Attachment 3 - Salient Characteristics.pdf

PDF 720 KB Posted

Attached to
Commercial Diesel Generator Set
Solicitation number
FA460826QC003
Issued by

About this file

This is a Salient Characteristics document that specifies minimum requirements for a commercial diesel generator set procurement.

The requirement is for a single Commercial Diesel Generator Set rated at 800kW Standby 60Hz. The generator must meet U.S. EPA Stationary Emergency Application standards with Tier 2, NSPS CI Stationary Emergency emission certification and UL 2200 listing. The unit shall deliver 277/480 volts, 3-phase, Wye configuration, 4-wire power with a 60Hz, 480-volt alternator rated for 105°C standby operation. The generator must be housed in a green steel sound attenuated Level 2 enclosure with horizontal sound attenuated cooling air outlet and include a sub-base mounted 660-gallon UL142 compliant fuel tank with dual stub-up connections, high fuel fill alarm, and fuel water separator. The PowerCommand 2.3 Controller shall serve as the primary control system with LCD display in English, exhaust gas temperature gauge, and externally mounted emergency stop switch.

Additional specifications include dual 1200-amp circuit breakers (one on left at 600/415V, one on right at 600V) with bottom entry options, normal duty engine air cleaner, 12-amp regulated external battery charger, radiator cooling for 50°C ambient conditions with low coolant level shutdown protection, and a 208/240/480-volt AC coolant heater rated for 40°F minimum ambient temperature. The generator includes a 2-year base warranty, non-seismic vibration isolators with 3040-pound capacity and 3366-pound per inch spring rate, and start-up/commissioning services. All documentation and literature shall be provided in English.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Salient Characteristics, Version I, Current as of 16 July 2026

The following minimum requirements pertain to the Generator Requirement.

PART 1 – Commercial Diesel Generator Set, 800kW Standby 60Hz

1.1 EQUIPMENT REQUIREMENTS

1. Meet U.S. EPA, Stationary Emergency Application

2. Duty Rating - Standby Power (ESP)

3. Emission Certification, EPA, Tier 2, NSPS CI Stationary Emergency

4. Listing - UL 2200

5. Voltage - 277/480, 3 Phase, Wye, 4 Wire

6. Alternator - 60Hz, Wye, 480 Volts, 105C - Standby

7. Steel Sound Attenuated Level 2 Enclosure, with Exhaust System

8. Enclosure Color - Green, Steel

9. Cooling Air Outlet - Horizontal, Sound Attenuated

10. Fuel Tank - Sub Base, 660 Gallon, UL142 Compliant

11. Listing, ULC - S601 - 07

12. Alarm - High Fuel Fill

13. Fuel Water Separator

14. Fuel Tank Connection - Dual Stub Up

15. Control Mounting - Left Facing

16. PowerCommand 2.3 Controller

17. Gauge - Exhaust Gas Temperature

18. LCD Control Display

19. Stop Switch - Emergency, Externally Mounted

20. Control Display Language – English

21. Circuit Breaker or Entrance Box or Terminal Box - Right and Left

22. Circuit Breaker - 1200A, Left, 3P, 600/415V, UL/IEC, Serv Ent, 100%UL

23. Circuit Breaker - 1200A, Right, 3P, UL 600, IEC 415, UL Serv Ent, 100%

24. Circuit Breaker or Entrance Box - Bottom Entry, Left Side

25. Circuit Breaker or Entrance Box - Bottom Entry, Right Side

26. Engine Air Cleaner - Normal Duty

27. External Battery Charger - 12 Amp, Regulated

28. Engine Cooling - Radiator, 50C Ambient

29. Shutdown - Low Coolant Level

30. Coolant Heater - 208/240/480 Volts AC, 40F Minimum Ambient Temperature

31. Genset Warranty - 2 Years Base

32. Literature - English

33. Packing - None, Base Mounted Housing

34. Vibration Isolator Restraint, Non-Seismic-3040lbs, 1.00" Deflection, 3366lbs/in Spring Rate

35. Start-up/Commissioning

Attachment 3 - Salient Characteristics

FA460826QC0003

PART 1 – Commercial Diesel Generator Set, 800kW Standby 60Hz