TRAVIS BLDG 924 FA-FA101 RECORD .pdf

PDF 823 KB Posted

Attached to
DOH Office Electrical Work Travis AFB
Solicitation number
FA442726Q1114
Issued by

About this file

This is a fire alarm system design and installation specification document for Building 924, Room 105 TI at Travis Air Force Base, California. The scope of work involves relocating one speaker strobe and adding one speaker strobe with associated circuits to accommodate Room 105 TI within the existing fire alarm infrastructure.

The contractor, HCI Systems Inc., must comply with comprehensive technical and regulatory requirements including the National Electrical Code Article 760, NFPA 72 (2013 Edition), California Fire Code, California Electrical Code, and California Building Code. All wiring installation must follow NEC Article 760 standards, with conductors installed in conduit and properly labeled. Devices must be approved and listed by the California State Fire Marshal and installed per manufacturer specifications. Key technical requirements include: strobe audibility of not less than 15 dB above ambient sound; wall-mounted strobes positioned between 80 and 96 inches above finished floor; synchronization of multiple strobes in the same field of view; and fire alarm control unit power supplied by a dedicated, locked red circuit breaker labeled "FIRE ALARM." All installation work must be completed in the presence of the fire marshal with satisfactory system testing, and a stamped set of approved fire alarm plans must remain on-site throughout installation. A Record of Completion document must be provided to the client upon final system acceptance and approval per NFPA 72.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SEQUENCE OF OPERATION

GENERAL NOTES

SCOPE OF WORK

VICINITY MAP

FIRE ALARM SYSTEM

BUILDING 924, ROOM 105 TI

TRAVIS AFB

TRAVIS AFB, CA 94525

ALARM SERVICE CONTRACTOR:

UL CERTIFICATE PROVIDER:

1419 NORTH MARKET BLVD.

SACRAMENTO, CALIFORNIA 95834

TEL. (916) 419-6900 FAX (916) 419-6903 S y s t e m s I n c.

FIRE / LIFE SAFETY & LOW VOLTAGE SPECIALISTS

HCIC7, C10, C16 LICENSE #905493

HCI SYSTEMS

SHEET # DWG #

FA1011 SCOPE OF WORK, GENERAL NOTES, SEQUENCE OF OPERATION, AND VICINITY MAP

FA2012 FLOOR PLAN, GENERAL NOTES AND SYMBOL LEGEND

FA3013 RISER DIAGRAM, CABLE SCHEDULE, CALCULATIONS AND FACP ADDRESS MATRIX

FA4014

DESCRIPTION

SHEET INDEX:

1. ALL WIRING SHALL BE INSTALLED IN ACCORDANCE WITH N.E.C. ARTICLE 760, POWER LIMITED FIRE PROTECTIVE

SIGNALING CIRCUITS.

2. UPON COMPLETION OF THE INSTALLATION OF THE FIRE ALARM SYSTEM, A SATISFACTORY TEST OF THE SYSTEM

SHALL BE MADE IN THE PRESENCE OF THE FIRE MARSHAL.

3. A STAMPED SET OF APPROVED FIRE ALARM PLANS SHALL BE ON THE JOB SITE AND USED FOR INSTALLATION. ANY DEVIATION FROM APPROVED PLANS, INCLUDING THE SUBSTITUTION OF DEVICES, SHALL BE APPROVED BY THE FIRE

MARSHAL.

4. ANY DISCREPANCIES BETWEEN THE DRAWINGS AND THE CODE OR RECOGNIZED STANDARDS SHALL BE BROUGHT

TO THE ATTENTION OF THE INSPECTOR OF RECORD.

5. ALL DEVICES OF THE FIRE ALARM SYSTEM SHALL BE APPROVED AND LISTED BY THE CALIFORNIA STATE FIRE

MARSHAL.

6. FIRE ALARM DEVICES SHALL BE INSTALLED PER NFPA. 72.

7. WIRING SHALL NOT BE LOOPED THROUGH DEVICES; WIRE MUST BE CUT AT EACH DEVICE. CIRCUITS SHALL NEVER BE SPLICED. ALL TERMINATIONS SHALL BE AT PANELS, AT TERMINAL CANS ON TERMINAL STRIPS OR AT DEVICES.

8. ALL CONDUCTORS ARE COPPER AND PROPERLY LABELED AT PANELS AND TERMINAL CANS.

9. ALL CIRCUITS SHALL BE PROTECTED IN CONDUIT.

10. ALL DEVICES IN THE ALARM SYSTEM SHALL BE COMPATIBLE AND INSTALLED TO MANUFACTURERS SPECIFICATIONS.

11. AUDIBILITY OF ALARM AND SHALL BE NOT LESS THAN 15 db ABOVE AMBIENT SOUND THROUGHOUT AREA OF

ALARM.

