON SPACING BETWEEN ADJACENT ANCHORS AND PROXIMITY
OF ANCHORS TO EDGE OF CONCRETE. INSTALL ANCHORS IN ACCORDANCE WITH SPACING AND
EDGE CLEARANCES INDICATED ON THE DRAWINGS.
I. EMBEDMENT DEPTH FOR MECHANICAL EXPANSION ANCHORS SHALL BE DEFINED AS THE DISTANCE
FROM THE SURFACE OF THE LOAD-BEARING BASE MATERIAL TO THE DEEPEST PART OF THE
ANCHOR WHICH TENSION LOAD IS TRANSFERRED TO THE CONCRETE, MEASURED PRIOR TO
APPLYING TORQUE TO THE ANCHOR.
J. EMBEDMENT DEPTH FOR ADHESIVE AND SCREW TYPE ANCHORS SHALL BE DEFINED AS THE
DISTANCE FROM THE SURFACE OF THE LOAD-BEARING BASE MATERIAL TO THE DEEPEST PART
OF THE ANCHOR AFTER THE ANCHOR HAS BEEN INSTALLED INTO THE HOLE.
K. ADHESIVE ANCHORING SYSTEMS SHALL BE ACCEPTABLE FOR LONG-TERM LOADING. ONLY
NON-EPOXY (HYBRID) BASED ADHESIVES SHALL BE USED WHEN BASE MATERIAL TEMPERATURES
ARE BELOW 40 DEG F.
L. POST-INSTALLED ANCHORAGE SHALL ONLY BE USED WHERE SPECIFIED ON THESE DOCUMENTS.
THE CONTRACTOR SHALL OBTAIN APPROVAL FROM THE CONTRACTING OFFICER PRIOR TO USING
POST-INSTALLED ANCHORAGE FOR MISSING OR MISLOCATED CAST-IN-PLACE ANCHORS. CARE
SHALL BE TAKEN TO AVOID CONFLICTS WITH EXISTING REINFORCING BARS.
M. STAINLESS STEEL ANCHORS ARE REQUIRED AT ALL EXPOSED LOCATIONS.
N. FOR PRODUCTS OTHER THAN THOSE SPECIFIED BELOW, CONTRACTOR SHALL SUBMIT DATA
SUBSTANTIATING THE SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING EQUIVALENT
PERFORMANCE VALUES (MINIMUM) AND BEHAVIOR OF THE SPECIFIED PRODUCT USING THE
APPROPRIATE DESIGN PROCEDURE AND/OR STANDARD(S) AS REQUIRED BY THE BUILDING CODE.
POST-INSTALLED ANCHOR SUBSTITUTIONS SHALL BE APPROVED BY THE ENGINEER OF RECORD
PRIOR TO THEIR USE.
O. SUBMITTALS ARE THE CONTRACTOR'S RESPONSIBILITY AND MUST INCLUDE EVALUATION
REPORTS FROM THE INTERNATIONAL CODE COUNCIL.
P. CONCRETE ANCHORS
a. MECHANICAL ANCHORS FOR USE IN CRACKED AND UNCRACKED CONCRETE SHALL HAVE
BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI 355.2 AND
ICC-ES AC193. PRE-APPROVED MECHANICAL ANCHORS INCLUDE:
1. HILTI KWIK BOLT TZ EXPANSION ANCHOR (ICC-ES ESR-1917)
2. HILTI HSL-3 HEAVY DUTY EXPANSION ANCHOR (ICC-ES ESR-1545)
3. HILTI HDA UNDERCUT ANCHOR (ICC-ES ESR- 1546)
4. HILTI KWIK HUS EZ SCREW ANCHOR (ICC-ES ESR-3027)
5. SIMPSON STRONG-TIE STRONG-BOLT 2 WEDGE ANCHOR (ICC-ES ESR-3037)
6. SIMPSON STRONG-TIE TITEN-HD SCREW ANCHOR (ICC-ES ESR-2713)
b. ADHESIVE ANCHORING SYSTEMS FOR USE IN CRACKED AND UNCRACKED CONCRETE
SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI 355.4 AND
ICC-ES AC308. PRE-APPROVED ADHESIVE ANCHORING SYSTEMS INCLUDE:
1. HILTI HIT-HY 200 ADHESIVE ANCHORING SYSTEM (ICC-ES ESR-3187)
2. HILTI HIT-RE 500-SD ADHESIVE ANCHORING SYSTEM (ICC-ES ESR-2322)
3. SIMPSON STRONG-TIE SET-XP ADHESIVE ANCHOR SYSTEM (ICC-ES ESR-2508)
14. LIGHT GAGE METAL FRAMING:
A. ALL LIGHT GAGE METAL FRAMING AND CONNECTIONS SHALL BE FABRICATED, AND ERECTED IN ACCORDANCE WITH AISI “SPECIFICATION FOR THE DESIGN OF COLD FORMED STEEL STRUCTURAL
MEMBERS” AND NAAMM ML/SFA 540 “LIGHTWEIGHT STEEL FRAMING SYSTEMS MANUAL.”
B. ALL LIGHT GAGE METAL FRAMING IDENTIFICATION SHOWN IN THESE DOCUMENTS IS IN
ACCORDANCE WITH THE STEEL STUD MANUFACTURERS ASSOCIATION (SSMA).
C. ALL STRUCTURAL MEMBERS SHALL BE FORMED FROM STEEL HAVING A GALVANIZED COATING
MEETING THE REQUIREMENTS OF ASTM A-653. STEEL MATERIAL SHALL HAVE A MINIMUM YIELD STRESS OF 33 KSI EXCEPT MEMBERS OF 54 MIL THICKNESS OR HEAVIER SHALL HAVE A MINIMUM
YIELD STRESS OF 50 KSI.
D. ALL CONNECTIONS SHALL BE MADE WITH A MINIMUM OF (4) #10-16 SCREWS OR EQUIVALENT
WELDS. (UNLESS NOTED OTHERWISE ON THE DRAWINGS)
E. ALL SCREWS SHALL BE OF THE DIAMETER AND SIZE INDICATED ON THE DRAWINGS, AND SHALL
BE THOSE MANUFACTURED AND TESTED BY ITW BUILDEX. MINIMUM SPACING AND EDGE
DISTANCE FOR SCREWS SHALL BE THE GREATER OF EITHER 1/2 INCH OR 3 X SHANK DIAMETER, UNLESS NOTED OTHERWISE ON THE DRAWINGS. SCREW PENETRATION THROUGH JOINED
MATERIALS SHALL NOT BE LESS THAN THREE EXPOSED THREADS. SELECT SCREWS WITH AN
ADEQUATE CUTTING TIP TO ACCOMMODATE THE TOTAL THICKNESS TO BE DRILLED. DRILLING
MUST BE COMPLETED BEFORE THE THREADS ENGAGE THE MATERIAL. WHERE SCREW
ATTACHMENTS ARE MADE TO FRAMING COMPONENTS OF DIFFERENT THICKNESSES, THE
THINNEST COMPONENT MUST BE PENETRATED FIRST. (UNLESS NOTED OTHERWISE) ALL
SCREWS ARE TYPE 'T1'.
F. DIAGONAL STRAP BRACING SHALL BE ATTACHED AT ALL INTERSECTIONS WITH VERTICAL
MEMBERS WITH A #10-16 SCREW OR EQUIVALENT WELDS.
G. WELDING SHALL BE DONE IN ACCORDANCE WITH AWS D1.3 - LATEST EDITION, STRUCTURAL
WELDING CODE, SHEET STEEL.
