Revised_Specifications_29_July_2014.pdf
PDF 63 KB Posted
- Attached to
- Renovate and Repair Building 1113 WSA
- Solicitation number
- FA4528-14-R-0007
About this file
Revised Specifications 29 July 2014
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Specification_Questions_1_August_2014.pdf | ||
| Amendment_2.pdf | ||
| Revised_Drawings_25_July_2014.pdf | ||
| Questions_and_Answers_29_July_2014.pdf | ||
| Pictures_3.zip | ZIP file | |
| Pictures_7.zip | ZIP file | |
| Pictures_6.zip | ZIP file | |
| Pictures_2.zip | ZIP file | |
| Pictures_1.zip | ZIP file | |
| Pictures_5.zip | ZIP file | |
| Pictures_8.zip | ZIP file | |
| Pictures_4.zip | ZIP file | |
| Amendment_1.pdf | ||
| Attachment_4_Past_Performance_Information_Form.docx | DOCX document | |
| Attachment_2_Drawings.pdf | ||
| Attachment_3_WD.pdf | ||
| Attachment_1_Specs.pdf | ||
| FA4528-14-R-0007_Final.pdf | ||
| Attachment_5_Financial_Responsibility.docx | DOCX document |
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPECIFICATIONS AND DRAWINGS REVISIONS AND ERRATA SHEET
QJVF12-0093, Repair ALCM Mx Training Facility, B1113
29 July 2014
Specifications
1. Section 07 42 13, Paragraph 1.5.4 --- Delete this paragraph.
2. Section 09 06 90, Paragraph 2.3.1.4 --- Change PT-1 Size from 18” x 18” to 24” x 12”. Change PT-2
Pattern from “Color Blox Tee” to “Color Blox”, Color from “Gray Matter A1126” to “Night Night A1119” and Size from 6” x 6” to 6” x 12”.
3. Section 09 06 90, Paragraph 2.3.2.2 --- Change “PT-4” to “PT-1” and Color from “Slinky 1103” to “Sea
Otter A1108”.
4. Section 09 06 90, Paragraph 2.3.2.3 --- Change “G-2” to “G-1” and Color from “Pewter 02” to
“Charcoal 47”.
5. Section 09 06 90, Paragraph 2.3.3.2 --- Change PT-4 Size from 6” x 6” to 24” x 12”.
6. Section 21 13 18.00 10 --- Add following paragraph to this section:
“1.2.5 Recessed Sprinklers
For clarification, the term “recessed” when used in reference to sprinklers throughout the fire sprinkler portion of the contract documents implies a “semi-recessed” sprinkler. Concealed style sprinklers are not specified for this project.”
Drawings
7. Sheets A-001, Removal Plan; A-002, Removal Elevations; A-101, Floor Plans; A-201, Exterior
Elevations; A-305, Wall Sections; A-501, Sections and Details; A-601, Room Finish Schedule; I-101, Finish Plan and MD101, HVAC Demolition Plan --- Replace these nine drawing sheets dated 15 April 2014 with drawing sheets dated 25 July 2014.
8. Sheet A-101, Floor Plans --- Revise detail reference 1/A-304 to reference detail 2/A-305 and revise detail reference 2/A-305 to reference detail 1/A-304 on the Floor Plan.
9. Sheet P-502, Hydraulic Piping Riser --- Add the following note to the drawing:
"HYDRAULIC PIPING
Provide a 316/316L stainless steel ASTM A269 seamless tubing. The ½-inch tubing shall have a tube wall thickness of .049 inches (3,700 psig working pressure) and the ¾-inch tubing shall have a wall thickness of .083 inches (4,200 psig working pressure). The ½-inch tubing shall be provided with an 810 fitting series and the ¾-inch tubing shall be provided with a 1210 fitting series all as manufactured by Swagelok or equal. The fittings shall be designed with two-ferrule, mechanical grip type of compression fitting as manufactured by Swagelok or equal. Any valves required shall be
QJVF12-0093 Specifications and Drawings Revisions and Errata Sheet 29 July 2014 Repair ALCM Mx Training Facility, B1113 constructed of stainless steel and suitable for Alternative Fuel Service with the fractional Swagelok tube fittings or equal."