Attachment 2 - Salient Characteristics.pdf

PDF 365 KB Posted

Attached to
High Voltage Transformers
Solicitation number
FA460824QC115
Issued by

About this file

This document is an attachment titled "Attachment 2 - Salient Characteristics" that describes the technical specifications and requirements for 75 KVA pad mount transformers as part of a federal contract opportunity.

The key details are:

  • The transformers must be three-phase, 75 KVA, with a 12470V delta primary and 208Y/120V wye-n secondary
  • The transformers must have a specific Barksdale Brown color finish, weatherproof and UV resistant epoxy coating, liquid-filled pad mounted design, loop feed, step-down operation, and several other salient technical characteristics
  • This is part of a federal contract opportunity with Solicitation Number FA460824QC115 for "High Voltage Transformers" issued by the Department of the Air Force Global Strike Command
  • The solicitation is a total small business set-aside with a due date for quotes of 2:00 PM CDT on Monday, August 12, 2024
  • The contract is for 11 transformers and other peripherals for the 2nd Civil Engineering Squadron at Barksdale Air Force Base in Louisiana

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment 1 – Salient Characteristics

75 KVA Pad Mount Transformer

The specified unit is required to have several key characteristics in order to meet the designated criteria.

The specified characteristics below collectively contribute to the efficiency and sustainability of the housing electrical system while allowing ease of maintenance and repairability. Itemized list is as follows:

Three Phase Pad mount 75 KVA:

• 12470V Delta Primary

• 208Y/120 Wye-n Secondary

• Finish Color: Barksdale Brown, DTM, Federal Standard # is FS 20117

• Paint Type: Weatherproof and UV Resistant Epoxy Coating and Undercoating

• Liquid Filled Pad Mounted

• Loop Feed

• Step-Down Operation

• Three Phase

• Primary BIL: 95 KV

• Secondary Phasor: Wye-N

• Secondary BIL: 30 KV

• Frequency: 60 Hz

• 5-position Tap Changer

• Tap Changer Switch Rating: 200-Amp, 15 kV

• Primary: Dead Front

• Termination: 200A Load Break Elbows w/ Inserts

• Primary Neutral Connection: N/A

• Primary Surge Arrestors: (3) High Voltage Elbow Surge Arrestors

• Primary Surge Arrestor Voltage Rating: 18 kV Class Elbow Arrestor

• Primary Over Current Protection Method: Fused, Oil-Immersed

• External Drip Shield

• Secondary: Live Front

• Secondary Connections: NEMA Spade Terminals, 4-Hole Spade, Externally Clamped, (4) Double Lug connections

• Secondary Over Current Protection (OCP): N/A

• Secondary Neutral Connection: Secondary X2 Neutral Grounded to Tank

• Secondary Grounding Provisions: (1) NEMA Ground Bar attached to tank via (2) Welded Ground

Bungs in LV Cabinet

• Load Break Switch: 4-Position Load Break Switch

• Load Break Switch Rating: 200-Amp, 15 kV

• Insulation Fluid: Biodegradable Natural Vegetable Oil Ester Insulating Fluid - Non-PCB Fluid

• Sound Level: <=51 dBA

112.5KVA Transformer Salient Characteristics

The specified unit is required to have several key characteristics to meet the designated criteria. The specified characteristics below collectively contribute to the efficiency and sustainability of the housing electrical system while promoting ease of maintenance and repairability. Itemized list is as follows:

Three Phase Pad mount 112.5 KVA:

- 65 Degree C Rise, 60 Hertz

- HV: 12470 Delta (95 KV)

- Loop Feed

- LV: 208Y/120 (30 KV)

- Taps: 2 @ 2.5% Above & Below Normal

- Liquid Level Gauge; Vacuum/Pressure Gauge; Temperature

- Gauge

- Bayonet Fusing

- Non-PCB Mineral Oil (ONAN)

- (6)Dead Front Wells & 15 kV Inserts

- (4)4 Hole Spades

- 2 Position On/Off Switch o Drain Valve w/ Sampler

300 KVA Pad Mount Transformer

The specified unit is required to have several key characteristics in order to meet the designated criteria.

The specified characteristics below collectively contribute to the efficiency and sustainability of the housing electrical system while allowing ease of maintenance and repairability. Itemized list is as follows:

Three Phase Pad mount 300 KVA:

• 208Y/120 Wye-n Secondary

• Finish Color: Barksdale Brown, DTM, Federal Standard # is FS 20117

• Paint Type: Weatherproof and UV Resistant Epoxy Coating and Undercoating

• Liquid Filled Pad Mounted

• Loop Feed

• Step-Down Operation

• Three Phase

• Primary BIL: 95 KV

• Secondary Phasor: Wye-N

• Secondary BIL: 30 KV

• Frequency: 60 Hz

• 5-position Tap Changer

• Tap Changer Switch Rating: 200-Amp, 15 kV

• Primary: Dead Front

• Termination: 200A Load Break Elbows w/ Inserts

• Primary Neutral Connection: N/A

• Primary Surge Arrestors: (3) High Voltage Elbow Surge Arrestors

• Primary Surge Arrestor Voltage Rating: 18 kV Class Elbow Arrestor

• Primary Over Current Protection Method: Fused, Oil-Immersed

• External Drip Shield

• Secondary: Live Front

• Secondary Connections: NEMA Spade Terminals, 4-Hole Spade, Externally Clamped, (4) Double Lug connections