H. SUGGESTED WELD METAL AND PROCESS FOR SHOP WELDING ARE: 70 ksi WELD METAL
STRENGTH (MINIMUM). SUGGESTED METHODS FOR FIELD WELDING: 1/8" (UNLESS NOTED
OTHERWISE) E70XX (MINIMUM) ELECTRODE - SMAW; OR”GASLESS” MIG.
I. MINIMUM WELD THROAT THICKNESS (t) MUST MATCH OR EXCEED THE BASE STEEL THICKNESS
OF THE THINNEST CONNECTED PART UNLESS NOTED OTHERWISE.
J. WEB STIFFENERS FOR STUD JOISTS SHALL BE PROVIDED AT ALL REACTION POINTS,
INTERMEDIATE CONCENTRATED LOADS, AND WHERE INDICATED ON THE DRAWINGS.
K. SEQUENCING OF WELDS SHALL BE SO AS TO AVOID DISTORTION OF MEMBERS. REPLACE ALL
MEMBERS WHEN BURN THROUGH OCCURS DURING WELDING.
L. ALL FRAMING COMPONENTS SHALL BE CUT SQUARELY FOR ATTACHMENT TO PERPENDICULAR
MEMBERS OR AS REQUIRED ON ANGULAR FIT AGAINST ABUTTING MEMBERS. MEMBERS SHALL BE
HELD POSITIVELY IN PLACE UNTIL PROPERLY FASTENED.
M. NO SPLICES IN STUDS, JOISTS, OR OTHER LOAD CARRYING MEMBERS MAY BE MADE WITHOUT
PRIOR ENGINEERING REVIEW AND SPECIFIC DETAILS FOR ANY SUCH SPLICE(S).
N. TRACK MEMBERS SHALL MATCH DEPTH AND MIL THICKNESS (GAGE) OF STUDS UNLESS NOTED
OTHERWISE.
15. LOAD-BEARING METAL STUDS
A. MECHANICAL BRIDGING, SPACED AT THE INTERVALS DESCRIBED HEREIN, SHALL BE INSTALLED
PRIOR TO THE ATTACHMENT OF FACING MATERIALS.
B. MECHANICAL BRIDGING SHALL BE INSTALLED, IN THE FORM OF COLD ROLLED CHANNELS AND CONNECTION CLIPS, IN ALL WALLS ON THIS PROJECT. SEE TYPICAL LIGHT GAGE METAL FRAMING
DETAILS ON THE DRAWINGS FOR SPECIFIC REQUIREMENTS.
C. ALL LIGHT GAGE METAL FRAMING SHOWN ON THESE DOCUMENTS IS BASED ON THE PHYSICAL
AND STRUCTURAL PROPERTIES OF SSMA METAL STUDS. ANY SUBSTITUTIONS MUST MEET THE
MINIMUM PROPERTIES PROVIDED BY THESE MEMBERS, AND MUST BE APPROVED IN WRITING BY
THE CONTRACTING OFFICER.
16. FOUNDATIONS:
A. FOUNDATIONS ARE DESIGNED TO BEAR ON SUITABLE EXISTING FILL, CONTROLLED STRUCTURAL
FILL, OR NATURAL CLAY SOILS AT AN ALLOWABLE PRESSURE OF 2,000 PSF.
B. COMPLY WITH ALL ASPECTS OF SOILS REPORT NO. 015-3164 DATED 12-10-2015 PREPARED BY
OLSSON ASSOCIATES 1802 EAST 123RD STREET, OLATHE, KS 66061.
C. SUBGRADE FILL MATERIALS SHALL BE IN ACCORDANCE WITH FILL PLACEMENT SCHEDULE BELOW.
D. THE GENERAL CONTRACTOR AND FOUNDATION CONTRACTOR SHALL UNDERSTAND THE SURVEY
AND GEOTECHNICAL REPORT BEFORE BIDDING THE WORK. RECOMMENDATIONS CONTAINED IN
THE GEOTECHNICAL REPORT SHALL BE INCLUDED IN THE CONTRACTOR'S WORK, UNLESS
SPECIFIED OR DETAILED OTHERWISE.
E. CONTRACTOR SHALL REMOVE EXISTING FOOTINGS AND FOUNDATIONS THAT ARE LOCATED
WITHIN THE FOOTPRINT OF THE NEW BUILDING.
F. CONTRACTOR SHALL NOTIFY CONTRACTING OFFICER OF ANY UNUSUAL SOIL CONDITIONS THAT ARE IN VARIANCE WITH THE GEOTECHNICAL REPORT OR WHEN DIFFERENT BEARING MATERIAL IS
EVIDENT AND THERE IS A QUESTION OF BEARING CAPACITY.
G. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL AND DISPOSAL OF UNSUITABLE FILL
MATERIAL OR ORGANIC MATERIAL.
17. SUBMITTALS:
A. CODE COMPLIANT STRUCTURAL DESIGN OF THE FOLLOWING ITEMS IS DEFERRED TO THE
GENERAL CONTRACTOR.
a. TEMPORARY BRACING AND SHORING
b. STEEL BAR JOISTS
c. METAL DECK ATTACHMENT
d. STRUCTURAL STEEL CONNECTIONS
e. ROOF ACCESS LADDERS & SAFETY CAGES
f. SEISMIC & WIND ANCHORAGE AND SWAY BRACING OF MECHANICAL, ELECTRICAL AND
PLUMBING SYSTEMS COMPONENTS.
B. DEFERRED SUBMITTALS SHALL INCLUDE SUBSTANTIATING STRUCTURAL CALCULATIONS AND
SHALL BEAR THE SIGNED WET STAMP OF A REGISTERED PROFESSIONAL ENGINEER WHO IS
LEGALLY AUTHORIZED TO PRACTICE IN THE JURISDICTION WHERE PROJECT IS LOCATED AND
WHO IS EXPERIENCED IN PROVIDING ENGINEERING SERVICES OF THE KIND INDICATED.
DEFERRED SUBMITTALS SHALL BEAR THE APPROVAL STAMP OF THE PROJECT ENGINEER OF
RECORD.
C. ALL SHOP DRAWINGS AND SUBMITTALS MUST BE REVIEWED AND APPROVED BY THE
CONTRACTOR PRIOR TO SUBMITTAL. CONTRACTING OFFICER'S REVIEW OF SHOP DRAWINGS IS
LIMITED TO CHECKING FOR GENERAL CONFORMANCE WITH DESIGN DRAWINGS AND STRENGTH
OF COMPONENTS AND MATERIALS. CONTRACTOR IS RESPONSIBLE FOR ANY CHANGES FROM THE
DESIGN DRAWINGS, QUANTITIES, DIMENSIONAL ERRORS OR OMISSIONS IN THE SHOP DRAWINGS.
D. ALL SHOP DRAWINGS MUST BE ORIGINAL DOCUMENTS AND SHALL NOT BE REPRODUCTIONS OF
THESE CONTRACT DOCUMENTS.
E. SUBMIT SHOP DRAWINGS DETAILING FABRICATION OF EACH MEMBER AND ITS CONNECTIONS.
DETAIL DRAWINGS ARE TO BE PREPARED UNDER THE SUPERVISION OF A LICENSED
PROFESSIONAL ENGINEER.
