The transformer must be three-phase, pad-mounted, liquid-filled, with a 12470V delta primary and 208Y/120V wye-n secondary. It shall have a weatherproof and UV-resistant epoxy coating, a 5-position tap changer, primary dead-front termination with 200A load break elbows, and secondary live-front NEMA spade terminals. The insulation fluid must be a biodegradable natural vegetable oil ester. The solicitation is a small business set-aside with a NAICS code of 335311 and 800-employee size standard. Quotes are due by 2:00 PM CDT on August 12, 2024 to the Department of the Air Force Global Strike Command.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FA460824QC115

Attachment 2

Salient Characteristics

75 KVA Pad Mount Transformer

The specified unit is required to have several key characteristics to meet the designated criteria. The specified characteristics below collectively contribute to the efficiency and sustainability of the housing electrical system while allowing ease of maintenance and repairability. Itemized list is as follows:

Three Phase Pad mount 75 KVA:

• 12470V Delta Primary

• 208Y/120 Wye-n Secondary

• Finish Color: Barksdale Brown, DTM, Federal Standard # is FS 20117

• Paint Type: Weatherproof and UV Resistant Epoxy Coating and Undercoating

• Liquid Filled Pad Mounted

• Loop Feed

• Step-Down Operation

• Three Phase

• Primary BIL: 95 KV

• Secondary Phasor: Wye-N

• Secondary BIL: 30 KV

• Frequency: 60 Hz

• 5-position Tap Changer

• Tap Changer Switch Rating: 200-Amp, 15 kV

• Primary: Dead Front

• Termination: 200A Load Break Elbows w/ Inserts

• Primary Neutral Connection: N/A

• Primary Surge Arrestors: (3) High Voltage Elbow Surge Arrestors

• Primary Surge Arrestor Voltage Rating: 18 kV Class Elbow Arrestor

• Primary Over Current Protection Method: Fused, Oil-Immersed

• External Drip Shield

• Secondary: Live Front

• Secondary Connections: NEMA Spade Terminals, 4-Hole Spade, Externally Clamped, (4) Double Lug connections

• Secondary Over Current Protection (OCP): N/A

• Secondary Neutral Connection: Secondary X2 Neutral Grounded to Tank

• Secondary Grounding Provisions: (1) NEMA Ground Bar attached to tank via (2) Welded Ground

Bungs in LV Cabinet

• Load Break Switch: 4-Position Load Break Switch

• Load Break Switch Rating: 200-Amp, 15 kV

• Insulation Fluid: Biodegradable Natural Vegetable Oil Ester Insulating Fluid - Non-PCB Fluid

• Sound Level: <=51 dBA

300 KVA Pad Mount Transformer

The specified unit is required to have several key characteristics to meet the designated criteria. The specified characteristics below collectively contribute to the efficiency and sustainability of the housing electrical

Three Phase Pad mount 300 KVA:

• 208Y/120 Wye-n Secondary

• Finish Color: Barksdale Brown, DTM, Federal Standard # is FS 20117

• Paint Type: Weatherproof and UV Resistant Epoxy Coating and Undercoating

• Liquid Filled Pad Mounted

• Loop Feed

• Step-Down Operation

• Three Phase

• Primary BIL: 95 KV

• Secondary Phasor: Wye-N

• Secondary BIL: 30 KV

• Frequency: 60 Hz

• 5-position Tap Changer

• Tap Changer Switch Rating: 200-Amp, 15 kV

• Primary: Dead Front

• Termination: 200A Load Break Elbows w/ Inserts

• Primary Neutral Connection: N/A

• Primary Surge Arrestors: (3) High Voltage Elbow Surge Arrestors

• Primary Surge Arrestor Voltage Rating: 18 kV Class Elbow Arrestor

• Primary Over Current Protection Method: Fused, Oil-Immersed

• External Drip Shield

• Secondary: Live Front

• Secondary Connections: NEMA Spade Terminals, 4-Hole Spade, Externally Clamped, (4) Double Lug connections

• Secondary Over Current Protection (OCP): N/A

• Secondary Neutral Connection: Secondary X2 Neutral Grounded to Tank

• Secondary Grounding Provisions: (1) NEMA Ground Bar attached to tank via (2) Welded Ground

