FAIRCHILD AIR FORCE BASE DESIGN STANDARDS 30 April 2018

DIVISION 08 – OPENINGS DATA SHEET

SECTION 087100– DOOR HARDWARE PAGE 1 OF 1

DIVISION 08 – OPENINGS

SECTION 087100 – DOOR HARDWARE

DATA SHEET

SECTION 087100 – DOOR HARDWARE

A. IN-HOUSE AND CORPS OF ENGINEER PROJECTS

1. Locksets, Latchsets, and Deadbolts

a. The designer shall write the specifications to include the following:

i. “Locksets, latchsets and deadlocks shall be heavy-duty weight. To the maximum extent possible, all locksets, latchsets and deadlocks shall be from the same manufacturer, and of matching style, finish, color, etc. All key operated locks shall be compatible with the Best Lock Corporation "BEST" interchangeable cores.”

ii. The keying schedule shall be developed by the designer and be included in either the project specifications or project drawings.

2. Lock cores shall be specified as follows:

a. For Base Contracted Projects:

i. The contractor shall provide seven pin "BEST" "TB" keyway cores (no substitutes) keyed to the Base Best Grandmaster Key controlled system. Final "pinned" cores and keys shall be purchased from "BEST" by the contractor and shipped to the base locksmith so that they are received prior to Substantial Completion. The base will install the final cores and return the construction cores to the manufacturer.

b. For Corps of Engineers (CoE) Contracted Projects:

i. Construction cores shall be provided by the contractor and in-place prior to Substantial Completion. The CoE shall MIPR funds to the base a minimum of 90 days prior to Substantial Completion so that the base can purchase “BEST” cores. The keying schedule shall still be prepared by the designer and included in the either the specifications or drawings, however, it will be annotated with a note that says “Final cores to be provided by the Government”.

3. Door hardware. For guidance see Specification Guidelines, Attachment 1.

END OF DATA SHEET

DIVISION 0 –

SECTION 0 00 –

SECTION 0 00 –

Contact: Gerald Aguiar Title:

Phone: 509.247.

Email: gerald.aguiar@us.af.mil

The purpose of this is to support the facility’s building standards for door hardware. The facility maintains the following hardware and is currently stocking replacement parts. The products listed in this booklet are to be used without substitution on new construction and modernization projects unless products are listed in this package as an alternate.

It is the intent of this booklet to provide guidelines for the architect’s specification section 08710, for product groups and the hardware schedule. It remains the architect’s responsibility to coordinate these products to meet the applicable building codes, life safety codes, and ADA requirements.

Section 08710 door hardware preamble must specify the following:

Door and frame prep Before hardware installation, verify that all doors and frames are properly prepared to receive the specified hardware. Hollow metal frames shall be prepared for ANSI strike plates per A115.1-2 (4-7/8” high), hinge preps will be mortised and reinforced with a minimum of 10 gauge reinforcement material;

minimum of 14 gauge reinforcement material for closer. Hollow metal doors shall be properly prepared and reinforced with a minimum of 16 gauge material for either mortised or cylindrical locks as specified. It is preferred that all hollow metal doors receiving door closers have 14 gauge reinforcement. If this is not possible, the use of sex bolts is mandatory. Wood doors shall be factory prepared to receive the scheduled hardware.

Hardware installation The manufacturer’s representative for the locking devices and closing devices must inspect and approve, in writing, the installation of their products. Hardware installed incorrectly must be reported to the architect prior to the architect’s final punch list.

For specifications or questions, please contact:

Jenny Senner CSI, CDT Architectural Consultant Representative Stanley Security Solutions Phone: (206) 419-5479 Jenny.Senner@sbdinc.com

FAIRCHILD AIR FORCE BASE DESIGN STANDARDS 30 April 2018

DIVISION 08 - OPENINGS

SECTION 087100 - DOOR HARDWARE

FAIRCHILD SPECIFICATION

Stanley 661HD-UL 628

Markar

Hanging Devices

Continuous Hinge

Alternate

Mortise Hinge Stanley FBB199 x NRP (Heavy use exterior doors) 626 FBB168 (Heavy use interior doors) 652 FBB179 (Interior doors) 652 Non Removable Pin (NRP) at interior out-swing doors

McKinney

Securing Devices

Lock Set Best

Alternate Schlage

Key System Best Removable/Interchangeable Core Visual Key Control – Keys Stamped “Do Not Duplicate” Stamp Keys, Stamp Cores,7-pin SFIC (Existing System)

Padlock Best 21B7220-L include 4 per project 626

Alternate

Exit Device

2403CD x 2003C (single door, narrow stile, exterior) 630 2401CD x 2001 X 2403CD x 2003C x KR822 (pr, narrow stile, ext.) 630 2103CD x Trim (at single door, exterior) 630 2101CD x 2103CD x NL Trim X KR822 (at pairs, exterior) FL2108 x 4908A (rated single doors) 630 FL2101 X FL2108 x 4908A x FLKR822 (rated pairs) 630 N674DA-3 Dummy push bars at vestibule doors 630

All non-rated exit devices to have cylinder dogging Keyed removable mullions ”ALK” option when specified Install using SNB for all exit devices

FAIRCHILD AIR FORCE BASE DESIGN STANDARDS 30 April

DIVISION 08 - OPENINGS

SECTION 087100 - DOOR HARDWARE

Coordinator Trimco 3094 Series x 2/3095 /or/ 3096 600 Use coordinator where required by fire code

Automatic Flush Bolts Trimco 3810 x 3810 (Automatic) (metal doors) 626 3815 x 3815 (Automatic) (wood doors) 626

Manual Flush Bolts Trimco 3917 (Manual) (metal doors) 626 3913 (Manual) (wood doors) 626

