Specification_Questions_1_August_2014.pdf

PDF 40 KB Posted

Attached to
Renovate and Repair Building 1113 WSA
Solicitation number
FA4528-14-R-0007
Issued by

About this file

Specification Questions 1 August 2014

View the file

Other files

File Type Posted
Revised_Specifications_29_July_2014.pdf PDF
Amendment_2.pdf PDF
Revised_Drawings_25_July_2014.pdf PDF
Questions_and_Answers_29_July_2014.pdf PDF
Pictures_3.zip ZIP file
Pictures_7.zip ZIP file
Pictures_6.zip ZIP file
Pictures_2.zip ZIP file
Pictures_1.zip ZIP file
Pictures_5.zip ZIP file
Pictures_8.zip ZIP file
Pictures_4.zip ZIP file
Amendment_1.pdf PDF
Attachment_4_Past_Performance_Information_Form.docx DOCX document
Attachment_2_Drawings.pdf PDF
Attachment_3_WD.pdf PDF
Attachment_1_Specs.pdf PDF
FA4528-14-R-0007_Final.pdf PDF
Attachment_5_Financial_Responsibility.docx DOCX document
Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1 August 2014 Specification Questions

Question:

What are the actual standoff-distances the building needs to be designed for? In the Q&A (item 19) a minimum standoff of 13ft is given, but not the actual standoff distance. The actual standoff distances are needed to design the translucent panel systems around it

Answer:

Standoff - The stand-off distance is the perimeter fence of the WSA, any vehicles within this fence line have been searched for explosives. In this case, the nearest perimeter fence is approximately 120-feet to the southwest, which is a substantial standoff distance.

Question:

Amendment 2 addresses the concerns regarding pipe and fitting for hydraulics. However, Amendment 2 specifically addresses requirements for 1/2” and 3/4” piping, yet plan shows 3/4”, 1” and 1-1/2” hydraulic piping. Please clarify

Answer:

Piping - On the hydraulic piping we need to provide a 316/316L stainless steel ASTM A269 seamless tubing. The ¾-inch tubing shall have a wall thickness of 0.083 inches (4,200 psig working pressure). The 1-inch tubing shall have a wall thickness of 0.095 inches (3,600 psig working pressure). The 1-1/2-inch tubing shall have a wall thickness of 0.156 inches (4,000 psig working pressure). The ¾-inch tubing shall be provided with 1210 fitting series, all as manufactured by Swagelok or equal. The 1-inch tubing shall be provided with 1610 series fittings. The 1-1/2-inch tubing shall be provided with 2400 series fittings.

The fittings shall be designed with two-ferrule, mechanical grip type of compression fitting as manufactured by Swagelok or equal. Any valves required shall be constructed of stainless steel and suitable for Alternative Fuel Service with the fractional Swagelok tube fittings or equal.