final 26 28 13 Fuses.pdf

PDF 47 KB Posted

Attached to
Saber Pre-solicitation notice Federal contract opportunity
Solicitation number
FA4600-10-R-0006
Issued by
Department of the Air Force Air Combat Command

About this file

-

View the file

Other files for this federal contract opportunity

Other files attached to Saber Pre-solicitation notice, newest first.
File Type Posted
SIGN IN SHEET Oct 15 2010.doc DOC document
Seed project Honor guard room.pdf PDF
Amendment6.doc DOC document
Attachment 3 Seed SOO Rpr AHU's O-Club B462 28 Sept 2010.doc DOC document
Question and Answers 28 Sep 2010.docx DOCX document
Amendment5.doc DOC document
Question and Answers 24 Sep 2010.docx DOCX document
Sheet 09.dwf DWF file
Sheet 17.dwf DWF file
Sheet 15.dwf DWF file
Sheet 05.dwf DWF file
Sheet 08.dwf DWF file
Sheet 16.dwf DWF file
Sheet 10.dwf DWF file
Sheet 13.dwf DWF file
amendment4.doc DOC document
Attachment 3 Rpr AHU's O-Club B462 Sept 2010.doc DOC document
Question and Answers.docx DOCX document
Final 23 05 00 Basic HVAC Materials and Methods.pdf PDF
Sheet 9-9.pdf PDF
Sheet 5-Sheet 5.pdf PDF
Sheet 12-12.pdf PDF
Section 1B AF66 Master Oct 2008.xls XLS spreadsheet
Sheet 16-16.pdf PDF
Sheet 11-11.pdf PDF
Section 1C Master Copy June 2008.pdf PDF
Final 07 53 00 Elastomeric Membrane Roofing.pdf PDF
final 23 05 93 Testing Adjusting and Balancing.pdf PDF
Sheet 10-10.pdf PDF
Performance Period.pdf PDF
final 26 05 33 Raceways.pdf PDF
final 26 05 19 Wires and Cables.pdf PDF
Sheet 2-02.pdf PDF
Final 09 91 00 Painting.pdf PDF
Sheet 3-Sheet 3.pdf PDF
final 07 92 00 Joint Sealers.pdf PDF
Final 05 50 00 Metal Fabrications.pdf PDF
Sheet 11-11.pdf PDF
final 26 05 53 Electrical Identification.pdf PDF
Final 23 38 13 Kitchen Ventilator Hood Systems.pdf PDF
final 23 07 00 HVAC Insulation.pdf PDF
final 23 00 00 General Provisions.pdf PDF
Ntitle.dwg DWG drawing
Rpr Wing XP.dwg DWG drawing
SITE PLAN.dwg DWG drawing
Site Visit Sign In Sheet.pdf PDF
Attachment 5.docx DOCX document
Attachment 2.docx DOCX document
Preconstruction Conference Attachment 4.doc DOC document
Attachment 1.docx DOCX document
Show all 50

Saber Pre-solicitation notice has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OFFUTT AIR FORCE BASE

(092036) 26 26 13-1 (Repair AHU O-Club, B462)

2010 by FEI

SECTION 26 28 13

FUSES

PART 1 - GENERAL

1.1 SUMMARY

A. Extent of fuse work is indicated by drawings and schedules.

B. Types of fuses specified in this section include the following:

1. Class RK1 time-delay.

PART 2 - PRODUCTS

2.1 ACCEPTABLE MANUFACTURERS

A. Manufacturer: Subject to compliance with requirements, provide products of one (1) of the following:

1. Bussman Div; McGraw-Edison Co.

2. Littelfuse Co.

3. Gould Shawmut.

B. Fuse types listed below are for Bussman Co. Fuses by Littelfuse Co. or Gould Shawmut shall be equivalent to types indicated.

2.2 FUSES

A. General: Except as otherwise indicated, provide fuses of types, sizes, ratings, and average time/current and peak let-through current characteristics indicated, which comply with manufacturer's standard design, materials and construction in accordance with published product information, and with industry standards and configurations.

B. Class RK1 Time-Delay Fuses: Provide UL Class RK1 time-delay fuses rated 250V (Type LPN-RK) for voltages under 250V and 600V (Type LPS-RK) for voltages 250-600V, 60 Hz, with 200,000 RMS symmetrical interrupting current rating.

PART 3 - EXECUTION

3.1 INSTALLATION OF FUSES

A. Install fuses as indicated, in accordance with the manufacturer's written instructions and with recognized industry practices to ensure that protective devices comply with requirements. Comply with

NEC and NEMA Standards for installation of fuses.

B. Coordinate with other work, including electrical wiring work, as necessary to interface installation of fuses with other work.

C. Install fuses in fused switches.

D. Short-circuit protection dual-element fuses installed in individual motor circuits with separate overload protection shall be sized at 175% of motor nameplate current rating or the next standard

OFFUTT AIR FORCE BASE

(092036) 26 26 13-2 (Repair AHU O-Club, B462)

2010 by FEI fuse size. Where excessive ambient temperature, high inertia motor loads or frequent "on-off" cycling requires larger fuses, consult the electrical engineer. Use fuse reducers where fuse gaps are larger than fuse dimension.

E. All fuse sizes shall be coordinated with manufacturer's requirements for each unit of equipment to be connected.

3.2 FIELD QUALITY CONTROL

A. Prior to energization of fusible devices, test devices for continuity of circuitry and for short-circuits.

Correct malfunctioning units and then demonstrate compliance with requirements.

END OF SECTION