CNS Questions2.pdf
PDF 124 KB Posted
- Attached to
- CNS Restroom Federal contract opportunity
- Solicitation number
- FA4600-10-B-0009
About this file
Answers to questions that were received AFTER 20 Aug deadline.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Bidder Abstract.pdf | ||
| Hour ext.pdf | ||
| CNS Questions.pdf | ||
| Deadline Amendment.doc | DOC document | |
| NCIC Data attachment.docx | DOCX document | |
| Sht04.dwf | DWF file | |
| Sht08.dwf | DWF file | |
| Sht03.dwf | DWF file | |
| Sht02.dwf | DWF file | |
| CNS Restroom Specs.pdf | ||
| Sht06.dwf | DWF file | |
| Sht10.dwf | DWF file | |
| 10B0009 CNS Sol.doc | DOC document | |
| Sht09.dwf | DWF file | |
| NE100010.docx | DOCX document | |
| Sht07.dwf | DWF file | |
| Sht01.dwf | DWF file | |
| Bidder Checklist Attch.doc | DOC document | |
| Sht05.dwf | DWF file | |
| Pre-Solicitation Notice CNS Restrooms.doc | DOC document |
Show all 20
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FA4600-10-B-0009
Last Minute Questions
1. The drawings say to connect the 120v side of the fire damper to an existing fire damper circuit. Where is the closest fire damper circuit?
THE DRAWINGS INDICATE FOR THE CONTRACTOR TO VERIFY THE LOCATION OF THE
CLOSEST CIRCUIT.
2. The drawings also say that the fire damper and air handling equipment associated with the fire damper equipment must be shut down. What air handler is this and where is it located?
SHUTDOWN OF UNIT IS NOT REQUIRED AS PART OF THE SCOPE OF THIS PROJECT. THE
DAMPER SHALL CLOSE UPON DETECTION OF SMOKE IN THE CORRIDOR.
MODIFICATIONS TO ANY AIR HANDLING UNITS ARE OUTSIDE OF THE SCOPE OF THIS
PROJECT.
3. Does the exhaust fan for the bathroom also have to be shut down?
OUR UNDERSTANDING IS THE EXHAUST FAN DOES NOT NEED TO BE SHUT DOWN.