Closing Device

Surface Closer •

Alternate

Stops & HoIders

Door Stop Trimco 1270 CXCP Wall Stop (Interior) 626 1211 -Floor Stop (Interior) 626 1214CK –Floor Stop (Exterior) 626

• Allow for maximum swing of doors

• Backing required at wall stops

Accessories

Push / Pull Bars Trimco 1729 630

Push / Pull Plate Trimco 1001 x 1017-3B 630

Armor Plate Trimco KO050 40" x 2" LDW x B3E x CSK (Single doors) 630 KO050 40" x 1" LDW x B3E x CSK (Pair doors) 630

Kick Plate Trimco KO050 10" x 2" LDW x B3E x CSK (Single doors) 630 KO050 10" x 1" LDW x B3E x CSK (Pair doors) 630

Mop Plate Trimco KO050 4" x 2" LDW x B3E x CSK (Single doors) 630 KO050 4" x 1" LDW x B3E x CSK (Pair doors) 630

Threshold Pemko 171A (1/2" x 5" Saddle threshold) MIL Architect to coordinate with project conditions

Smoke Seal Pemko S88

Weather Seal Pemko 305CS (at head and jambs) 628 18061 (at sill on door – surface mount) 628

Astragal Pemko 355CS 628

FAIRCHILD AIR FORCE BASE DESIGN STANDARDS 30 April 2018

DIVISION 08 - OPENINGS

SECTION 087100 - DOOR HARDWARE

Meeting Stile Pemko 303CV 628

Drip Guard Pemko 346C x 4" ODW (Exterior doors exposed to rain) 628

Door Silencer Trimco 1229A (Metal Frames) Gray 1229B (Wood Frames) Gray

FAIRCHILD AIR FORCE BASE DESIGN STANDARDS 30 April 2018

DIVISION 08 - OPENINGS

SECTION 087100 - DOOR HARDWARE

FAIRCHILD AIR FORCE BASE DESIGN STANDARDS 30 April

DIVISION 08 - OPENINGS

SECTION 087100 - DOOR HARDWARE

SECTION 087100 - DOOR HARDWARE

SECTION 087100 - DOOR HARDWARE

SECTION 087100 - DOOR HARDWARE

SECTION 087100 - DOOR HARDWARE

SECTION 087100 - DOOR HARDWARE

SECTION 087100 - DOOR HARDWARE

SECTION 087100 - DOOR HARDWARE

SECTION 087100 - DOOR HARDWARE

Outside trim operation

Trim operation lever or knob

996L Breakaway™ lever

Standard

Key locks and unlocks lever or knob. e.g., 996L (Classroom)

Lever styles

06*

Default lever

Knurling available

Standard Levers

FAIRCHILD AIR FORCE BASE DESIGN STANDARDS 30 April 2018

DIVISION 08 - OPENINGS

SECTION 087100 - DOOR HARDWARE

98/99 Rim exit device

98 and 99 Rim exit devices for all types of single and double doors with mullion, UL listed for panic exit hardware. Devices are ANSI A156.3 – 2001 Grade 1. The 98 device has a smooth mechanism case and the 99 device has a grooved case. The rim device is non-handed except when the following device options are used: SD (special dogging), -2 (double cylinder) or SS (signal switch). See

Opposite page for available outside trim and device functions. Covers stock hollow metal doors with

86 or 161 cutouts on single doors (may cover cutouts on pairs – consult template).

Finishes – US3, US3A, US4, US4A, US10, US26, US26D, US26D-AM Antimicrobial, US28, 313, 315 &

643E. US15 and US32D available with 98 Series only.

The 299 Strike ships standard, optional strikes available

Hex key dogging comes standard on 98/99 Rim exit devices

Specifications Device functions Device ships EO/DT/NL. Field selectable. For TP, K or L remove

NL drive screw from device.

Device lengths 3'

4'

2'4' to 3' (711mm to 914 mm) Door size

2'10" to 4' (864 mm to 1219 mm) Door size

Device centerline from finished floor

39 13/16" (1011 mm)

39 11/16" (1008 mm) with mullion

Center case dimensions

8" x 2 3/4" x2 3/8" (203mm x 70mm x 60mm)

Mechanism case dimensions

2 1/4" x 2 1/4" (57mm x 57mm)

Projection Pushbar neutral – 3 13/16" (97 mm)

Pushbar depressed – 3 1/16" (78 mm)

Latch bolt Deadlocking, 3/4" (19mm) throw

Fasteners & sex bolts (SNB)

Includes screw pack for 1 3/4" (44mm) and 2 1/4" (57mm) thick metal or wood doors. Optional 425 SNB available, see page 9 for quantities.

Electric options LX

RX

RX2

E

EL

QEL

SS

CX

ALK

Latchbolt monitor switch

Pushpad monitor switch

Double pushpad monitor switch

Electric locking & unlocking trim

Electric latch retraction

Quiet electric latch retraction

Signal switch

Chexit delayed exit

Alarm exit kit

WP-RX Waterproof request to exit

CON Allegion Connect

Mechanical options

-2

AX

GBK

PN

XP

SNB

SEC

Double cylinder

Accessible device Glass bead kit

Pneumatic latch retraction

Extra protection

Sex bolts

Security screws

Hex key dogging standardDogging feature

Dogging options CD

SD

LD

DI

CI

Cylinder dogging

Special center case dogging

Less dogging

Dogging indicator

Cylinder dogging indicator

Strikes 299 – Dull black

QEL

Quiet electric latch retraction

• Bolt retraction via switch

• Converts exit door to push-pull operation

CX

Chexit delayed exit

• Meets NFPA 101 requirements

• Self-contained controls, locking, alarm

ALK

Alarm exit kit

• Unauthorized opening triggers 85-decibel horn

• Set in armed or disarmed mode by key

CON

Allegion Connectors

• Common connectors to connect various door hardware all the way to the power supply

RX

Pushpad monitor switch

• Signals use of an opening

• SPDT switch to monitor pushpad

XP

Extra protection

• 90˚ latch-to-strike contact

• Force resistance of 2,000+ lbs.