F. CONTRACTOR SHALL SUBMIT STRUCTURAL SHOP DRAWINGS FOR THE FOLLOWING:
a. CONCRETE MIX DESIGN AND MATERIALS
b. CONCRETE REINFORCING STEEL
c. STRUCTURAL STEEL
d. STEEL JOISTS
e. STEEL DECK & ATTACHMENT METHODS AND MATERIALS
f. LIGHT GAGE METAL FRAMING & CONNECTIONS
S0.1 GENERAL NOTES
S0.2 TYPICAL DETAILS
S0.3 TYPICAL DETAILS
S0.4 TYPICAL DETAILS
S0.5 TYPICAL DETAILS
S1.1 FOUNDATION PLAN
S2.1 ROOF FRAMING PLAN
S3.1 FOUNDATION SECTIONS
S3.2 FOUNDATION SECTIONS
S4.1 FRAMING SECTIONS
S4.2 FRAMING SECTIONS
S4.3 FRAMING SECTIONS
S4.4 FRAMING SECTIONS
S0.1
1 STRUCTURAL GENERAL NOTES
S0.1
3 STRUCTURAL SHEET INDEX
S0.1
2 FILL PLACEMENT SCHEDULE
STEELSTL
EXTERIOREXT
FINISHED
FOUNDATION
FOOTING
GRADE BEAM
HORIZONTAL
GALVANIZED
HORIZ
FIN
FND
GALV
FLR
FTG
G.B.
GA
FLOOR
GAUGE
UNLESS NOTED OTHERWISE
WELDED WIRE FABRICW.W.F.
T.O.
T&B
VAR
U.N.O.
TYP
VERT
w/
TOP OF....(ADD ITEM)
TOP & BOTTOM
VARIES
WITH
TYPICAL
VERTICAL
CENTER OF GRAVITY OF STRANDS
A.B. ANCHOR BOLT
CMU CONCRETE MASONRY UNIT
DRAWING
DIAMETER
DIMENSION
CONCRETE
EACH WAY
EXISTING
CONTINUOUS
EACH FACE
ELEVATION
EXPANSION
DWG
ELEV
EXIST
E.F.
EQ
E.W.
EXP
EQUAL
DEG
CONC
CONT
CTR
DIA
DTL
DIM
CENTER
DEGREE
DETAIL
BALANCE
BUILDING
BEARING
BETWEEN
CONTROL JOINT
CAST-IN-PLACE CONCRETE
CENTER LINE
ARCHITECTURAL PLANS
BTWN
C.G.S.
CL
C.J.
CIP
CLR
COL
CLEAR
COLUMN
BLDG
BM
BAL
ARCH
BRG
BOT
BEAM
AT
BOTTOM
ABOVE FINISH FLOOR
ALTERNATE
A.F.F.
ALT
JOINTJT
LONG LEG HORIZONTAL
LONG LEG VERTICAL
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
OPP OPPOSITE
SECT
SQ
STD
SPA
SIM
SPECS
SHT
PSF
REINF
SCHED
PSI
RAD
PC
PT
SPECIFICATION
STANDARD
SQUARE
SHEET
SECTION
SIMILAR
SPACING
REINFORCEMENT
POST TENSION
RADIUS
SCHEDULE
PRECAST
MISC
MK
N.T.S.
O.C.
OPNG
O.F.
MIN
MANUF
LLV
LBS
LLH
MAX
MAS
K
MISCELLANEOUS
NOT TO SCALE
ON CENTER
OUTSIDE FACE
MINIMUM
MARK
OPENING
MANUFACTURER
KIP (1000 LBS)
POUNDS
MASONRY
MAXIMUM
I.F.
JST
INSIDE FACE
JOIST
F.S. FAR SIDE
N.S. NEAR SIDE
FIELD VERIFYF.V.
REINF. BAR
SPLICE LENGTH
#6 AND
SMALLER
#7 AND
LARGER
57db
49db
44db
40db
72db
61db
55db
51db db = DIAMETER OF BAR (INCHES)
CONCRETE
STRENGTH
F'c, PSI
TYPICAL WELDED WIRE REINFORCEMENT SPLICE
NOTES:
1. BAR LAP SPLICE LENGTH SHALL BE AS NOTED IN
THE DOCUMENTS AND AS REQUIRED IN NOTE 4 BELOW.
2. TABULATED SPLICE LENGTH VALUES ARE BASED
ON:
A. UNCOATED BARS
B. Fy = 60ksi
C. BAR SPACING AND COVER AS NOTED:
BARS WITH CLEAR SPACING AND CLEAR
COVER NOT LESS THAN db AND STIRRUPS
OR TIES THROUGHOUT THE SPLICE LENGTH
NOT LESS THAN CODEMINIMUM
OR
BARS WITH CLEAR SPACING NOT LESS
THAN 2db AND CLEAR COVER NOT LESS THAN db.
4. REQUIRED LAP SPLICE LENGTH = TABULATED SPLICE
LENGTH MULTIPLIED BY ALL APPLICABLE
ADJUSTMENT FACTORS BELOW.
A. FOR CLASS A SPLICE = 0.769
B. FOR LIGHTWEIGHT CONCRETE = 1.3
C. FOR EPOXY COATED BARS = 1.2
1. COVER LESS TAHN 3db OR CLEAR SPACING LESS THAN 6db = 1.5
D. FOR Fy OTHER THAN 60ksi = Fy (ACTUAL)/60
E. FOR BARS NOT MEETING REQUIREMENTS OF BAR
SPACING AND COVER IN NOTE 3.C = 1.5
F. HORIZONTAL BARS WITH MORE THAN 12 INCHES
CONCRETE BELOW THE SPLICE = 1.3
5. REQUIRED LAP SPLICE LENGTH SHALL, UNDER NO
CIRCUMSTANCES, BE LESS THAN 12".
6. REQUIRED SPLICES OF PLAIN WIRE WELDED WIRE
REINFORCEMENT (W.W.F.) SHALL BE AS SHOWN
BELOW U.N.O. ON THE DOCUMENTS.
2" MIN
6" MIN
FOOTING SCHEDULE - 2000 PSF SOIL BEARING
M3.0 3'-0" x 3'-0" x 30" NONE - MASS CONCRETE
REINFORCINGSIZEMARK GROSS LOAD CAPACITY
(kips)
14.6
*CONTINUE GRADE BEAM REINFORCING THROUGH ALL PERIMETER MX.X FOOTINGS
COMPONENTS & CLADDING WIND PRESSURES (PSF)
115 MPH (3 SEC GUST), EXPOSURE C, LRFD
50-55'
ZONE
HEIGHT
0-15'
+17.3 -42.7
-71.6
-107.7
+42.7 -46.2
-57.1
15-20' 20-25' 25-30' 30-35' 35-40' 40-45' 45-50' 55-60'
+17.3
+17.3
+42.7
NOTES:
1. WIND ZONES ARE IN ACCORDANCE WITH ASCE 7-10, FIGURE 30.5-1 WITH A
ROOF ANGLE 0º - 7º (FLAT ROOF).
2. PRESSURES ARE BASED ON AN EFFECTIVE WIND AREA OF 10 SQUARE FEET.
3. PRESSURES SHOWN ARE NOMINAL WIND PRESSURES AT ULTIMATE LOAD
LEVEL (LRFD) AND SHALL BE USED IN ACCORDANCE WITH THE LOAD
COMBINATIONS SPECIFIED IN ASCE 7-10, CHAPTER 2.
4. DESIGNER MAY USE THE APPROPRIATE ADJUSTMENT FACTORS OR METHODS
OF ASCE 7-10 TO COMPUTE COMPONENT & CLADDING PRESSURES FOR
SPECIFIC COMPONENTS OF THIS STRUCTURE.
5. PRESSURES SHOWN ARE APPLIED NORMAL TO THE SURFACE, FOR EXPOSURE
& HEIGHT INDICATED ON THE TABLE. ADJUST TO OTHER CONDITIONS USING
EQUATION 30.5-1.
6. PLUS AND MINUS SIGNS SIGNIFY PRESSURES ACTING TOWARD AND AWAY
FROM THE SURFACES, RESPECTIVELY.
7. NOTATION:
a: 10 PERCENT OF LEAST HORIZONTAL DIMENSION OR 0.4h, WHICHEVER IS
SMALLER, BUT NOT LESS THAN 4% OF LEAST HORIZONTAL DIMENSION
OR 3 FT (0.9 m).
h: MEAN ROOF HEIGHT, IN FEET (METERS), EXCEPT THAT EAVE HEIGHT
SHALL BE USED FOR ROOF ANGLES <10°.
