CNS Questions2.pdf

PDF 124 KB Posted

Attached to
CNS Restroom Federal contract opportunity
Solicitation number
FA4600-10-B-0009
Issued by
Department of the Air Force Air Combat Command

About this file

Answers to questions that were received AFTER 20 Aug deadline.

View the file

Other files for this federal contract opportunity

Other files attached to CNS Restroom, newest first.
File Type Posted
Bidder Abstract.pdf PDF
Hour ext.pdf PDF
CNS Questions.pdf PDF
Deadline Amendment.doc DOC document
NCIC Data attachment.docx DOCX document
Sht04.dwf DWF file
Sht08.dwf DWF file
Sht03.dwf DWF file
Sht02.dwf DWF file
CNS Restroom Specs.pdf PDF
Sht06.dwf DWF file
Sht10.dwf DWF file
10B0009 CNS Sol.doc DOC document
Sht09.dwf DWF file
NE100010.docx DOCX document
Sht07.dwf DWF file
Sht01.dwf DWF file
Bidder Checklist Attch.doc DOC document
Sht05.dwf DWF file
Pre-Solicitation Notice CNS Restrooms.doc DOC document
Show all 20

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FA4600-10-B-0009

Last Minute Questions

1. The drawings say to connect the 120v side of the fire damper to an existing fire damper circuit. Where is the closest fire damper circuit?

THE DRAWINGS INDICATE FOR THE CONTRACTOR TO VERIFY THE LOCATION OF THE

CLOSEST CIRCUIT.

2. The drawings also say that the fire damper and air handling equipment associated with the fire damper equipment must be shut down. What air handler is this and where is it located?

SHUTDOWN OF UNIT IS NOT REQUIRED AS PART OF THE SCOPE OF THIS PROJECT. THE

DAMPER SHALL CLOSE UPON DETECTION OF SMOKE IN THE CORRIDOR.

MODIFICATIONS TO ANY AIR HANDLING UNITS ARE OUTSIDE OF THE SCOPE OF THIS

PROJECT.

3. Does the exhaust fan for the bathroom also have to be shut down?

OUR UNDERSTANDING IS THE EXHAUST FAN DOES NOT NEED TO BE SHUT DOWN.