Questions and Answers for Hangar Doors Bldg. 714
1) What is the existing supply voltage for the trolley duct system?
a. 240/416 VAC
2) Does the current system have 4 or 7 conductors?
a. 3
3) What amp rating are you requiring the trolley duct to be?
a. Existing is 200 Amp
4) Would you accept another trolley duct mfg if shown to be a betterment?
a. Yes
5) New trolley duct systems typically use dual trolleys to ensure consistent supply voltage to the drive door. Are 2 trolley collectors required for door #7 and door #8?
a. 2 are required