This document appears to be a detailed water treatment and chemical monitoring log for various buildings and equipment, tracking multiple parameters such as pH, iron levels, water conductivity, nitrite levels, and glycol measurements. The log contains entries for numerous buildings (labeled with numbers like 3, 4, 10, 14, etc.), with each entry recording both "hot" and "chill" system measurements, along with mechanical notes and treatment observations.
Key observations include frequent mechanical issues such as leaks, non-operational systems, pot feeder problems, and challenges with chemical treatment. Many entries note specific problems like "system losing treatment", "could not treat due to no pot feeder", "boiler leak in system", and "multiple leaks in system". The log systematically documents pH levels (ranging approximately from 7.1 to 11.5), iron concentrations, water test conductivity, nitrite levels, and glycol measurements. Technicians have consistently added nitrite to systems and documented various operational constraints preventing full system treatment or maintenance.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Building EQUIP Metalurgy pH Iron
Water Test
Conduct ivity
Treatme nt
Conduct ivity
Water Test
Nitrite
Treatm ent
Nitrite Moly Glycol
Mechanic al
Problems -
NOTES
hot 8.3 0.25 350 100 chill 11.5 1.2 644 150
Added nitrite.
System losing treatment hot 9.7 0.1 650 2019 200 chill 9.3 1.5 1379 450 hot 1 8.3 3.2 311 3012 100
Added nitrite.
System losing treatment.
chill 10.2 1.9 3264 1250 hot 8.3 0.9 314 100 Leak chill 11.4 0.63 1637 400 Added nitrite hot 9 2.1 400 2819 150 Leak chill 1 north 9.7 0.14 390 400
Added nitrite chill 2 south 10.3 0.12 2819 800
38 hot 8.6 2.1 1400 2000 chill 10.3 3.2 5760 1550
39 hot 9.4 0.4 5231 1450 chill 10.7 2 3126 1450 hot 1 north 8.3 0.2 352 2491 100
Added nitrite hot 2 NE 8.4 0.29 351 2291 100 Added nitrite hot 3 S 3551 0.06 1050 2319 1050 chill 1 N 10 0.3 5530 900 chill 2 NE 10.4 0.8 3330 1200 chill 3 S 9.3 0.8 4206 800
51 hot 10.6 0.9 5021 1350 chill 8.9 2.3 3583 1050
52 hot 8.7 3 726 250 Added nitrite chill 7.7 2 7625 1500 hot 9.2 0.17 406 150 non operational chill 10.6 0.07 5301 1500 hot 10.4 0.8 1234 150 could not treat due to no pot feeder hot 11.4 0.6 3050 3000 could not get water sample chill 10.4 1.2 2940 750 Could not get sample hot 1 8.8 0.8 3880 950 no pot feeder/ system no operational hot 2 10.9 0.45 351 100 no pot feeder to treat, no expansion tank
1902 chill 8.9 0.3 1902 650 hot 1
MR2 8.4 0.2 312 2891 100 950
boiler leak in system hot 2 Inside 8.4 0.2 307 100 chill MR1 9 0.4 no expansin tank chill N 10.7 0.3 1587 550 multiple leaks in system chill MR2 9.5 0.3 2650 950 no pot feeder
155 hot alum 8.4 0.35 353 100 100 no pot feeder chill 10.1 0.09 1218 600 chill south 9.8 0.2 1040 800
Do not service per Ed.
hot 9.2 0.9 402 150
System was running cold chill 10.3 0.25 3751 1600
177 hot 8.4 0.9 291 100 leaking lid chill 9.5 0.8 2031 1000
179 hot 9 0.2 439 100 no pot feeder chill 10.3 0.17 2600 650 hot 9.1 0.44 515 150 leaking line could not treat chill 10.7 0.3 6031 1550 hot 8.7 1.7 500 100
Did not add due to leaking valve chill 10.6 2.8 3960 1250
187 hot 8.4 0.4 349 2183 100 Added nitrite chill 10.1 4.2 2926 900 hot alum 7.8 2.2 2102 57
Need sample point to collect sample chill 9.6 9.6 1000 250 Added nitrite
206 hot 8.5 1 421 100 Small leak chill 7.9 0.6 2566 650
214 hot 1 W 10.5 0.8 5423 1500 hot 2 8.4 0.3 235 100 chill 10.3 0.3 2650 1050 chill W 10.3 0.4 2650 1050 No sample point
226 chill 10 2 1345 600
228 hot 8.4 0.17 638 800 chill 10 0.9 6000 1500
240 hot 8.4 0.18 332 250 Pot feeder leaking chill 8.8 1.5 200 200
Water was running hot.