AX

Accessible device

• UL certified to meet new 5 lb.

maximum operating force requirement

• Exceeds ANSI/

BHMA

requirements

CD

Cylinder dogging

• Replaces hex key dogging

• Requires standard 1 1/4" mortise cylinder

EL

Electric latch retraction

• Enables remote unlatching

• Alternative to manual dogging

PN

Pneumatic latch retraction

• For areas where electrical devices banned

• Special linkage for mechanical or pneumatic dogging

FAIRCHILD AIR FORCE BASE DESIGN STANDARDS 30 April 2018

DIVISION 08 - OPENINGS

SECTION 087100 - DOOR HARDWARE

98-F/99-F Rim exit device

98-F and 99-F Rim fire exit devices for all types of single doors up to 4' x 10' (1219mm x 3048mm) or 8' x 10' (2438mm x 3048mm) double doors with 9954 or 9854 mullion, UL listed for fire exit hardware. See page 61 for detailed information on UL listed fire exit hardware label and door opening size information. Devices are ANSI A156.3 – 2001 Grade 1. The 98-F device has a smooth mechanism case and the 99-F device has a grooved case. The rim device is non-handed except when the following device options are used: -2 (double cylinder) or SS (signal switch). See opposite page for available outside trim and device functions.

Finishes – US3, US3A, US4, US4A, US10, US26, US26D, US26D-AM Antimicrobial, US28, 313, 315 &

643E. US15 and US32D available with 98 Series only.

Specifications Device functions Device ships EO/DT/NL. Field selectable. For TP, K or L remove

NL drive screw from device.

Device lengths 3'

4'

2'4' to 3' (711mm to 914 mm) Door size

2'10" to 4' (864 mm to 1219 mm) Door size

Device centerline from finished floor

39 13/16" (1011 mm)

39 11/16" (1008 mm) with mullion

Center case dimensions

8" x 2 3/4" x2 3/8" (203mm x 70mm x 60mm)

Mechanism case dimensions

2 1/4" x 2 1/4" (57mm x 57mm)

Projection Pushbar neutral – 3 13/16" (97 mm)

Pushbar depressed – 3 1/16" (78 mm)

Latch bolt Deadlocking, 3/4" (19mm) throw

Fasteners & sex bolts (SNB)

Includes screw pack for 1 3/4" (44mm) and 2 1/4" (57mm) thick metal or wood doors. Optional 425 SNB available for metal doors. 425 & 825 SNB required on wood doors without SLM blocking. See page 11 for quantities.

Electric options LX

RX

RX2

E

EL

QEL

SS

CX

ALK

Latchbolt monitor switch

Pushpad monitor switch

Double pushpad monitor switch

Electric locking & unlocking trim

Electric latch retraction

Quiet electric latch retraction

Signal switch

Chexit delayed exit

Alarm exit kit

WP-RX Waterproof request to exit

CON Allegion Connect

Mechanical options

-2

AX

GBK

PN

XP

SNB

SEC

SLM

Double cylinder

Accessible device Glass bead kit

Pneumatic latch retraction

Extra protection

Sex bolts

Security screws

Special Laminate Material Blocking

Dogging option No mechanical dogging. EL and QEL option available

Strikes 299F – Dull black, 499F with mullions

CX

Chexit delayed exit

• Meets NFPA 101 requirements

• Self-contained controls, locking, alarm

SG

Safety glow

• Shows exit door location in darkness or smoke

• Developed to meet MEA standards

ALK

Alarm exit kit

• Unauthorized opening triggers 85-decibel horn

• Set in armed or disarmed mode by key

RX

Pushpad monitor switch

Signals use of an opening

SPDT switch to monitor pushpad

XP

Extra protection

• 90˚ latch-to-strike contact

• Force resistance of 2,000+ lbs.

EL

Electric latch retraction

• Enables remote unlatching

• Alternative to manual dogging

PN

Pneumatic latch retraction

For areas where electrical devices banned

Special linkage for mechanical or pneumatic dogging

The 299F Strike ships standard, optional strikes available

499F Strike with

9854/9954 mullion

QEL

Quiet electric latch retraction

• Bolt retraction via switch

• Converts exit door to push-pull operation

AX

Accessible device

UL certified to meet new 5 lb.

maximum operating force requirement

Exceeds ANSI/

BHMA

requirements

CON

Allegion Connectors

• Common connectors to connect various door hardware all the way to the power supply

FAIRCHILD AIR FORCE BASE DESIGN STANDARDS 30 April 2018

DIVISION 08 - OPENINGS

SECTION 087100 - DOOR HARDWARE

9827/9927 Surface mounted vertical rod device

9827/9927 Surface mounted vertical rod device for all types of single or double doors, UL listed for panic exit hardware. Devices are ANSI A156.3 – 2001 Grade 1. Covers stock hollow metal doors with 86 or 161 cutouts. The 9827 device has a smooth mechanism case and the 9927 device has a grooved case. The surface vertical rod device is non-handed except when the following device options are used: SD (special dogging), or SS (signal switch). See opposite page for available outside trim and functions. Vertical rod and latch guards are available to protect the bottom rod of the exit device from damage by impacts of carts or gurneys passing through doors.

