Sump Pump Q and A_1.pdf

PDF 108 KB Posted

Attached to
Sump Pump 104 Federal contract opportunity
Solicitation number
FA452820R0005
Issued by
Department of the Air Force Global Strike Command

View the file

Other files for this federal contract opportunity

Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. Drawing 4 Plan B-B States:

Install 4” bronze or stainless steel flanges on connection to pump with stainless steel bolts, nuts and washers (Type

2) Please clarify: The transition from Sch 80 PVC pipe to the flange should be PVC glue flange, from pipe to the flange off the pump.

Answer: The flange can also be PVS slip flange glued to Schedule 80 PVC pipe (see below). Hardware needs to remain stainless steel.

2. Drawing 5 Note 6 states:

Includes Meyers lift out rail assemblies Part No SRA for Gould’s Motor & Pump. Gould’s manufactures their own lift out rail assemblies, Meyer’s rail lift out assemblies are manufactured for the Meyers Sump Pumps. Rail lift out assemblies are specific to ea. individual pump manufacture. Please clarify.

Answer: The lift out rail assemblies DO NOT need to be Meyers lift out rail assembly Part No SRA. They can be any lift out rail assembly that fits with the required Gould’s Motor & Pump (see below).