12. AREAS HAVING MORE THAN 2 STROBES IN THE SAME FIELD OF VIEW SHALL BE SYNCHRONIZED TOGETHER.

13. STROBE LOCATION IS BASED ON 20 FOOT CEILING HEIGHT AND ARE INSTALLED ACCORDING TO NFPA 72

REQUIREMENTS UNLESS OTHERWISE NOTED.

14. WALL-MOUNTED STROBES SHALL HAVE THEIR BOTTOMS NOT LESS THAN 80 INCHES ABOVE FINISHED FLOOR AND

NO GREATER THAN 96 INCHES ABOVE FINISHED FLOOR.

15. POWER FOR THE FIRE ALARM CONTROL UNIT IS TO BE PROVIDED BY A DEDICATED CIRCUIT BREAKER. INDICATE LOCATION OF THIS BREAKER AT THE FACU. BREAKER TO BE RED AND LABELED "FIRE ALARM".

16. ELECTRICAL POWER SERVICE SHALL BE ON A DEDICATED CIRCUIT(S). THE CIRCUIT(S) AND CONNECTIONS SHALL BE MECHANICALLY PROTECTED (CIRCUIT BREAKERS SHALL BE LOCKED IN THE ON POSITION WITH AN APPROVED MECHANICAL CLIP.) CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED MARKING, SHALL BE ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL, AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT". THE LOCATION OF THE CIRCUIT

DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT.

17. FIRE ALARM CONDUCTORS USED IN WET OR UNDERGROUND LOCATIONS SHALL BE OF TYPE THWN.

18. FIRE ALARM SYSTEM "RECORD OF COMPLETION" DOCUMENT SHALL BE PROVIDED TO THE CLIENT ALONG WITH THE OTHER REQUIRED CLOSE-OUT DOCUMENTATION AT THE TIME OF SYSTEM ACCEPTANCE AND APPROVAL PER

NFPA 72.

NORTH

AREA OF WORK

CONTRACTOR INFORMATION

BP BACKFLOW PREVENTER

CSFD COMBINATION SMOKE / FIRE DAMPER

EOL END-OF-LINE

ELR END-OF-LINE RESISTOR

ER EXISTING DEVICE TO BE REMOVED

ERR EXISTING DEVICE TO BE REMOVED

AND REPLACED WITH NEW

EX EXISTING DEVICE TO REMAIN

N NEW DEVICE

RR EXISTING DEVICE TO BE REMOVED

AND RELOCATED

FACU FIRE ALARM CONTROL UNIT

FAPS FIRE ALARM POWER SUPPLY

FATC FIRE ALARM TERMINAL CABINET

LRM LOCAL RAIL MODULE

PIV POST INDICATOR VALVE

APPLICABLE CODES & REGULATIONS

FPL FIRE-POWER LIMITED

FPLP FIRE-POWER LIMITED PLENUM

FPLR FIRE-POWER LIMITED RISER

TP TWISTED PAIR

TSP TWISTED SHIELDED PAIR

THHN "T" THERMOPLASTIC INSULATED CABLE

"HH" MEANS THAT THE WIRE IS HEAT

RESISTANT AND CAN WITHSTAND

A HIGHER TEMPERATURE

(UP TO 194° F)

"N" NYLON COATING THAT COVERS

WIRE INSULATION

THWN "T" THERMOPLASTIC INSULATED CABLE

"H" MEANS WIRE IS HEAT RESISTANT

"W" MEANS WIRE IS APPROVED FOR

DAMP/WET LOCATIONS

"N" NYLON COATING THAT COVERS

WIRE INSULATION

WP WEATHERPROOF DEVICE

ABBREVIATIONS

CALIFORNIA CODE OF REGULATIONS (CCR), TITLE 19

CCR, TITLE 24, PART 2: 2013 CALIFORNIA BUILDING CODE (CBC)

CCR, TITLE 24, PART 3: 2013 CALIFORNIA ELECTRICAL CODE (CEC)

CCR, TITLE 24, PART 4: 2013 CALIFORNIA MECHANICAL CODE (CMC)

CCR, TITLE 24, PART 9: 2013 CALIFORNIA FIRE CODE (CFC)

CCR, 2013 CALIFORNIA ELEVATOR SAFETY CONSTRUCTION CODE

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 72, 2013 EDITION,

AS AMENDED IN CHAPTER 47 OF THE 2013 CFC.

LOCAL JURISDICTION AMENDMENTS TO STATE CODE

RELOCATE ONE SPEAKER STROBE AND ADD ONE SPEAKER STROBE TO SAME NOTIFICATION

CIRCUITS TO ACCOMMODATE ROOM 105 TI.

REVISION 1

REVISION 2

POINT TO POINT DIAGRAM

NOTATIONS

REFERENCE DETAIL

PAGE NUMBER

DETAIL NUMBER

INITIATION ACTION MANUAL PULL FLOW SWITCHSMOKE

DETECTOR

DUCT

DETECTOR

TAMPER

SWITCH

MASS NOTIF.