Finishes – US3, US3A, US4, US4A, US10, US26, US26D, US26D-AM Antimicrobial, US28, 313, 315 &

643E. US15 and US32D available with 98 Series only.

Specifications Device functions Device ships EO/DT/NL. Field selectable. For TP, K or L remove

NL drive screw from device.

Device lengths 2'

3'

4'

2" (610 mm) Door size (shipped less UL label)

2'4' to 3' (711mm to 914 mm) Door size

2'10" to 4' (864 mm to 1219 mm) Door size

Device centerline from finished floor

395/8" (1006 mm)

Center case dimensions

8" x 2 3/4" x2 3/8" (203mm x 70mm x 60mm)

Mechanism case dimensions

2 1/4" x 2 1/4" (57mm x 57mm)

Projection Pushbar neutral – 3 13/16" (97 mm)

Pushbar depressed – 3 1/16" (78 mm)

Latch bolt Deadlocking anti-friction top & bottom bolt, 5/8" (16mm) throw

Door undercut 1/4" (7mm) recommended

Top & bottom

Latch case

4 1/2" x 2 1/8" x 1 1/2" (114mm x 54mm x 38mm)

Vertical rods 1/2" square tubing, standard rods accommodate 7' (2134mm) doors. Top rod length: 34 15/16" (887mm); Bottom rod length:

31 1/2" (794mm) Extension rods available in 1' (205mm) or 3'

(914mm) for doors over 7'. One piece top rod is available for 8'

(2438mm) and 10' (3048mm) doors.

Fasteners & sex bolts (SNB)

Includes screw pack for 1 3/4" (44mm) to 2 1/4" (57mm) thick metal or wood doors, and 325 SNB for top and bottom latch.

Optional 425 SNB available.

Electric options LX

RX

RX2

EL

QEL

SS

CX

ALK

PN

LBR

Latchbolt monitor switch

Pushpad monitor switch

Double pushpad monitor switch

Electric latch retraction

Quiet electric latch retraction

Signal switch

Chexit delayed exit

Alarm exit kit

Pneumatic latch retraction

Less bottom rod

WP-RX Waterproof request to exit

CON Allegion Connect

Mechanical options

GBK

PL

WS

SNB

SEC

Glass bead kit

Pullman latch

Tornado and hurricane tested

Sex bolts

Security screws

Hex key dogging standardDogging feature

Dogging option CD

SD

LD

DI

CI

Cylinder dogging

Special center case dogging

Less dogging

Dogging indicator

Cylinder dogging indicator

Strikes Top - 299 – Dull black, Bottom – 248L4 & 304L - Unfinished

SS

Signal switch

• Signals unauthorized use of an opening

• Switch makes latch bolt tamper-resistant

ALK

Alarm exit kit

• Unauthorized opening triggers 85-decibel horn

• Set in armed or disarmed mode by key

RX

Pushpad monitor switch

• Signals use of an opening

• SPDT switch to monitor pushpad

EL

Electric latch retraction

• Enables remote unlatching

• Alternative to manual dogging

PN

Pneumatic latch retraction

• For areas where electrical devices banned

• Special linkage for mechanical or pneumatic dogging

Hex key dogging comes standard on 9827/9927

QEL

Quiet electric latch retraction

• Bolt retraction via switch

• Converts exit door to push-pull operation

WS

Windstorm

Severe weather certified/tested

FEMA and ICC compliant

• Tornado & hurricane tested

E (E996L) Electrified breakaway lever

• Electrified remote locking/unlocking

• Standard in fail safe condition

CX

Chexit delayed exit

• Meets NFPA 101 requirements

• Self-contained controls, locking, alarm

299 Top strike

248L4 Bottom Strike for use with flat threshold

304L Bottom strike

Top latch

Bottom latch

CON

Allegion Connectors

• Common connectors to connect various door hardware all the way to the power supply

FAIRCHILD AIR FORCE BASE DESIGN STANDARDS 30 April 2018

DIVISION 08 - OPENINGS

SECTION 087100 - DOOR HARDWARE

9827-F/9927-F Fire exit surface mounted vertical rod device pairs of doors up to 8' x 10'

(2438mm x 3048mm) , UL listed for fire exit hardware. See page 68 for detailed information on

UL listed fire exit hardware label and door opening size information. Devices are ANSI A156.3 –

2001 Grade 1. The 9827-F device has a smooth mechanism case and the 9927-F device has a grooved case. The surface vertical rod device is non-handed except when the following device options are used: SS (signal switch). See opposite page for available outside trim and device functions. Vertical rod and latch guards are available to protect the bottom rod of the exit device from damage by impacts of carts or gurneys passing through doors. Rod and latch guards can be used on hollow metal or tin clad composite fire doors.

Finishes – US3, US4, US10, US26, US26D, US28 & 313. US15 and US32D available with 98

Series only.

Specifications Device functions Device ships EO/DT/NL. Field selectable. For TP, K or L remove

NL drive screw from device.

Device lengths 2'

3'

4'

2" (610 mm) Door size (shipped less UL label)

2'4' to 3' (711mm to 914 mm) Door size

2'10" to 4' (864 mm to 1219 mm) Door size

Device centerline from finished floor

395/8" (1006 mm)

Center case dimensions

8" x 2 3/4" x2 3/8" (203mm x 70mm x 60mm)

Mechanism case dimensions

2 1/4" x 2 1/4" (57mm x 57mm)

Projection Pushbar neutral – 3 13/16" (97 mm)

Pushbar depressed – 3 1/16" (78 mm)

Latch bolt Deadlocking anti-friction top & bottom bolt, 5/8" (16mm) throw

Door undercut 1/4" (7mm) recommended

Top & bottom

Latch case

4 1/2" x 2 1/8" x 1 1/2" (114mm x 54mm x 38mm)

Vertical rods 1/2" square tubing, standard rods accommodate 7' (2134mm) doors. Top rod length: 34 15/16" (887mm); Bottom rod length:

31 1/2" (794mm) Extension rods available in 1' (205mm) or 3'

(914mm) for doors over 7'. One piece top rod is available for 8'

(2438mm) and 10' (3048mm) doors.

