Attachment 5 Water Storage Tank - Pre-proposal questions.pdf
PDF 71 KB Posted
- Attached to
- Ground Water Storage Inspection- Amendment 1 Federal contract opportunity
- Solicitation number
- FA460824QS019
About this file
This document is a set of pre-proposal questions and answers related to the federal contract opportunity for the inspection of a 250,000 gallon above ground water storage tank at Barksdale AFB, Louisiana.
The key details are that the inspection does not require API 653 inspections, as the AWWA and NFPA inspections will be sufficient to meet the requirements. The vendor shall furnish all materials, labor, and equipment necessary to perform a full interior and exterior inspection of the water tank, including the cathodic protection system, floor, roof, welds, seams, foundation, anchors, safety systems, hatches, shell, manway, ladders, roof manway with vent, telemetry nozzle, level indicator system, center column, overflow pipe & flap valve, roof railing, and conduit. The work must adhere to all federal, state, and local codes and standards. The contract opportunity is for the Department of the Air Force Global Strike Command.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment 1 FA460824QS019 Water Storage Tank.pdf | ||
| Attachment 1 Revised SOW- 1143939 Rpr E Side Water Tank FY24_rev 2.pdf | ||
| Attachment 4 Reps and Certs PIID.pdf | ||
| Attachment 2 WDL FA4608QS019.pdf | ||
| Attachment 3 Bid Schedule Water Storage Tank Inspection.pdf | ||
| Attachment 1 Water Storage Tank -SOW- 1143939 Rpr E Side Water Tank.pdf | ||
| 24QS019 Combined Synopsis Ground Storage Water Tank.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FA460824QS019 Pre-Proposal Question Attachment 5
1. Is API 653 going to be a requirement to bid? API inspections are not needed for this style of tank.
Even though the tank might have been built to API standards, they don’t necessarily need to be inspection to those. Since the tank holds water and not hazardous substances, API inspection is not required. The AWWA and NFPA inspections will be sufficient to provide you with all of the necessary information and recommendations for your tank needs.
Answer: Concur, the AWWA and NFPA inspections will be sufficient for this project. We can omit the API 653 inspection requirement as long as the other inspection requirements provides all repairs needed for the tank internally and externally.