BUTTON PUMP RUNNING PUMP PHASE

REVERSAL

X

PUMP POWER

LOSS/ PHASE LOSS

PUMP CONTROLLER

ALARM

KEYED

MICROPHONE

ANY SYSTEM

TROUBLE

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X X X

X X X

X

X

X

EXISTING DIAGRAM

FA101

SCOPE OF WORK,

GENERAL NOTES,

SEQUENCE OF

OPERATION, VICINITY

MAP

REVISION DATE

TRAVIS AFB, CA, 94535

FIRE ALARM SYSTEM

16-21008

M WALLIOR

W WALKUP

10/6/15

S y s t e m s I n c.

FIRE / LIFE SAFETY & LOW VOLTAGE SPECIALISTS

HCI

TRAVIS AFB

ROOM 105 TI

C

LT

I L

E R

F E

F

Y

ET

A S

O

F I

H

A

I NI C.

& OWL V

G E

I L

C P S E

A

IS

T

Phone: (916) 419-6900 Fax: (916) 419-6903 24-Hour Service: (877) 331-2084 Website: www.hcisystems.net

Sacramento Office:

1419 N. Market Blvd. Suite 5 Sacramento, CA 95834

BUILDING 924

PALM SPRINGS - SACRAMENTO - SAN DIEGO

FRESNO - GLENDALE - HAYWARD - IRVINE - ONTARIO

FIRE ALARM SYSTEM

RECORD DRAWINGS 12/12/15

NA

AutoCAD SHX Text

ACTIVATE STROBES & PLAY FIRE ALARM MESSAGE

AutoCAD SHX Text

DISPLAY ALARM CONDITION ON FACP/ REMOTE ANN

AutoCAD SHX Text

TRANSMIT MANUAL PULL STATION ALARM TO CENTRAL STATION

AutoCAD SHX Text

ACTIVATE ALL STROBES AND PLAY MASS NOTIFICATION MESSAGE

AutoCAD SHX Text

DISPLAY SUPERVISORY CONDITION ON FACP AND REMOTE ANN.

AutoCAD SHX Text

TRANSMIT MASS NOTIF. SUPERVISORY SIGNALTO CENTRAL STATION

AutoCAD SHX Text

TRANSMIT SMOKE DETECTOR ALARM TO CENTRAL STATION

AutoCAD SHX Text

TRANSMIT DUCT SMOKE DETECTOR SUPERVISORY TO CENTRAL STATION

AutoCAD SHX Text

TRANSMIT SPRINKLER VALVE SUPERVISORY TO CENTRAL STATION

AutoCAD SHX Text

ACTIVATE WATER FLOW HORN STROBE

AutoCAD SHX Text

TRANSMIT SPRINKLER WATER FLOW ALARM TO CENTRAL STATION

AutoCAD SHX Text

TRANSMIT PUMP RUNNING ALARM TO CENTRAL STATION

AutoCAD SHX Text

TRANSMIT PUMP CONTROLLER SUPERVISORY TO CENTRAL STATION

AutoCAD SHX Text

OVERRIDE FIRE ALARM MESSAGE

AutoCAD SHX Text

OVERRIDE ALL MESSAGES TEMPORARILY

AutoCAD SHX Text

DISPLAY TROUBLE CONDITION ON FACP AND REMOTE ANNUNCIATOR

AutoCAD SHX Text

TRANSMIT SYSTEM TROUBLE TO CENTRAL STATION

AutoCAD SHX Text

SHUT DOWN ASSOCIATED AHU

AutoCAD SHX Text This drawing and the information and design application herein contained is the property of HCI Systems Inc. and is loaned upon the express condition that the same be returned to HCI Systems Inc. upon request; all information herein contained shall be treated as secret and confidential; no reproduction of this drawing or part thereof shall be made without the written consent of HCI Systems Incorporated.

AutoCAD SHX Text

LICENSE:

AutoCAD SHX Text

DRAWN:

AutoCAD SHX Text

REVIEWED:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

SHEET TITLE:

AutoCAD SHX Text

PROJECT:

AutoCAD SHX Text

CONTRACTOR:

AutoCAD SHX Text

JOB NUMBER:

AutoCAD SHX Text

DRAWING NUMBER:

AutoCAD SHX Text

NOTES:

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text Exp.

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text F

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text 02/16

AutoCAD SHX Text A

AutoCAD SHX Text F

AutoCAD SHX Text C

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DESIGNER: MARC P WALLIOR

AutoCAD SHX Text

NICET LEVEL IV #90198

AutoCAD SHX Text

ACE #14570

AutoCAD SHX Text

DRAWINGS NOT PLOTTED 30" X 42" ARE NOT TO SCALE

Sheets and Views
FA101

File details come from the government source that posted it. Updated .