Fasteners & sex bolts (SNB)

Includes screw pack for 1 3/4" (44mm) to 2 1/4" (57mm) thick metal or wood doors, and 325 SNB for top and bottom latch.

Optional 425 SNB available.

Electric options LX

RX

RX2

E

EL

QEL

SS

CX

ALK

Latchbolt monitor switch

Pushpad monitor switch

Double pushpad monitor switch

Electric unlocking and locking trim

Electric latch retraction

Quiet electric latch retraction

Signal switch

Chexit delayed exit

Alarm exit kit

WP-RX Waterproof request to exit

CON Allegion Connect

Mechanical options

GBK

PN

LBR

PL

WS

SNB

SEC

SLM

Glass bead kit

Pneumatic latch retraction

Less bottom rod

Pullman latch

Tornado and hurricane tested

Sex bolts

Security screws

Special laminate material blocking

Dogging option No mechanical dogging. EL and QEL option available

99F (499F LBR) Dull black, Bottom – 304L - Unfinished

ALK

Alarm exit kit

• Unauthorized opening triggers 85-decibel horn

• Set in armed or disarmed mode by key

RX

Pushpad monitor switch

• Signals use of an opening

• SPDT switch to monitor pushpad

EL

Electric latch retraction

Enables remote unlatching

Alternative to manual dogging

PN

Pneumatic latch retraction

• For areas where electrical devices banned

• Special linkage for mechanical or pneumatic dogging

QEL

Quiet electric latch retraction

• Bolt retraction via switch

• Converts exit door to push-pull operation

WS

Windstorm

• Severe weather certified/tested

• FEMA and ICC compliant

• Tornado & hurricane tested

E (E996L) Electrified breakaway lever

• Electrified remote locking/unlocking

• Standard in fail safe condition

LBR

Less bottom rod

• Available with UL

Fire Label

• For pairs of vertical rod devices

CX

Chexit delayed exit

Meets NFPA 101 requirements

Self-contained controls, locking, alarm

299 Top strike

499F Top strike - LBR

304L Bottom strike

Top latch

Bottom latch

9827-F/9927-F Surface Mounted Vertical Rod Fire Device

CON

Allegion Connectors

• Common connectors to connect various door hardware all the way to the power supply

FAIRCHILD AIR FORCE BASE DESIGN STANDARDS 30 April 2018

DIVISION 08 - OPENINGS

SECTION 087100 - DOOR HARDWARE

9847/9947 Concealed vertical rod device

9847/9947 Concealed vertical rod device for use on single or double metal doors, UL listed for panic exit hardware. Devices are ANSI A156.3 – 2001 Grade 1. The 9847 device has a smooth mechanism case and the 9947 device has a grooved case. The concealed vertical rod device is non-handed except when the following device options are used: SD (special dogging), or SS (signal switch). See opposite page for available outside trim and device functions.

Finishes – US3, US3A, US4, US4A, US10, US26, US26D, US26D-AM Antimicrobial, US28, 313, 315 &

643E. US15 and US32D available with 98 Series only.

Specifications Device functions Device ships EO/DT/NL. Field selectable. For TP, K or L remove

NL drive screw from device.

Device lengths 2'

3'

4'

2" (610 mm) Door size (shipped less UL label)

2'4' to 3' (711mm to 914 mm) Door size

2'10" to 4' (864 mm to 1219 mm) Door size

Device centerline from finished floor

395/8" (1006 mm) Standard

Adjustable from 355/8" (905mm) to 495/8" (1260mm)

Center case dimensions

8" x 2 3/4" x2 3/8" (203mm x 70mm x 60mm)

Mechanism case dimensions

2 1/4" x 2 1/4" (57mm x 57mm)

Projection Pushbar neutral – 3 13/16" (97 mm)

Pushbar depressed – 3 1/16" (78 mm)

Latch bolt Deadlocking top & bottom bolt, 5/8" (16mm) throw

Door undercut 1/4" (7mm) recommended

Top & bottom

Latch case

4 1/2" x 2 1/8" x 1 1/2" (114mm x 54mm x 38mm)

Vertical rods Round 2-piece adjustable rods – Top rod adjustable from 6'8"

(2027mm) to 8'4"(2533mm). Bottom rod adjustable 35 5/8"

(905 mm) to 49 5/8" (1260 mm). Extension rod kits available for doors over 8'4" (2533mm).

Fasteners & sex bolts (SNB)

Includes screw pack for 1 3/4" (44mm) to 2 1/4" (57mm) thick metal doors. Optional 425 SNB available.

