This document is a Limited Asbestos Inspection Report for Building 335 at the Little Rock Air Force Base in Jacksonville, Arkansas. The report was prepared by Safety & Environmental Investigations, Inc. for HGL Construction, Inc. in December 2018. It summarizes the findings of a pre-renovation inspection of the ceilings and HVAC system in the building. Samples were collected and analyzed, and the results indicate no asbestos-containing materials were detected. As a result, the report states that planned renovations to the HVAC system may proceed without regard to asbestos. The report includes details on the sampling methodology, laboratory analysis, and limitations of the inspection.

The related federal contract opportunity is for the removal, furnishing, and installation of a new fire alarm and mass notification system in Building 335 at the Little Rock Air Force Base. The solicitation number is FA446024Q0268, and the Department of the Air Force Air Mobility Command is the procuring agency. The contractor is required to provide all necessary personnel, equipment, materials, and services to complete the work within 180 days of award, in compliance with relevant regulations and codes.

View the file

Other files

File Type Posted
Combo Updated.pdf PDF
Performance Work Statement Revised.pdf PDF
Combo Updated.pdf PDF
Appendixes.pdf PDF
Questions and Answers.pdf PDF
Updated Combo.pdf PDF
PWS Updated.pdf PDF
Combo Updated.pdf PDF
Provision and Clauses.pdf PDF
Combo.pdf PDF
B335 Monaco BN Justification -_Redacted.pdf PDF
Addendum 52.212-1 & 52.212-2.pdf PDF
PWS FIRE Updated.pdf PDF
Wage Determination.pdf PDF
Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P.O. Box 22038, Little Rock, Arkansas 72221 Phone (501) 227-8900 FAX: (501) 227-7535

Safety & Environmental

Investigations, Inc.

LIMITED ASBESTOS INSPECTION REPORT

Building 335 HVAC / Ceilings

Little Rock Air Force Base Jacksonville, Arkansas 72078

December 2018

LIMITED ASBESTOS INSPECTION REPORT

December 2018

Prepared For: Chris Shawver HGL Construction, Inc.

PO Box 135

Prepared By: Safety & Environmental Investigations, Inc.

PO Box 22038 Little Rock, Arkansas 72221

Building 335 HVAC / Ceilings SEI Job # 18124 Page 3

Jacksonville, Arkansas

Limited Asbestos Inspection Report

Safety & Environmental Investigations, (SEI) Inc. was retained by HGL Construction, Inc. to perform a Limited pre-renovation asbestos inspection of the ceilings and HVAC System of Building 335 located at the Little Rock Air Force Base, Jacksonville, Arkansas. On November 29th, 2018, Mr. Joshua Roberson (Certification #015183) of SEI, Inc. (License #000260) performed the on-site inspection and sampling of the structure for the presence of suspect asbestos-containing materials. The inspection was performed following EPA AHERA guidelines (40 CFR 763) and NESHAP (40 CFR 61, Subpart M) and the Arkansas Department of Environmental Quality, Regulation 21.

Background

Building 335 is a single-story, brick structure with a pitched, shingled roof on a concrete slab foundation. The interior of the structure consisted of lay-in ceiling tiles, sheet rock walls and ceilings with carpet, tile and concrete flooring. The structure was occupied and in good condition at the time of the inspection. The date of construction was unknown and according to the client, the structure is scheduled for future renovations to the ceiling and HVAC system.

Purpose of Study

The purpose of this study was to identify and collect samples of suspect asbestos-containing materials from the structure for laboratory analysis. At the client’s request, an inspection for the presence of suspect asbestos-containing materials was performed of the identified areas of the structure. Identified asbestos-containing materials have been quantified.

Sampling was performed in accordance with guidelines published in the Asbestos Hazard Emergency Response Act (AHERA), 40 CFR Part 763. Suspect asbestos-containing materials were divided into three different categories: surfacing, thermal system insulation, and miscellaneous materials. Each category of materials was divided into homogeneous areas, which are defined as materials similar in appearance, color, texture, and installation date. Samples were collected from each homogeneous area according to the following scale:

Surfacing Materials: <1000 sq. ft. 3 Samples 1,000 – 5,000 sq. ft. 5 Samples >5,000 sq. ft. 7 Samples Thermal System Insulation any amount 3 Samples Minimum Miscellaneous Materials any amount 2 Samples Minimum

Building 335 HVAC / Ceilings SEI Job # 18124 Page 4

The Environmental Protection Agency defines an asbestos-containing material as any material which contains greater than one percent (1%) asbestos by weight. The entire homogeneous area is classified as asbestos-containing if any one (1) of the samples collected from that area is found to contain more than 1% asbestos. All samples collected from a homogeneous material must reveal a result of one (1) percent asbestos or less for a material to be considered non-asbestos containing.