• Secondary Over Current Protection (OCP): N/A

• Secondary Neutral Connection: Secondary X2 Neutral Grounded to Tank

• Secondary Grounding Provisions: (1) NEMA Ground Bar attached to tank via (2) Welded Ground

Bungs in LV Cabinet

• Load Break Switch: 4-Position Load Break Switch

• Load Break Switch Rating: 200-Amp, 15 kV

• Sound Level: <=51 dBA

500 kVA 3 Phase Pad Mount Transformer

The specified unit is required to have several key characteristics in order to meet the designated criteria.

The specified characteristics below collectively contribute to the efficiency and sustainability of the housing electrical system while allowing ease of maintenance and repairability. Itemized list is as follows:

Three Phase Pad mount 500 KVA:

• 208Y/120 Wye-N Secondary

• Finish Color: Barksdale Brown, DTM, Federal Standard # is FS 20117

• Paint Type: Weatherproof and UV Resistant Epoxy Coating and Undercoating

• Loop Feed

• Step-Down Operation

• Primary Voltage: 12470V

• Primary Phasor: Delta

• Primary BIL: 95 KV

• Secondary Voltage: 208Y/120

• Secondary Phasor: Wye-N

• Secondary BIL: 30 KV

• Frequency: 60 Hz

• Tap Changer: 5-position Tap Changer

• Tap Changer Switch Rating: 300-Amp, 15 kV

• Primary Connection Type: Dead Front

• Primary Termination: Externally Clamped Integral Bushings w/ Removable Studs, 600A Dead

Break Elbows

• Primary Neutral Connection: N/A

• Primary Surge Arrestors: (3) High Voltage Elbow Surge Arrestors

• Primary Over Current Protection Method: Fused, Oil-Immersed

• External Drip Shield

• Secondary Connection Type: Live Front

• Secondary Connections: NEMA Spade Terminals, 6-Hole Spade, Externally Clamped, Accepts up to (6) Double Lug connections with (3) cables per side of Spade connector

• Secondary Over Current Protection (OCP): N/A

• Secondary Neutral Connection: Secondary X2 Neutral Grounded to Tank

• Secondary Grounding Provisions: (1) NEMA Ground Bar attached to tank via (2) Welded Ground

Bungs in LV Cabinet

• Load Break Switch: 4-Position Load Break Switch

• Load Break Switch Rating: 300-Amp, 15 kV

• Sound Level: <= 56 dBA

750 KVA Pad Mount Transformer

The specified unit is required to have several key characteristics in order to meet the designated criteria.

The specified characteristics below collectively contribute to the efficiency and sustainability of the housing electrical system while allowing ease of maintenance and repairability. Itemized list is as follows:

Three Phase Pad mount 750 KVA:

• 480Y/277 Wye-N

• Finish Color: Barksdale Brown, DTM, Federal Standard # is FS 20117

• Paint Type: Weatherproof and UV Resistant Epoxy Coating and Undercoating

• Transformer Feed Type: Loop Feed

• Operation: Step-Down Operation

• Phase: Three Phase

• Primary Voltage: 12470V

• Primary Voltage Switch: N/A

• Primary Phasor: Delta

• Primary BIL: 95 KV

• Secondary Voltage: 480Y/277

• Secondary Phasor: Wye-N

• Secondary BIL: 30 KV

• Frequency: 60 Hz

• Tap Changer: 5-position Tap Changer

• Tap Changer Switch Rating: 300-Amp, 15 kV

• Primary Connection Type: Dead Front

• Primary Termination: Externally Clamped Integral Bushings w/ Removable Studs, 600A Dead

Break Elbows

• Primary Neutral Connection: N/A

• Primary Surge Arrestors: (3) High Voltage Elbow Surge Arrestors

• Primary Over Current Protection (OCP): Bayonet Expulsion Fuse in series w/ Partial-Range

Current-Limiting Fuse

• Primary Over Current Protection Method: Fused, Oil-Immersed

• External Drip Shield

• Secondary Connection Type: Live Front

• Secondary Connections: NEMA Spade Terminals, 6-Hole Spade, Externally Clamped, Accepts up to (6) Double Lug connections with (3) cables per side of Spade connector

• Secondary Over Current Protection (OCP): N/A

• Secondary Neutral Connection: Secondary X2 Neutral Grounded to Tank

• Load Break Switch: 4-Position Load Break Switch

• Load Break Switch Rating: 300-Amp, 15 kV

Salient Characteristics 75 kVA xfmr.pdf
Salient CHaracteristics 112.5 kVA xfmr.pdf
Salient Characteristics 300 kVA xfmr.pdf
Salient Characteristics 500 kVA xfmr.pdf
Salient Characteristics 750 kVA xfmr.pdf