Electric options LX

RX

RX2

E

EL

QEL

SS

CX

ALK

Latchbolt monitor switch

Pushpad monitor switch

Double pushpad monitor switch

Electric unlocking and locking trim

Electric latch retraction

Quiet electric latch retraction

Signal switch

Chexit delayed exit

Alarm exit kit

WP-RX Waterproof request to exit

CON Allegion Connect

Mechanical options

GBK

PN

LBR

PL

SNB

SEC

Glass bead kit

Pneumatic latch retraction

Less bottom rod

Pullman latch

Sex bolts

Security screws

Hex key dogging standardDogging feature

Dogging option CD

SD

LD

DI

CI

Cylinder dogging

Special center case dogging

Less dogging

Dogging indicator

Cylinder dogging indicator

Strikes Top – 338 - Unfinished, Bottom – 385A - Unfinished

DI

Dogging indicator

• Monitor dogging status without a control panel

• Red indicator light shows visibility to dogging from

ALK

Alarm exit kit

• Unauthorized opening triggers 85-decibel horn

• Set in armed or disarmed mode by key

RX

Pushpad monitor switch

Signals use of an opening

SPDT switch to monitor pushpad

EL

Electric latch retraction

• Enables remote unlatching

• Alternative to manual dogging

PN

Pneumatic latch retraction

• For areas where electrical devices banned

• Special linkage for mechanical or pneumatic dogging

Hex key dogging comes standard on 9847/9947

Concealed vertical rod devices

E (E996L) Electrified breakaway lever

• Electrified remote locking/unlocking

• Standard in fail safe condition

LX

Latchbolt monitor switch

• Signals use of an opening

• SPDT switch to monitor latch bolt

QEL

Quiet electric latch retraction

Bolt retraction via switch

Converts exit door to push-pull operation

Top Strike

385A Bottom Strike

Top Latch

Bottom Latch

CX

Chexit delayed exit

Meets NFPA 101 requirements

Self-contained controls, locking, alarm

CON

Allegion Connectors

• Common connectors to connect various door hardware all the way to the power supply

FAIRCHILD AIR FORCE BASE DESIGN STANDARDS 30 April 2018

DIVISION 08 - OPENINGS

SECTION 087100 - DOOR HARDWARE

9847-F/9947-F Fire exit concealed vertical rod device for use on pairs of doors up to 8' x 10'

(2438mm x 3048mm) , UL listed for fire exit hardware. See page 68 for detailed information on

UL listed fire exit hardware label and door opening size information. Devices are ANSI A156.3

– 2001 Grade 1. The 9847-F device has a smooth mechanism case and the 9947-F device has a grooved case. The concealed vertical rod device is non-handed except when the following device option is used: SS (signal switch) devices. See opposite page for available outside trim and functions.

Finishes – US3, US3A, US4, US4A, US10, US26, US26D, US26D-AM Antimicrobial, US28, 313, 315 & 643E. US15 and US32D available with 98 Series only.

Specifications Device functions Device ships EO/DT/NL. Field selectable. For TP, K or L remove

NL drive screw from device.

Device lengths 2'

3'

4'

2" (610 mm) Door size (shipped less UL label)

2'4' to 3' (711mm to 914 mm) Door size

2'10" to 4' (864 mm to 1219 mm) Door size

Device centerline from finished floor

395/8" (1006 mm) Standard

Adjustable from 355/8" (905mm) to 495/8" (1260mm)

Center case dimensions

8" x 2 3/4" x2 3/8" (203mm x 70mm x 60mm)

Mechanism case dimensions

2 1/4" x 2 1/4" (57mm x 57mm)

Projection Pushbar neutral – 3 13/16" (97 mm)

Pushbar depressed – 3 1/16" (78 mm)

Latch bolt Deadlocking top & bottom bolt, 5/8" (16mm) throw

Door undercut 1/4" (7mm) recommended

Top & bottom

Latch case

3 3/4" x 1 1/2" x 1" (95mm x 38mm x 25mm)

Vertical rods Round 2-piece adjustable rods – Top rod adjustable from 6'8"

(2027mm) to 8'4"(2533mm). Bottom rod adjustable 35 5/8"

(905 mm) to 49 5/8" (1260 mm). Extension rod kits available for doors over 8'4" (2533mm).

Fasteners & sex bolts (SNB)

Includes screw pack for 1 3/4" (44mm) to 2 1/4" (57mm) thick metal doors. Optional 425 SNB available.

Electric options LX

RX

RX2

E

EL

QEL

SS

CX

ALK

Latchbolt monitor switch

Pushpad monitor switch

Double pushpad monitor switch

Electric unlocking and locking trim

Electric latch retraction

Quiet electric latch retraction

Signal switch

Chexit delayed exit

Alarm exit kit

WP-RX Waterproof request to exit

CON Allegion Connect

Mechanical options

LBR

PN

GBK

SNB

SEC

SLM

Less bottom rod

Pneumatic latch retraction

Glass bead kit

Sex bolts

Security screws

Special laminate material blocking

Dogging option No mechanical dogging. EL and QEL option available

Strikes Top – 338 - Unfinished, Bottom – 385A - Unfinished

9847-F/9947-F Concealed vertical rod fire exit device

ALK

Alarm exit kit

• Unauthorized opening triggers 85-decibel horn

• Set in armed or disarmed mode by key

RX

Pushpad monitor switch

• Signals use of an opening

• SPDT switch to monitor pushpad

EL

Electric latch retraction

• Enables remote unlatching

• Alternative to manual dogging

PN

Pneumatic latch retraction

• For areas where electrical devices banned

• Special linkage for mechanical or pneumatic dogging

RG

Rod guard

• Protection from carts/gurneys

• Eases wheelchair access

E (E996L) Electrified breakaway lever

• Electrified remote locking/unlocking

• Standard in fail safe condition

LX

Latchbolt monitor switch

• Signals use of an opening

• SPDT switch to monitor latch bolt

QEL

Quiet electric latch retraction

• Bolt retraction via switch

• Converts exit door to push-pull operation

CX

Chexit delayed exit

• Meets NFPA 101 requirements

• Self-contained controls, locking, alarm

Top Strike

385A Bottom Strike

Top Latch

Bottom Latch

CON

Allegion Connectors

• Common connectors to connect various door hardware all the way to the power supply