The condition of suspect homogeneous areas was assessed to determine if the materials were friable (RACM) or non-friable. Friable materials (RACM) are materials that when dry can be crumbled, pulverized, or reduced to powder by hand pressure. Non-Friable materials are materials that cannot be crumbled, pulverized, or reduced to powder by hand pressure when dry. Non-Friable materials are divided into two categories, Category I Non-Friable materials, (asbestos-containing packing, gaskets, resilient floor coverings, and asphalt roofing products that contain >1% asbestos), and Category II Non-Friable materials (any material, excluding category I non-friable ACM, containing >1% asbestos that cannot be crumbled, pulverized, or reduced to powder by hand pressure).

Asbestos samples were analyzed via Polarized Light Microscopy utilizing EPA Method 600/R-93/116 by BH&M Environmental Consultants, Inc. Millington, Tennessee.

BH&M is accredited by the National Voluntary Laboratory Accreditation Program for Bulk Asbestos Analysis (NVLAP Air and Bulk #201018-0). It should be noted EPA NESHAPS recommends point-counting of positive asbestos results revealing less than 10% asbestos content by visual estimation.

Findings

The following table provides a summary of the suspect materials sampled from the structure, along with the analytical results and locations of the materials.

Building 335 HVAC / Ceilings SEI Job # 18124 Page 5 Little Rock Air Force Base Jacksonville, Arkansas

Table I – Asbestos Sample Summary Building 335

Little Rock Air Force Base

HA#

Sample

No.

Description

Analysis Result %/Type ACM

Sample Location

CT01

01 2x2 Pitted Lay-in Ceiling Tiles None Detected

Electrical Room

02 2x2 Pitted Lay-in Ceiling Tiles None Detected Electrical

Room

AC01

03 Acoustic Spray-on Ceiling None Detected Mechanical

Room

04 Acoustic Spray-on Ceiling None Detected Mechanical

Room

05 Acoustic Spray-on Ceiling None Detected Mechanical

Room

SR01

06 Sheet Rock and Mud Ceilings None Detected

Electrical Room

07 Sheet Rock and Mud Ceilings None Detected Electrical

Room

CT02

08 2x4 Grooved Lay-in Ceiling Tiles None Detected Office Area

09 2x4 Grooved Lay-in Ceiling Tiles None Detected Hall @

Restroom

Safety & Environmental Investigations, Inc. has received the analytical results from the samples collected from Building 335 located at the Little Rock Air Force Base in Jacksonville, Arkansas. The analysis revealed No Asbestos Detected in the samples collected. Planned renovations to the HVAC system may proceed without regard to asbestos-containing materials.

Discussion

A 10-Day Notice of Intent (NOI) is also required to be filed with the Arkansas Department of Environmental Quality (ADEQ) for any demolition or the removal of RACM exceeding 160 square or 260 linear feet.

Sample locations and the location of identified asbestos materials are identified on drawings included in the appendices of this report.

Other materials identified on-site but deemed not-suspect includes the following:

fiberglass batt insulation, fiberglass duct insulation and rubber pipe insulation.

Limitations

This report relates to the ceiling and HVAC materials of Building 335 located at the Little Rock Air Force Base in Jacksonville, Arkansas. No other materials were noted or sampled during this investigation. According to the client, the structure is scheduled for future renovations to the HVAC system.

Building 335 HVAC / Ceilings SEI Job # 18124 Page 6

Asbestos samples were collected from materials identified as Homogeneous Materials based upon visual inspection of the site. SEI, Inc. is not responsible for assumptions on homogeneity which prove to be incorrect. In addition, samples collected represent only that portion of the entire homogeneous material. SEI, Inc. is not responsible for materials not identified and sampled due to the restraints on accessibility of the material. No warranties, expressed or implied, relate to the previous and/or future conditions.

During any operations involving renovation or demolition, suspect asbestos materials may be encountered which were not identified in this inspection. Work should immediately cease, and a certified inspector contacted for further sampling to identify those additional materials.

Asbestos Analysis was performed by BH&M Environmental Consultants, Inc.

Millington. Tennessee. BH&M is solely responsible for all asbestos analytical results contained in and referred to in this report.

This report prepared by:

Joshua A. Roberson Field Services Manager Safety & Environmental Investigations, Inc.

APPENDICIES

FIELD LOGS

LABORATORY ANALYSIS RESULTS

PHOTOGRAPHS

Above Ceiling Tile

Above Sheetrock Ceiling