0: ANGLE OF PLANE OF ROOF FROM HORIZONTAL, IN DEGREES.
+18.4 -45.5
-76.4
-114.8
+45.5 -49.3
-60.9
+18.4
+18.4
+45.5
+19.3 -47.7
-79.9
-120.2
+47.7 -51.6
-63.7
+19.3
+19.3
+47.7
+20.0 -49.4
-82.9
-124.6
+49.4 -53.5
-66.1
+20.0
+20.0
+49.4
+20.7 -51.2
-85.8
-129.1
+51.2 -55.4
-68.4
+20.7
+20.7
+51.2
+21.3 -52.6
-88.2
-132.6
+52.6 -56.9
-70.3
+21.3
+21.3
+52.6
+21.9 -54.0
-90.6
-136.2
+54.0 -58.4
-72.2
+21.9
+21.9
+54.0
+22.3 -55.1
-92.4
-138.8
+55.1 -59.6
-73.6
+22.3
+22.3
+55.1
+22.7 -56.1
-94.1
-141.5
+56.1 -60.7
-75.0
+22.7
+22.7
+56.1
+23.2 -57.2
-95.9
-144.2
+57.2 -61.9
-76.5
+23.2
+23.2
+57.2 a a a a a a a a
FLAT ROOF
GABLE ROOF ( 7°)
INTERIOR ZONES INTERIOR ZONES INTERIOR ZONES
h h
T T/
T/
SAWCUT OR FORMED FILL w/
SEALANT & BACKING ROD
50% WWF (ALTERNATE
WIRES) DISCONTINUOUS
@ JOINT
T/
2T BUILDING OR
STRUCTURE
WWF
1/2" EXP JOINT MAT'L w/
REMOVABLE CAP STRIP.
SEAL TOP WITH GREY
CONST SEALANT
OLD
POUR
NEW
POUR
NOTE:
CONTRACTOR MAY SUBSTITUTE SMOOTH
DOWELS FOR KEY. CONTACT ENGINEER
FOR DETAILS.
CONTRACTION CONTRACTION ISOLATION
1"
T.O. SLAB
ELEV PER PLAN
8"
8"
T.O. SLAB
ELEV PER PLAN
EXISTING SLAB
#4 x 2'-0" DOWEL TO MATCH
SLAB REINF @ 48" O.C.. EMBED
6" INTO EXISTING SLAB w/
EPOXY ANCHORAGE SYSTEM
PER GENERAL NOTES
#4 BAR CONT
SLAB-ON-GRADE
PER PLAN
CL COL = CL BASE
PLATE (TYP)
3/4"Ø AR-1
ANCHOR RODS
HSS4x4 PER PLAN
3/16
PL3/4"x10"x0'-10"
BASE PLATE
BP-1
10"
1/
2"
1/ 2"
NOTE:
PLACE BASE PLATES
ON 1 1/2" NON-SHRINK
GROUT U.N.O.
1 1/2" 1 1/2"
5" T
H R
D
PR
O
JE
C
TI
O N
1' -0
" E M
BE
D
TY
P
U .N
.O
" T
YP
U
.N .O
2"
T
YP
3/4" DIA ANCHOR
ROD ASTM F1554,
GR 36
HEAVY HEX NUT &
PL1/4"x2"x2" SQ PLATE
WASHER (TYP U.N.O.)
HEAVY HEX
NUT TACK
WELD NUT (3)
PLACES TO
PREVENT
LOOSENING
AR-1
C :\P
- C
AT
M
R ep ai r 2
5_ dh ay w ar d.
rv t
15098 (P15179)
05.02.16
100% DESIGN SET
S0.2
TYPICAL
DETAILS
DO 5022 CATM
Range Repair
WHITEMAN AIR FORCE BASE
MISSOURI
S0.2
1 STRUCTURAL ABBREVIATIONS
S0.2
2 REINF BAR SPLICE LENGTH TABLE
S0.2
3 FOOTING SCHEDULE
N.T.S.S0.2
4 COMPONENTS & CLADDING WIND PRESSURES TABLE
N.T.S.S0.2
7 SLAB JOINT DETAILS
N.T.S.S0.2
5 SLAB JOINT DETAILS
N.T.S.S0.2
6 BASE PLATE DETAILS
BEAM-TO-COL
MINIMUM CONNECTION SCHEDULE
MINIMUM
LENGTH, "L" (IN)
W36 6
MINIMUM "N" QUANTITY
3/4" BOLTS IN WEB
W8
W12
W14
BEAM SIZE
W10
W24
W21
W18
W16
W33
W30
W27 5
BEAM-TO-COL
REFERENCE NOTES:
A BEAM SIZE PER SCHEDULE (TYP).
B PERPENDICULAR BEAM AS OCCURS
(NOT SHOWN).
C 3/16" CAP PLATE @ T.O. COL, SEAL
WELD ALL AROUND.
D "N" QUANTITY OF 3/4" BOLTS @
3" O.C. IN HORIZ SSL HOLES.
E 3/4" Ø BOLTS IN STD HOLES.
F 5/16" MIN THICKNESS DBL CLIP
ANGLES OR BENT PLATE.
G WIDE FLANGE COLUMN.
SCHEDULE NOTES:
1. ALL BOLTS SHALL BE 3/4" Ø ASTM A325.
2. ALL BOLTS SHALL HAV EHEAVY HEX NUTS.
3. NUTS SHALL BE TIGHTENED TO SNUG TIGHT
CONDITION.
4. CLIP ANGLES MAY BE SHOP WELDED TO BEAM
WEB PER AISC.
5. FOR BEAMS WITH AXIAL LOADS PER PLAN, BOLTS
AND CONNECTIONS SHALL BE SLIP-CRITICAL PER
AISC GUIDELINES.
NOTE:
CONNECTIONS SHOWN IN THIS DETAIL ARE
CONSIDERED MINIMUM REQUIREMENTS.
FABRICATOR SHALL BE RESPONSIBLE FOR DESIGN AND
DETAIL OF EACH CONNECTION FOR LOADS SHOWN ON
PLANS IN ACCORDANCE WITH THE SPECIFICATION AND
THE GENERAL STRUCTURAL NOTES.
SUGGESTED CONNECTION DETAILS ARE SHOWN.
FABRICATOR MAY OPT TO USE OTHER AISC APPROVED
CONNECTIONS IN LIEU OF THESE SHOWN HEREIN.
HSS COL
PL3/8" SHEAR TAB
5/16
5/16
B
C
3" MIN
D
A
L
B USE FACE
MOUNTED
SHEAR TAB
3" MAX
HSS COL
D
A
C
PL3/8" THROUGH
PLATE
L
5/16
5/16
TYP
1" M
IN
"X"
LO
AD
B
O
TT
O M
NOTES:
PROVIDE (2) L2x2x3/16 (MIN) CHORD BRACE AT BOTTOM CHORD CONCENTRATED
LOAD LOCATIONS FOR SUSPENDED EQUIPMENT SUPPORTS, AND OTHER
SUPERIMPOSED OR SUSPENDED LOADS WHERE THE DIMENSION "X" IS GREATER
THAN THE LESSER OF 4 INCHES OR THE JOIST CHORD WIDTH AS SHOWN.