Bungs in LV Cabinet

• Load Break Switch: 4-Position Load Break Switch

• Load Break Switch Rating: 200-Amp, 15 kV

• Sound Level: <=51 dBA

500 kVA 3 Phase Pad Mount Transformer

The specified unit is required to have several key characteristics to meet the designated criteria. The specified characteristics below collectively contribute to the efficiency and sustainability of the housing electrical

Three Phase Pad mount 500 KVA:

• 208Y/120 Wye-N Secondary

• Finish Color: Barksdale Brown, DTM, Federal Standard # is FS 20117

• Paint Type: Weatherproof and UV Resistant Epoxy Coating and Undercoating

• Loop Feed

• Step-Down Operation

• Primary Voltage: 12470V

• Primary Phasor: Delta

• Primary BIL: 95 KV

• Secondary Voltage: 208Y/120

• Secondary Phasor: Wye-N

• Secondary BIL: 30 KV

• Frequency: 60 Hz

• Tap Changer: 5-position Tap Changer

• Tap Changer Switch Rating: 300-Amp, 15 kV

• Primary Connection Type: Dead Front

• Primary Termination: Externally Clamped Integral Bushings w/ Removable Studs, 600A Dead Break

Elbows

• Primary Neutral Connection: N/A

• Primary Surge Arrestors: (3) High Voltage Elbow Surge Arrestors

• Primary Over Current Protection Method: Fused, Oil-Immersed

• External Drip Shield

• Secondary Connection Type: Live Front

• Secondary Connections: NEMA Spade Terminals, 6-Hole Spade, Externally Clamped, Accepts up to

(6) Double Lug connections with (3) cables per side of Spade connector

• Secondary Over Current Protection (OCP): N/A

• Secondary Neutral Connection: Secondary X2 Neutral Grounded to Tank

• Secondary Grounding Provisions: (1) NEMA Ground Bar attached to tank via (2) Welded Ground

Bungs in LV Cabinet

• Load Break Switch: 4-Position Load Break Switch

• Load Break Switch Rating: 300-Amp, 15 kV

• Sound Level: <= 56 dBA

750 KVA Pad Mount Transformer

The specified unit is required to have several key characteristics to meet the designated criteria. The specified characteristics below collectively contribute to the efficiency and sustainability of the housing electrical

Three Phase Pad mount 750 KVA:

• 480Y/277 Wye-N

• Finish Color: Barksdale Brown, DTM, Federal Standard # is FS 20117

• Paint Type: Weatherproof and UV Resistant Epoxy Coating and Undercoating

• Transformer Feed Type: Loop Feed

• Operation: Step-Down Operation

• Phase: Three Phase

• Primary Voltage: 12470V

• Primary Voltage Switch: N/A

• Primary Phasor: Delta

• Primary BIL: 95 KV

• Secondary Voltage: 480Y/277

• Secondary Phasor: Wye-N

• Secondary BIL: 30 KV

• Frequency: 60 Hz

• Tap Changer: 5-position Tap Changer

• Tap Changer Switch Rating: 300-Amp, 15 kV

• Primary Connection Type: Dead Front

• Primary Termination: Externally Clamped Integral Bushings w/ Removable Studs, 600A Dead Break

Elbows

• Primary Neutral Connection: N/A

• Primary Surge Arrestors: (3) High Voltage Elbow Surge Arrestors

• Primary Over Current Protection (OCP): Bayonet Expulsion Fuse in series w/ Partial-Range Current-

Limiting Fuse

• Primary Over Current Protection Method: Fused, Oil-Immersed

• External Drip Shield

• Secondary Connection Type: Live Front

• Secondary Connections: NEMA Spade Terminals, 6-Hole Spade, Externally Clamped, Accepts up to

(6) Double Lug connections with (3) cables per side of Spade connector

• Secondary Over Current Protection (OCP): N/A

• Secondary Neutral Connection: Secondary X2 Neutral Grounded to Tank

• Load Break Switch: 4-Position Load Break Switch

• Load Break Switch Rating: 300-Amp, 15 kV

500 kVA 3 Phase Pad Mount Transformer
750 KVA Pad Mount Transformer