Attach 5 - VC and VE Reports.pdf

PDF 556 KB Posted

Attached to
Unfired Pressure Vessel (UPV) Inspections with Amendment 0003 Federal contract opportunity
Solicitation number
FA461325Q0007
Issued by
Department of the Air Force Global Strike Command

About this file

This file contains two AF Form 1222-AF Equivalent (7-12-13) Boiler or Pressure Vessel Inspection Reports from inspections conducted on 7-12-2021 at FE Warren Air Force Base in Wyoming.

The first report is for LP-Tank-1 in Area-501, a compressed air storage vessel manufactured by UNT Steel Corporation in 1953. The vessel has a maximum allowable working pressure (MAWP) of 200 PSI and actual operating pressure of 110 PSI. The inspection found the vessel unsatisfactory due to the safety relief valve being set at 250 PSI, which exceeds NFPA requirements limiting pressure to 100% of MAWP. The second report is for Air-1 in Building 34, an air receiver manufactured by Morganton in 2014. This vessel passed inspection with no deficiencies, showing proper thickness measurements and only minor surface corrosion. Both vessels underwent visual inspections per NBIC Part 2 standards, with pressure gages and safety devices documented.

View the file

Other files for this federal contract opportunity

Other files attached to Unfired Pressure Vessel (UPV) Inspections with Amendment 0003, newest first.
File Type Posted
Amendment 0003.pdf PDF
Attach 6 - Q and A Govt Responses II.pdf PDF
Amendment 0002.pdf PDF
Amendment 0001.pdf PDF
Attach 4 - Q and A Govt Responses.pdf PDF
Attach 3 - WD 2015-5405 (Rev24).pdf PDF
Attach 1 - PWS - UPV Inspections.pdf PDF
Attach 2 - AF 1222.pdf PDF
Solicitation - FA461325Q0007.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

File details come from the government source that posted it. Updated .