BOTTOM CHORD
PANEL POINT
NEW BRACES
3/16
TYP
TOP CHORD
WIDTH
BOT CHORD
WIDTH
TOP CHORD
PANEL POINT
WELDED OPTION #1
WELDED OPTION #2
(T1/2)
T1B-P1c
EDGE ANGLE PER
OTHER DETAILS
PL1/4" x 2" x 12"
LONG
3/16
3/16
TYP EA END
6"
T1
EDGE ANGLE PER
OTHER DETAILS
OPTION 4OPTION 2
OPTION 3OPTION 1 OPTION 5
COPE
HORIZ LEG
ANGLE
CROSS PIECE
3/16
3/16
3/16
ANGLE CROSS
PIECE
COPE VERT
LEG1/2"
3/16
ANGLE CROSS
PIECE
1/4" THICK ANGLE
@ EA END1/2"
3/16
HSS CROSS
PIECE
3/16
COPE TUBE
END
1/2"
3/16
HSS CROSS
PIECE
1/4" THICK ANGLE
@ EA END
3/16
1/2"
1 1/2" MAX
BEAM PER PLAN
CONT BENT PLATE OR
ANGLE AS OCCURS PER
DETAILS
JOIST PER
PLAN
CONT EDGE MEMBER PER
DETAILS (ANGLE, BENT PL,
ETC) SPLICE @ ENDS PER
OTHER DETAILS
3/16 JST
WIDTH
TYP EA JOIST
PER
DETAILS
NOTE:
TO ENSURE ACCURATE PLACEMENT,
ALL EDGE ANGLE WELDS MAY BE
FIELD WELDS AT CONTRACTOR'S
OPTION.
3/16 3-24
TYP
HSS3X
3X
3/1
6 HSS3X3X3/16
W10X12
HSS4x4x1/4 COLUMN
EXTENSION (TYP)
EXISTING HSS4x4
COLUMN (TYP)
PL3/8" GUSSET
PLATE (TYP)
3/16
3/16
3/16 4" MIN
3/16 4" MIN
PER PLAN
NOTE:
BRACE WELD LENGTHS SHOWN
ARE MINIMUM REQ'D. GUSSET
PLATES SHALL BE WELDED
ALONG FULL CONTACT LENGTH.
3/16 4" MIN
3/16 4" MIN
TYP
3/16 4" MIN
3/16 4" MIN
T.O. EXIST COL
ELEV = 107'-0"
(F.V.)
T.O. BEAM ELEV
PER PLAN
S4.2
B.O. STEEL
PER DETAILS
1/4
1/4
1/4
1/4 1/4
3" MIN
BRG
T.O. STEEL
PER DETAILS
L4x4x5/16 x COL WIDTH+1"
OR BENT PLATE AS REQ'D
CENTERED ON COL
L6x4x3/8 x COL WIDTH+ 1"
CENTERED ON COL
BUILD FLUSH
w/ COL
SIDE WALL
ANGLE
TO
HSS COL
STEEL TUBE PER PLAN
1/4" STIFFENERS 6"
APART CENTERED
ON
COLUMN
COL PER PLAN
T.O. STL =
B.O. DECK
1ST TOP CHORD
PANEL POINT
3/16
3/16WELD FOR
6 KIPS
JOIST BEYOND
PER PLAN
KICKER ANGLE SIZE & LOCATION
PER DETAILS (L2x2x1/4 MINIMUM)
EXTEND TO FIRST TOP CHORD
PANEL POINT OF ROOF JOISTBEAM PER
PLAN
3/16
3/16 WELD FOR 6
KIPS
1ST TOP CHORD
PANEL POINT
CROSS PIECE PER PLAN OR
DETAILS. WELD TO JOIST EA
SIDE AT 1ST TOP CHORD PANEL
POINT (END CONNECTIONS PER
OPTIONS 1-4)
3/16
3/16WELD FOR
6 KIPS
JOIST BEYOND
PER PLAN
KICKER ANGLE SIZE &
LOCATION PER DETAILS
(L2x2x1/4 MINIMUM)
3/16
3/16 WELD FOR 6
KIPS
BEAM PER
PLAN
KICKER ANGLE SIZE &
LOCATION PER DETAILS
(L2x2x1/4 MINIMUM)
STRUT ANGLE
MATCH KICKER
SIZE & SPACING
3/16
3/16WELD FOR
6 KIPS
ROOF DECK
PER PLAN
BEAM PER
PLAN 3/16
3/16 WELD FOR 6
KIPS
C :\P
- C
AT
M
R ep ai r 2
5_ dh ay w ar d.
rv t
15098 (P15179)
05.02.16
100% DESIGN SET
S0.3
TYPICAL
DETAILS
DO 5022 CATM
Range Repair
WHITEMAN AIR FORCE BASE
MISSOURI
N.T.S.S0.3
1 BEAM CONNECTION DETAILS
N.T.S.S0.3
2 JOIST REINFORCING DETAIL
N.T.S.S0.3
3 EDGE ANGLE SPLICE DETAILS
N.T.S.S0.3
4 ANGLE ATTACHMENT DETAILS
N.T.S.S0.3
5 ROOF EDGE ANGLE ATTACHMENT
S0.3
6 NOT USED
N.T.S.S0.3
7 BRACE ELEVATION
N.T.S.S0.3
8 CONNECTION DETAIL
N.T.S.S0.3
9 BEAM BOTTOM FLANGE KICKER DETAILS
OPTION 1
1/4" DIA HILTI KWIK BOLT III
w/ 2" EMBEDMENT @ 16"
O.C. (CONCRETE
SUPPORT)
OPTION 2
1/4" DIA x 1 1/2" TAPCON
ANCHORS @ 16" O.C.
(CONCRETE SUPPORT)
OPTION 3
HILTI X-U FASTENERS @
16" O.C. (CONC OR STEEL
SUPPORT)
OPTION 4
#12 SELF-DRILLING
SCREW @ 16" O.C.
(STEEL SUPPORT)
SELF-DRILLING SCREWS #10 (MIN)
BOTH SIDES, TYP EA STUD
METAL STUD PER
OTHER DETAILS
(TYP)
CONT TRACK
SELF-DRILLING SCREWS #10 (MIN)
BOTH SIDES, TYP EA STUD
1/8 1"
1/8 1"
@ 1/4 PTS
METAL STUD PER
OTHER DETAILS
(TYP)
CONT TRACK
BRIDGING CLIP MANUFACTURED BY THE
STEEL NETWORK ATTACH TO CRC16 w/ (2) #
10x16 SCREW & TO STUD W/ (2) #10 SCREWS
@ EA STUD AS SHOWN
COLD ROLLED
CHANNEL (CRC)
REFER TO WALL
SECTION FOR STUD &
TRACK SPECIFICATION
" M
AX
V
ER
TI
C
AL
S
PA
C
IN
G
D
IS
TA
N
C E
" M
IN
E
D G
E
NOTE
FOR STUDS SMALLER
THAN 6" USE BRIDGE CLIP.
FOR 6" STUDS USE BC600.
FOR 8" STUDS AND
LARGER USE BC800.
MTL STUD, EA SIDE SIZE
& GAGE PER DETAILS
TRACK T&B SIZE & GAGE
PER DETAILS
#10-16 SCREWS
@ 6" O.C. (TYP)
1/8 2-12
TYP
WALL STUD
DEPTH
WALL STUD
DEPTH
TRACK OR
SLIP TRACK
TRACK
METAL STUD
CRIPPLES @
16" O.C. (TYP)
COPE FLANGES &
EXTEND WEBS OF
BOX BEAM SIDE
STUDS OVER JAMB
STUDS. ANCHOR
TO JAMB STUDS w/
(4) #12-14 SCREWS
IN PRE-DRILLED
HOLES OR USE
EQUIV WELDS
(3) FULL HT STUDS
OPENINGS TO 8'-0"
(2) FULL HT STUDS
OPENINGS LESS
THAN 5'-0" (SEE
STUD COL DETAIL)
TRACK
FULL HEIGHT
STUDS @
JAMBS
METAL STUD
TRIMMER (TYP)
TRACK SILL
AS OCCURS
METAL STUD BOX BEAM
HEADER PER OTHER DETAILS
NOTE:
STUD AND TRACK GAGE AND SIZE PER
OTHER DETAILS THESE DOCUMENTS.
