Attachment 3 - Salient Characteristics.pdf
PDF 720 KB Posted
- Attached to
- Commercial Diesel Generator Set
- Solicitation number
- FA460826QC003
About this file
This is a Salient Characteristics document that specifies minimum requirements for a commercial diesel generator set procurement.
The requirement is for a single Commercial Diesel Generator Set rated at 800kW Standby 60Hz. The generator must meet U.S. EPA Stationary Emergency Application standards with Tier 2, NSPS CI Stationary Emergency emission certification and UL 2200 listing. The unit shall deliver 277/480 volts, 3-phase, Wye configuration, 4-wire power with a 60Hz, 480-volt alternator rated for 105°C standby operation. The generator must be housed in a green steel sound attenuated Level 2 enclosure with horizontal sound attenuated cooling air outlet and include a sub-base mounted 660-gallon UL142 compliant fuel tank with dual stub-up connections, high fuel fill alarm, and fuel water separator. The PowerCommand 2.3 Controller shall serve as the primary control system with LCD display in English, exhaust gas temperature gauge, and externally mounted emergency stop switch.
Additional specifications include dual 1200-amp circuit breakers (one on left at 600/415V, one on right at 600V) with bottom entry options, normal duty engine air cleaner, 12-amp regulated external battery charger, radiator cooling for 50°C ambient conditions with low coolant level shutdown protection, and a 208/240/480-volt AC coolant heater rated for 40°F minimum ambient temperature. The generator includes a 2-year base warranty, non-seismic vibration isolators with 3040-pound capacity and 3366-pound per inch spring rate, and start-up/commissioning services. All documentation and literature shall be provided in English.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Salient Characteristics, Version I, Current as of 16 July 2026
The following minimum requirements pertain to the Generator Requirement.
PART 1 – Commercial Diesel Generator Set, 800kW Standby 60Hz
1.1 EQUIPMENT REQUIREMENTS
1. Meet U.S. EPA, Stationary Emergency Application
2. Duty Rating - Standby Power (ESP)
3. Emission Certification, EPA, Tier 2, NSPS CI Stationary Emergency
4. Listing - UL 2200
5. Voltage - 277/480, 3 Phase, Wye, 4 Wire
6. Alternator - 60Hz, Wye, 480 Volts, 105C - Standby
7. Steel Sound Attenuated Level 2 Enclosure, with Exhaust System
8. Enclosure Color - Green, Steel
9. Cooling Air Outlet - Horizontal, Sound Attenuated
10. Fuel Tank - Sub Base, 660 Gallon, UL142 Compliant
11. Listing, ULC - S601 - 07
12. Alarm - High Fuel Fill
13. Fuel Water Separator
14. Fuel Tank Connection - Dual Stub Up
15. Control Mounting - Left Facing
16. PowerCommand 2.3 Controller
17. Gauge - Exhaust Gas Temperature
18. LCD Control Display
19. Stop Switch - Emergency, Externally Mounted
20. Control Display Language – English
21. Circuit Breaker or Entrance Box or Terminal Box - Right and Left
22. Circuit Breaker - 1200A, Left, 3P, 600/415V, UL/IEC, Serv Ent, 100%UL
23. Circuit Breaker - 1200A, Right, 3P, UL 600, IEC 415, UL Serv Ent, 100%
24. Circuit Breaker or Entrance Box - Bottom Entry, Left Side
25. Circuit Breaker or Entrance Box - Bottom Entry, Right Side
26. Engine Air Cleaner - Normal Duty
27. External Battery Charger - 12 Amp, Regulated
28. Engine Cooling - Radiator, 50C Ambient
29. Shutdown - Low Coolant Level
30. Coolant Heater - 208/240/480 Volts AC, 40F Minimum Ambient Temperature
31. Genset Warranty - 2 Years Base
32. Literature - English
33. Packing - None, Base Mounted Housing
34. Vibration Isolator Restraint, Non-Seismic-3040lbs, 1.00" Deflection, 3366lbs/in Spring Rate
35. Start-up/Commissioning
Attachment 3 - Salient Characteristics
FA460826QC0003
PART 1 – Commercial Diesel Generator Set, 800kW Standby 60Hz
File details come from the government source that posted it. Updated .