Medium Voltage Circuit Summery – Three Phase Faults

Short circuit analysis summary

Feeder 10:

Bus Kv = 12.47kV

Symmetrical fault current = 7736.9

X/R Ratio = 13.07

Multiplication factor = 1.50

Asymmetrical fault current = 11605.7