CLARIFICATIONS

As of 12 Feb 2015

FA4608-15-R-0006 AWUB 07-0110

Repair Electrical Equipment with Pad Mounted on Davis Rd

1) A more specific, unrelated question that was raised by the equipment suppliers. The equipment suppliers stated that no one can provide a UL listed NEMA 12 switchboard that is specified in the solicitation documents. NEMA 12 is considered dustproof; and, the manufacturers are saying that the switchboard must have air flow to keep it from overheating. Please advise if there is alternate equipment that can be used. If so, please provide a specification.

NEMA 1 will be fine for the indoor MDP switchboard.