OPENING PER ARCH
MAX WIDTH = 8'-0"
EQ EQ EQ EQ EQ
BLOCKING NOTES:
1. PLACE SOLID BLOCKING ADJACENT TO ALL OPENINGS
AND (2) BAYS AT ENDS OF JOIST SYSTEM.
2. BLOCKING SPACING SHALL NOT EXCEED 10'-0" O.C.
#12-14 SCREWS (TYP)
CONT FS200-43 (50KSI)
STRAPPING T&B OF
BLOCKING
JOIST PER PLAN (TYP)
ATTACH BLOCKING TO
JOIST ON EA SIDE (4) #12-14
SCREWS PER END MIN
CONT SOLID BLOCKING
PER PLAN
BLOCKING NOTES:
1. PLACE SOLID BLOCKING ADJACENT TO ALL OPENINGS
AND (2) BAYS AT ENDS OF JOIST SYSTEM.
2. BLOCKING SPACING SHALL NOT EXCEED 10'-0" O.C.
#12-14 SCREWS (TYP)
CONT BRIDGE BAR
CONT FS200-43 (50KSI)
STRAPPING T&B OF BLOCKING
JOIST PER PLAN (TYP)
NOTE:
SECOND ROW OF STUDS AT
DEMISING WALL NOT SHOWN
ATTACH VERTICLIP SLD 33MIL AS
MANUFACTURED BY THE STEEL
NETWORK, INC. (888-474-4876) TO STUD
MEMBERS w/ (2) #8 SELF-DRILLING
SCREWS PROVIDED THROUGH PRE-
INTALLED SHOULDER WASHERS
TYP STUDS @ INTERIOR
DEMISING WALL.
400S200-68 @ 16" O.C.
INSTALL STUD 3/4"
SHORT @ HEAD INTO
TRACK FOR VERT
DEFLECTION
ROOF DECK
ATTACH 400T200-33MIL w/ (2)
#8 P.A.F. TO STRUCTURE
3/4" MIN EDGE DISTANCE (2) 600S200-97 BUILT-UP
STUDS BACK TO BACK
SLAB-ON-GRADE
PER PLAN
CONT TRACK
L2 1/2x2 1/2x1/4 x 3" LG EA
SIDE OF BUILT-UP STUDS
3/16
3/16WELD TOP
& SIDES
5/8" HILTI KWIK BOLT 3
EXPANSION ANCHOR
EMBED 3 1/2"
T.O. SLAB ELEV
PER PLAN
LB362/400
LB600
LB800
LB1000
LB1200
METAL STUD 20
GA OR THICKER
(4) #12-14 SCREWS
(3) HILTI X-U FASTENERS
STEEL ANGLE, TUBE,
CHANNEL, ETC
STIFFCLIP LB BY THE
STEEL NETWORK CLIP
LENGTH = STUD DEPTH
NOTE:
WELDED CONNECTIONS MAY BE USED
FOR 12, 14, 16 & 18 GA MATERIAL ONLY.
(4) #12-14 SCREWS
STIFFCLIP LB BY THE
STEEL NETWORK CLIP
LENGTH = STUD DEPTH
STEEL ANGLE,
TUBE, CHANNEL,
ETC
2"
1/2"
2 3/4"
2" 2"
2" 2"
2"
2 3/4"
1 1/2" 3 3/4" 2 3/4"
1" 3 1/2" 1 1/2"
1/8
1/8 CLIP "A" TO
ANGLE
C :\P
- C
AT
M
R ep ai r 2
5_ dh ay w ar d.
rv t
15098 (P15179)
05.02.16
100% DESIGN SET
S0.4
TYPICAL
DETAILS
DO 5022 CATM
Range Repair
WHITEMAN AIR FORCE BASE
MISSOURI
N.T.S.S0.4
1 BOTTOM TRACK CONNECTION
N.T.S.S0.4
2 DOUBLE STUD COLUMN
N.T.S.S0.4
3 STUD BRACING DETAIL
N.T.S.S0.4
4 BOX BEAM HEADER
N.T.S.S0.4
5 STUD FRAMED OPENING DETAIL
N.T.S.S0.4
7 TYPICAL JOIST BRIDGING DETAIL
N.T.S.S0.4
8 TYPICAL JOIST BRIDGING DETAIL
N.T.S.S0.4
9 INTERIOR SLIP TRACK DETAIL
N.T.S.S0.4
10 ANCHORAGE OF BUILT-UP STUDS
N.T.S.S0.4
6 CLIP "A" CONNECTION DETAIL
T.O. WALL
12' - 8"
A B C D E F G H I J K
JOIST NOTE:
1. EXISTING CROSS BRACING SHALL BE REMOVED TO ALLOW FOR
INSTALLATION OF NEW JOISTS. JOIST SUPPLIER SHALL DESIGN &
PROVIDE NEW BOLTED CROSS BRACING TO SPAN BETWEEN NEW &
EXISTING JOISTS. JOIST SUPPLIER SHALL FIELD VERIFY THE
LOCATIONS OF THE EXISTING CROSS BRACING PRIOR TO FABRICATION.
2. BRACING @ NORTH & SOUTH SHALL BE DESIGNED FOR WIND LOADING
PER SECTIONS 5/S4.1 & 1/S4.2 IN ADDITION TO GENERAL STABILITY.
WLL
WDL
JOIST SCHEDULE
JOIST
DESIGNATION
64DLHSP1
64DLHSP2
DEPTH @
END
64"
64"
DEPTH @
CENTER
95"
95"
WLL
(PLF)
WDL
(PLF)
WDLU
WDLU
(PLF)
(F.V.)
TRUSS BEARING
12' - 8 7/8"
PER PLAN (F.V.) PER PLAN (F.V.) PER PLAN (F.V.) PER PLAN (F.V.) PER PLAN (F.V.) PER PLAN (F.V.) PER PLAN (F.V.) PER PLAN (F.V.) PER PLAN (F.V.) PER PLAN (F.V.)
112'-8" (F.V.)
112'-8 7/8"
BRACING PER
JOIST SUPPLIER
(F.V.) (F.V.) (F.V.) (F.V.) (F.V.) (F.V.) (F.V.) (F.V.) (F.V.) (F.V.)
EN
D
D
EP
TH
C
EN
TE
R
D
EP
TH
JOIST NOTE:
1. JOIST BOTTOM CHORDS SHALL SUPPORT FIRING LINE BAFFLES @ 4'-0" O.C.
JOIST SCHEDULE
JOIST
DESIGNATION
12K1
WLL
(PLF)
WDL
(PLF)
PDL
(LBS)
PER PLAN (F.V.) PER PLAN (F.V.)