FAIRCHILD AIR FORCE BASE DESIGN STANDARDS 30 April 2018

DIVISION 08 - OPENINGS

SECTION 087100 - DOOR HARDWARE

pril 8FAIRCHILD AIR FORCE BASE DESIGN STANDARDS 30 April 2018

SECTION 087100 - DOOR HARDWARE

SECTION 087100 - DOOR HARDWARE

SECTION 087100 - DOOR HARDWARE

SECTION 087100 - DOOR HARDWARE

SECTION 087100 - DOOR HARDWARE

SECTION 087100 - DOOR HARDWARE

SECTION 087100 - DOOR HARDWARE

SECTION 087100 - DOOR HARDWARE

SECTION 087100 - DOOR HARDWARE

SECTION 087100 - DOOR HARDWARE

SECTION 087100 - DOOR HARDWARE

SECTION 087100 - DOOR HARDWARE

SECTION 087100 - DOOR HARDWARE

2018 BASE DESIGN STANDARDS
Division Outline
Table of Contents
Introduction
References
Military References
Non-Military References
DIV A - DESIGN SPECIFIC REQUIREMENTS
DIV A Section A.1 -DATA - Specifications, Drawings, and Mapping Requirements
DIV A Section A.1 -ATTACHMENT - Submittal Checklist
DIV A Section A.2-DATA - Structural and Civil Requirements
DIV A Section A.3-DATA - Environmental
DIV A Section A.3-Environmental Forms
DIV A Section A.4-DATA - Antiterrorism / Force Protection
DIV A Section A.5-DATA - Demolition
DIV 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
DIV 00-DATA General Requirements
DIV 01 - GENERAL REQUIREMENTS
DIV 01 Section 011100-DATA - Summary of Work
DIV 01 Section 011100-SPEC - Summary of Work
DIV 01 Section 012513-DATA - Product Substitution Procedures
DIV 01 Section 012513-SPEC - Product Substitution Procedures
DIV 01 Section 013100-DATA - Project Managment and Coordination
DIV 01 Section 013100-SPEC - Project Management and Coordination
DIV 01 Section 013100-ATTACHMENT - Request for Information
DIV 01 Section 013200-DATA - Construction Progress Documentation
DIV 01 Section 013300-DATA - Submittal Procedures
DIV 01 Section 013300-SPEC - Submittal Prcedures
DIV 01 Section 013520-DATA - Safety Requirements
DIV 01 Section 013520-SPEC - Safety Requirements
DIV 01 Section 013543-DATA - Enviromental Procedures
DIV 01 Section 013543-SPEC - Environmental Procedures
DIV 01 Section 013543-ATTACHMENT - Solid Waste Tracking Sheet
DIV 01 Section 013543-ATTACHMENT - Hazardous Materials Tracking Sheet
DIV 01 Section 014516-DATA - Quality Requirements
DIV 01 Section 014516-SPEC - Quality Procedures
DIV 01 Section 014516-ATTACHMENT - Daily Construction Quality Control Report
DIV 01 Section 014516-ATTACHMENT - Contractor Test Report
DIV 01 Section 015000-DATA - Temporary Facilities and Controls
DIV 01 Section 015000-SPEC - Temporary Facilities and Controls
DIV 01 Section 016000-DATA - Product Requirements
DIV 01 Section 016000-SPEC - Product Requirements
DIV 01 Section 016000-ATTACHMENT - Contractors Recovered Materials Certification Users Guide
DIV 01 Section 017329-DATA - Cutting and Patching
DIV 01 Section 017329-SPEC - Cutting and Patching
DIV 01 Section 017700-DATA - Closeout Procedures
DIV 01 Section 017700-SPEC - Closeout Procedures
DIV 01 Section 017720- DATA - Equipment-In-Place List
DIV 01 Section 017720-SPEC - Equipment-In-Place List
DIV 01 Section 017720-ATTACHMENT - Equipment In Place List
DIV 01 Section 017823-DATA - Operation and Maintenance Data
DIV 01 Section 017823-SPEC - Operation and Maintenance Data
DIV 01 Section 017823-ATTACHMENT - O&M Manual-Review Checklist
DIV 01 Section 017836-DATA - Warranties
DIV 01 Section 017836-SPEC - Warranties
DIV 01 Section 017839-DATA - Project Record Documents
DIV 01 Section 017839-SPEC - Project Record Documents
DIV 01 Section 017900-DATA - Demonstration and Training
DIV 02 - EXISTING CONDITIONS
DIV 02 Section 020000-DATA - Existing Conditions
DIV 02 Section 028200-SPEC - Asbestos Abatement
DIV 03 - CONCRETE
DIV 03 Section 030000-DATA - General Requirements
DIV 04 - MASONRY
DIV 04 Section 040000-DATA - General Requirements
DIV 04 Section 042000-DATA - Unit Masonry
DIV 05 - METALS
DIV 05 Section 050000-DATA - General Requirements
DIV 06 - WOODS, PLASTICS, AND COMPOSITES
DIV 06 Section 060000-DATA - General Requirements
DIV 06 Section 064000-DATA - Architectural Woodwork
DIV 07 - THERMAL AND MOISTURE PROTECT
DIV 07 Section 070000-DATA - General Requirements
DIV 07 Section 074113-DATA - Metel Roof Panels
DIV 07 Section 074113-SPEC - Metal Roof Panels
DIV 07 Section 074113-ATTACHMENT - Warranty of Construction
DIV 08 - OPENINGS
