Questions and Answers – Part 1
Solicitation Number #
FA461322Q1033
Question
Question/Comment/Clarification Government Response
1) Are J-hooks acceptable for cable management? Yes, J-Hooks are acceptable as needed.
2) If necessary due to current communication outlet box condition, may the contractor install a new outlet box for the communication cables?
Yes, the contractor may install a new box if the condition prevents the use of the current box. No outlet boxes are known to be in this condition.
3) Is the jack pinout type 568 B wiring pattern?
Yes, as identified in section 1.1.4. on page 3 of the Performance Work Statement.
4) Is there a patch panel specific brand?
No, patch panel specifications as identified in section
1.1.5. on page 3 of the Performance Work Statement and in the TIC Handbook.
5) Who will coordinate scheduled access to the buildings post award?
90 CS Project Manager will coordinate scheduled access to the buildings.
6) Is there a required type of program that the as-built plans need to be submitted in?
No required type of program for the “AS-BUILT” plans, see section 1.2.2 Drawings on page 4 of the Performance Work Statement.
RFQ FA461322Q1033