PDL
WDL
W LL
TRUSS BEARING ELEV
VARIES PER PLAN
WDL
W LL
PDL PDL PDLPDL PDL
4' - 0"4' - 0"4' - 0"4' - 0"4' - 0"
UNISTRUT PER
DETAILS (TYP)
C :\P
- C
AT
M
R ep ai r 2
5_ dh ay w ar d.
rv t
15098 (P15179)
05.02.16
100% DESIGN SET
S0.5
TYPICAL
DETAILS
DO 5022 CATM
Range Repair
WHITEMAN AIR FORCE BASE
MISSOURI
C :\P
- C
AT
M
R ep ai r 2
5_ dh ay w ar d.
rv t
15098 (P15179)
05.02.16
100% DESIGN SET
S0.5
TYPICAL
DETAILS
DO 5022 CATM
Range Repair
WHITEMAN AIR FORCE BASE
MISSOURI
S0.5
3 NOT USED
S0.5
5 NOT USED
S0.5
6 NOT USED
S0.5
7 NOT USED
N.T.S.S0.5
1 64DLHSP JOIST GIRDER LOADING DIAGRAM
N.T.S.S0.5
2 12K1SP JOIST LOADING DIAGRAM
S0.5
4 NOT USED
UP
FX.X
BP-X
BASE PLATE PER
TYPICAL DETAILS
ON S0.2
FOOTING SIZE PER
SCHEDULE ON S0.2
COLUMN
FOOTING PER
SCHEDULE 3/S0.2NOTE:
SEE TYPICAL DETAILS FOR
BASE PLATE & ANCHOR ROD
INFORMATION
FOOTING LEGEND
A B C D E F G H I J K
12' - 0" (F.V.) 12' - 0" (F.V.) 12' - 0" (F.V.) 12' - 0" (F.V.) 12' - 0" (F.V.) 12' - 0" (F.V.) 12' - 0" (F.V.) 12' - 0" (F.V.) 12' - 0" (F.V.) 12' - 0" (F.V.)
F.
V.
F.
V.
F.
V.
F.
V.
F.
V.
F.
V.
F.
V.
F.
V.
F.
V.
0" (F
.V
4'
3/
4" 4'
0"
4" CONCRETE SLAB-ON-GRADE w/ (1) LAYER 6x6-W1.4xW1.4 W.W.F. CENTERED IN SLAB OVER
10 MIL VAPOR BARRIER, OVER 4" GRANULAR
LEVELING COURSE (SEE GEOTECHNICAL
REPORT REFERENCED IN THE GENERAL NOTES)
T.O. SLAB ELEVATION = 100'-0"
(CIVIL REFERENCE ELEV = 845.33')
S3.1
S3.1
S3.1
SL
SL
S3.2
S3.1
S3.1
S3.1
S3.1
D
S3.1
EE
F
G
CONTRACTION
JOINT PER TYPICAL
DETAILS (TYP)
S1.1
REMOVE & REPLACE
EXIST SLAB AS REQ'D
FOR PLACEMENT OF
NEW GRADE BEAM
S3.2
L TYP
TYP I
K
J
H
H
H
H
H
H
H
H
H
HH
H
H
H
H
H
H
H
H
H
H
H
M3.0
BP-1
M3.0BP-1
B
/4
F.
V.
4' - 5 5/8" (F.V.)5 1/8" (F.V.)
(F.V.)
3' - 1 1/8"
(F .V
3'
-2
EXISTING TARGET
SHED
I
I
I SL
SL
C
S3.1
S0.2
O TYP
F G
S3.2
S3.1
12' - 0"
4' -4
3/ 4"
4' -0
HSS8X3X5/16 (LOW)
HSS6X3X3/16 (HIGH)
S3.2
600S162-54 @ 16" O.C.
S3.2
NM
F
STRINGER
H
EA
D
ER
STRINGER
T.O. FLR ELEV = 10 2' - 0"
COL
COL
COL PER
S2.1
C :\P
-C
AT
M
R ep ai r2
5_ dh ay w ar d.
rv t
15098 (P15179)
05.02.16
100% DESIGN SET
S1.1
FOUNDATION
PLAN
DO 5022 CATM
Range Repair
WHITEMAN AIR FORCE BASE
MISSOURI
PLAN NOTES:
1. CONDITIONS AND DIMENSIONS SHOWN ON THIS PLAN HAVE BEEN TAKEN FROM
EXISTING DRAWINGS, FIELD MEASUREMENTS AND FIELD OBSERVATIONS.
DETAILS HAVE BEEN DEVELOPED BASED ON THE BEST AVAILABLE
INFORMATION. CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND
DIMENSIONS SHOWN, AND, IF THE AS-BUILT CONDITION IS DIFFERENT THAN
THAT REPRESENTED IN THESE DOCUMENTS, SHALL NOTIFY THE CONTRACTING
OFFICER PRIOR TO PROCEEDING WITH THE WORK.
2. THE CONCRETE SLAB-ON-GRADE HAS BEEN DESIGNED FOR ITS FINAL USE AND
NOT FOR CONSTRUCTION CONSIDERATIONS. CONTRACTOR SHALL
COORDINATE SLAB DESIGN WITH CONSTRUCTION NEEDS. THE SLAB DESIGN
INDICATED ON THESE DRAWINGS IS TO BE CONSIDERED A MINIMUM. SUBMIT
CHANGES TO THE SLAB DESIGN TO THE CONTRACTING OFFICER FOR REVIEW.
3. ALL NEW EXTERIOR WALL STUDS SHALL BE 600S162-43 WALL STUDS @ 16" O.C. U.N.O.
4. CONTRACTOR SHALL SHORE THE EXISTING TARGET SHED UNTIL CONSTRUCTION
OF NEW SUPPORTS IS COMPLETE.
5. SEE SHEET S0.2 FOR OTHER TYPICAL FOUNDATION DETAILS.
PLAN REFERENCE NOTES:
A PROVIDE (2) #4 x 5'-0" LONG DIAGONAL BARS AT MID DEPTH OF SLAB.
B PROVIDE DOWELS INTO EXTERIOR SIDEWALK/PAVING TO PREVENT FROST
HEAVE. SEE 2/S3.1 FOR INFORMATION.
C SLAB BLOCKOUT PER 3/S3.2.
D EXISTING TRENCH DRAIN TO BE COVERED & REMAIN PATCH VISIBLE CRACKS
& SPALLS PER 6/S3.1.
E MECHANICAL SLAB PER S2.1.
F FRAMING LAYOUT SHOWN FOR REFERENCE ONLY. STAIR FRAMING AND
CONNECTION DETAILING SHALL BE DETERMINED BY THE STEEL FABRICATOR.
STAIR, HANDRAIL, INTERMEDIATE LANDING AND GUARDRAIL DESIGN SHALL BE
THE RESPONSIBILITY OF THE STEEL FABRICATOR. (INCLUDING ATTACHMENT
TO THE BUILDING AND ALL REQUIRED FOUNDATIONS.) IF ADDITIONAL COLUMNS
OR POSTS ARE REQUIRED SUPPLIER TO CHECK SLAB OR COORDINATE
ADDITIONAL FOOTINGS WITH GENERAL CONTRACTOR. COORDINATE
GEOMETRY OF STAIRS w/ ARCHITECTURAL DRAWINGS. PROVIDE DRAWINGS
AND CALCULATIONS FOR THE STAIRS GUARDRAIL / HANDRAILS SEALED BY AN
ENGINEER REGISTERED IN THE JURISDICTION WHERE THE PROJECT IS
LOCATED. DESIGN CRITERIA FOR THE STAIRS, LANDINGS AND HANDRAIL /
GUARDRAILS SHALL BE AS SET FORTH IN THE SPECIFICATIONS. MINIMUM
MEMBER SIZES ARE AS FOLLOWS:
STRINGER: 3/8" PLATE
HEADER: C8x11.5
INT. STAIR PAN: 14 GA (MIN 2" CONC ABOVE DECK FLUTES)
COLUMNS: HSS3x3x1/4
G FLOOR SHEATHING SHALL BE 3/4" MINIMAL THICKNESS WITH APA 32/16 SPAN
RATED, EXPOSURE 1, STRUCTURAL SHEATHING. RUN PANELS PERPENDICULAR
TO THE SUPPORTS, STAGGER PANEL ENDS 1/2 PANEL LENGTH ATTACH WITH #10
OR #12 PANHEAD OR WAFERHEAD SELF DRILLING SCREWS 6" O.C. ALONG
BUILDING PERIMETER & CONTINUOUS PANEL EDGES, @ 6" O.C. @ OTHER PANEL
EDGES, & 12" O.C. OVER INTERMEDIATE SUPPORTS. SPACE NAILS @ 6" O.C.