DIV 08 Section 080000-DATA - General Requirements
DIV 08 Section 087100-DATA - Door Hardware
DIV 08 Section 087100 SPEC GUIDELINE - Door Hardware
DIV 09 -FINISHES
DIV 09 Section 090000-DATA - General Requirements
DIV 09 Section 093013-DATA - Ceramic Tile
DIV 09 Section 096800-DATA - Carpet
DIV 09 Section 096800-SPEC - Carpet
DIV 10- SPECIALTIES
DIV 10 Section 100000-DATA - General Requirements
DIV 10 Section 101400-DATA - Signage
DIV 11- EQUIPMENT
DIV 11 Section 110000-DATA - General Requirements
DIV 12- FURNISHINGS
DIV 12 Section 120000-DATA - General Requirements
DIV 13 -SPECIAL CONSTRUCTION
DIV 13 Section 130000-DATA - General Requirements
DIV 13 Section 133419-DATA - Metal Buildings
DIV 14 - CONVEYING SYSTEMS
DIV 14 Section 140000-DATA - General Requirements
DIV 21 -FIRE SUPPRESSION
DIV 21 Section 210000-DATA - General Requirements
DIV 22-PLUMBING
DIV 22 Section 220000-DATA - General Requirements
DIV 23-HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
DIV 23 Section 230000-DATA - General Requirements
DIV 23 Section 230900-DATA - Instrumentation and Control for HVAC Emergency Management and Control System (EMCS)
DIV 23 Section 230900-SPEC - Instrumentation and Control for HVAC Energy Management and Control System (EMCS)
DIV 23 Section 230900-DETAIL - EMCS Block Diagram
DIV 23 Section 235200-DATA - Heating Boilers
DIV 26-ELECTRICAL
DIV 26 Section 260000-DATA - General Requirements
DIV 26 Section 262000-DATA - 15 Kv Electrical Distribution
DIV 26 Section 262713-SPEC - Electric Meters
DIV 26 Section 263213-DATA - Engine Generators
DIV 26 Section 264200-DATA - Cathodic Protection
DIV 27-COMMUNICATIONS
DIV 27 Section 270000-DATA - General Requirements
DIV 27 Section 275116-DATA - Mass Notification Systems
DIV 27 Section 275400-DATA - Klaxon and NAOC Alarm Systems
DIV 27 Section 275400-DETAIL SHEET - Klaxon and NAOC Alarm Systems
DIV 27 Section 275400-DETAIL 01 - Klaxon System at Facility
DIV 27 Section 275400-DETAIL 02 - NAOC System at Facility
DIV 28-ELECTRONIC SAFETY AND SECURITY
DIV 28 Section 284611-DATA - Carbon Monoxide Detection and Alarm
DIV 28 Section 284620-DATA - Fire Alarm System
DIV 31-EARTHWORK
DIV 31 Section 312000-DATA - Earth Moving
DIV 32- EXTERIOR IMPROVEMENTS
DIV 32 Section 320000-DATA - General Conditions
SECTION 320000 – GENERAL REQUIREMENTS
DATA SHEET
DIV 32 Section 320000-DETAIL SHEET - Miscellaneous Details
DIV 32 Section 320000-DETAIL-01 - Sidewalk Intersection
DIV 32 Section 320000-DETAIL-02 - Bollards
DIV 32 Section 320000-DETAIL-03 - Bike Rack
DIV 32 Section 320000-DETAIL-04 - Outdoor Bench
DIV 32 Section 321600-DETAIL SHEET - Curbs and Gutters
DIV 32 Section 321600-DETAIL-01 - Typical Curb and Gutter
DIV 32 Section 321600-DETAIL-02 - Typical Curb Cut
DIV 32 Section 321600-DETAIL-03 - Asphalt Curb Backing
DIV 32 Section 321600-DETAIL-04 - Earthen Curb Backing
DIV 32 Section 323100-DATA-Fences and Gates
DIV 32 Section 323100-DETAIL SHEET - Fences and Gates
DIV 32 Section 323100-DETAIL-01 - Wall Column
DIV 32 Section 323100-DETAIL-02 - Screen Wall
DIV 32 Section 323100-DETAIL-03 - Wall Screen or Enclosure
DIV 32 Section 328400-DATA - Planting Irrigation
DIV 32 Section 328400-DETAIL SHEET - Planting and Irrigation
DIV 32 Section 328400-DETAIL-01 - Flush Point
DIV 32 Section 328400-DETAIL-02 - Emitter
DIV 32 Section 328400-DETAIL-03 - Electric Control Valve
DIV 32 Section 328400-DETAIL-04 - Quick Coupler Valve
DIV 32 Section 328400-DETAIL-05 - Auto Drain Valve
DIV 32 Section 328400-DETAIL-06 - Backflow Preventer
DIV 32 Section 328400-DETAIL-07 - Swing Joint
DIV 32 Section 329000-DATA - Planting
DIV 32 Section 329000-ATTACHMENT - Contractor Pesticide Documentation Rqmts
DIV 32 Section 329300-DETAIL SHEETS - Plants
DIV 32 Section 329300-DETAIL-01 - Clear View Triangle
DIV 32 Section 329300-DETAIL-02 - Tree Planting
DIV 32 Section 329300-DETAIL-03 - Shrub Planting
DIV 32 Section 329300-DETAIL-04 - Ground Cover Planting

DIV 32 Section 329300-DATA SHEET - Deciduous Trees

DIV 33-UTILITIES
DIV 33 Section 330000-DATA - General Requirements
DIV 33 Section 330000-ATTACHMENT 01 - Utility Verification Procedures
DIV 33 Section 330000-ATTACHMENT 02 - Fire Suppression and Alarm Systems
DIV 33 Section 331233 -SPEC - Water Meters
DIV 33 Section 335113.00 30-SPEC - Gas Meters

END OF BDS