OVER INTERMEDIATE SUPPORTS WITHIN 6'-0" OF THE BUILDING CORNERS.
H EXISTING HSS4x4 COLUMNS TO REMAIN.
I EXISITNG WALL TO REMAIN.
J EXISTING BULLET TRAP TO REMAIN.
K EXISTING RANGE FLOOR SLAB TO REMAIN. PATCH SPALLS & OTHER DAMAGED
SECTIONS OF FLOOR SLAB PER STRUCTURAL GENERAL NOTE 11.N ON 1/S0.1.
L EXTERIOR SLABS PER CIVIL.
M PROVIDE JOIST BRIDGING PER 7 OR 8/S0.4.
N (2) 600S162-43 w/ (2) 362T125-43 BOX BEAM HEADER PER TYPICAL DETAILS.
O LOADING TABLE PER ARCH.
1/8" = 1'-0"S1.1
1 FOUNDATION PLAN
LEGENDS:
SL = SLAB EDGE.
1/4" = 1'-0"S1.1
2 ENLARGED PLAN
NORTH NORTH
W14x30
COLUMN LEGEND
COLUMN SIZE
W8x10
BEAM SIZE
BEAM LEGEND
12K1
JOIST LEGEND
JOIST SIZE
SP JOISTS
PER S0.5
A B C D E F G H I J K
S4.1
S4.2
12' - 0" (F.V.) 12' - 0" (F.V.) 12' - 0" (F.V.) 12' - 0" (F.V.) 12' - 0" (F.V.) 12' - 0" (F.V.) 12' - 0" (F.V.) 12' - 0" (F.V.) 12' - 0" (F.V.) 12' - 0" (F.V.)
0" (F
.V
0" (F
.V
0" (F
.V
0" (F
.V
0" (F
.V
0" (F
.V
0" (F
.V
0" (F
.V
4" (F
.V
F.
V.
4'
-4 3/
4" 4'
-0
HSS4X4X1/4
HSS4X4X1/4 HSS4X4X1/4
HSS4X4X1/4HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
EXISTING GIRDER
EXISTING GIRDER
EXISTING GIRDER
EXISTING GIRDER
EXISTING GIRDER
EXISTING GIRDER
EXISTING GIRDER
EXISTING GIRDER
EXISTING GIRDER
S3.1
A A
S4.1
64DLHSP1
64DLHSP1
64DLHSP1
64DLHSP1
64DLHSP2
64DLHSP2
64DLHSP2
64DLHSP1
1' -0
5'
-0
5' -0
5'
-0
5' -0
5'
-0
5' -0
5'
-0
5' -0
5'
-0
5' -0
8'
-9
1' -3
0"
1' -3
3' -9
5'
-0
S3.1
S3.1
S3.1
EQ
SP
A
K1
SP
G
K1
SP
G
K1
SP
G
K1
SP
G
K1
SP
G
K1
SP
G
K1
SP
G
K1
SP
G
K1
SP
G
K1
SP
G
W
X3
W
X3
W
X3
W
X3
W
X3
W
X3
W
X3
W
X3
W
X3
W
X3
W
X3
W10X12 W10X12 W10X12
W8X10W8X10
W10X12 W10X12 W10X12 W10X12 W10X12 W10X12
W8X10W8X10W8X10W8X10
W8X10
W8X10W8X10W8X10
HSS4X4X1/4
HSS4X4X1/4
BB
W10X12
S4.3
S0.3
ELEV
S0.3
ELEV5
S4.2
S4.2
S4.3
S4.3
S4.3
S4.36
S4.3
T.O. DECK ELEV = 1 14' - 2 5/8"
T.O. DECK ELEV = 1 12' - 10 3/4"
W10X12
HSS6X3X3/16 (LOW)
S4.1
S4.2
E
F C C
TYP D
H
S4.4
"O .C
M
AX
0S
0-
T.O. DECK ELEV = 10 8' - 8 7/8"
T.O. DECK ELEV = 10 9' - 8 7/8"
3/
4" (F
.V
4' - 5 5/8" (F.V.)5 1/8" (F.V.)
(F.V.)
3' - 1 1/8"
(F .V
3' -4
PE
R
AR
C
H /M
EP
PE
R
AR
C H
/M
EP
J
I
I
I
I
I
I
I
I
J
S4.2
HSS3X3X1/4 (LOW) HSS3X3X1/4 (LOW) HSS3X3X1/4 (LOW) HSS3X3X1/4 (LOW)HSS3X3X1/4 (LOW)HSS3X3X1/4 (LOW) HSS3X3X1/4 (LOW)
K
K HIGH & LOW
D D
D
H
IG
H R
O O
F D
EC
K
PE
R
PL
AN
N O
TE
S
LO
W
R O
O F
D
EC
K
PE
R
PL
AN
N
O
TE
S
HSS3x3x1/4 (LOW)
7' - 3 1/4"
C :\P
-C
AT
M
R ep ai r2
5_ dh ay w ar d.
rv t
15098 (P15179)
05.02.16
100% DESIGN SET
S2.1
ROOF FRAMING
PLAN
DO 5022 CATM
Range Repair
WHITEMAN AIR FORCE BASE
MISSOURI
PLAN NOTES:
1. CONDITIONS AND DIMENSIONS SHOWN ON THIS PLAN HAVE BEEN TAKEN FROM
EXISTING DRAWINGS, FIELD MEASUREMENTS AND FIELD OBSERVATIONS.
DETAILS HAVE BEEN DEVELOPED BASED ON THE BEST AVAILABLE
INFORMATION. CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND
DIMENSIONS SHOWN, AND, IF THE AS-BUILT CONDITION IS DIFFERENT THAN
THAT REPRESENTED IN THESE DOCUMENTS, SHALL NOTIFY THE ARCHITECT
AND ENGINEER PRIOR TO PROCEEDING WITH THE WORK.
2. ALL SIMPLE BEAM CONNECTIONS SHALL BE PER TYPICAL DETAILS U.N.O.
DESIGN FOR LOADS INDICATED WHERE SHOWN. DESIGN FOR 10 KIP REACTION
IF NO LOAD SHOWN. DESIGN FOR 10 KIP REACTION OF NO LOAD SHOWN.
3. ALL PERIMETER ROOF EDGE ANGLES SHALL BE CONTINUOUS AND SPLICED IN
ACCORDANCE WITH TYPICAL DETAILS.
4. LOW ROOF DECK IS 1 1/2" 22GA WIDE RIB PAINTED ROOF DECK NORTH
OF GRID 5. WELD TO SUPPORTING STEEL TO TRANSFER 250 PLF DIAPHRAGM
SHEAR AND FOR UPLIFT PER THE GENERAL NOTES.
5. HIGH ROOF DECK IS VULCRAFT 3" 22GA DEEP RIB PAINTED ROOF DECK SOUTH OF
GRID 5. WELD TO SUPPORTING STEEL TO TRANSFER 250 PLF DIAPHRAGM SHEAR
AND FOR UPLIFT PER THE GENERAL NOTES.
6. ALL NEW EXTERIOR WALL STUDS SHALL BE 600S162-43 STUDS @ 16" O.C. UNLESS
NOTED OTHERWISE.
7. REINFORCE EXISTING JOIST GIRDERS PER 1/S0.5.
8. CONTRACTOR IS SOLELY RESPONSIBLE FOR STRUCTURAL STABILITY OF THE
EXISTING BUILDING DURING DEMOLITION…
This is the start of the file's text. The full file is on GovTribe.