241 hot 10 1.1 2200 600 chill 10.2 0.7 1742 600
243 chill 9.6 0.13 629 150 hot 1 N 8.3 0.5 253 100 leaking prv/ no pot feeder hot 2 S 9.6 1.8 non op no feeder
249 hot E 8.7 0.6 353 100 no pot feeder chill 1 E 10.8 1.4 2961 800 chill 2 W 8.3 1.3 351 100 Pump has a leak hot W 8.4 0.2 308 100 prv failed,pot feeder is tied to to make up chill 9.4 0.24 536 150 expansion tank in the wrong place
350 hot 8.5 0.2 2811 850 chill 10.1 0.2 1991 950
380A hot 10.4 0.4 3621 950 chill 10.2 0.2 2102 800
380B hot 9.9 0.66 2377 600 chill 10.1 2 4521 1000
381 hot 1 9.8 0.1 2240 900 hot 2 10.5 0.2 2711 900 hot 3 9.46 0.1 2800 750 chill 10.2 0.75 3937 800
383 hot 10 0.8 1300 700 chill 10.3 0.32 2270 900
400 hot 9.9 0.3 3817 1000 chill 10.4 0.9 3816 1300 hot 1 Dom 10.1 0.28 1344 600
Added nitrite hot 2 hvac 9.7 3.8 3899 1100 chill 9.7 0.14 2678 750
Leak/ could not service
404 hot/chill 8.5 0.9 1902 600
406 hot 9.8 0.45 3917 950 chill 10.1 0 2230 850
407 hot 9.9 5 2311 800 chill 7.8 1 1799 750
408 hot 9.4 3 1655 650 chill 10.2 3.1 3122 1000
409 hot 9 3.1 2441 850 chill 9.8 0.5 3000 1000
410 hot 9.7 0.2 3002 900 chill 10.4 0.6 4121 1200
434 hot 1 E 9.7 0.1 2556 800 hot 2 W 9.3 2.1 1545 650 chill 1 W 8.8 1 600 1650 100 400 chill 2 E 9.7 0.1 3136 950
437 hot 9.9 0.2 3120 900 chill 10.4 1.1 3488 1050 hot
Suspend service per Kelly 4.7.21 chill
Suspend service per Kelly 4.7.21
440 hot 9.4 0.2 1661 650 No pot feeder chill 10.4 0.1 3672 1100
441 hot 8.7 0.42 771 2539 300 1050 Added nitrite chill 10.1 0.6 1988 800
442 hot 9.9 1 3310 950 chill 10.4 0.35 3671 950
443 hot 9.3 0.2 1233 2391 400 850 chill 10 0.4 820 300
444 hot 8.5 0.2 416 2891 300 250 nitrite chill 10.2 0.3 1996 900 No pot feeder
525 hot 9.7 0.5 2400 800 chill 8.9 0 3690 800
549 hot 1 W 9 0.2 2020 900 hot 2 9.1 0.32 1765 850 chill 1 W 9.5 0.5 549 1200
Added a half bag of nitrite.
chill 2 9 0.9 4600 1200
552 hot 9.8 0.25 2300 300 chill 10.1 0.1 2924 1000
554 hot alum 8.8 0.28 2201 150 Access blocked hot 9 1.1 9000 1200+
Leaking pot feeder.
Could not service hot 9.1 2.3 391 250 could not add chemical, need a funnel chill 10.2 1.9 3700 800 Injection site
648 hot 9.5 0.18 430 100 Valve has leak chill 9.4 0.22 288 100 Added nitrite
650 hot 10.3 0.08 3500 700 chill 9.4 0.03 1389 234 needs injector\
660 hot 9 1 1657 1230 chill 10.5 0.3 568 234.5
I added 1 bag of nitrite to system.
hot 9.1 1.2 424 100
Added 1 bag of nitrite to the system.
chill 9 0.8 2312 700
668 hot 8.5 0.4 4421 1250 chill 9.1 0.45 540 668 Injection site hot 8.5 0.3 1200 200
I added 1 bag of nitrite hot Domes 8.9 0.23 2150 100.5
Injection site chill 9.2 0.14 2860 800 hot 9.7 0.75 5000 1200
Leaking pot feeder.
Could not service chill 9.9 0.47 3589 550
Leaking pot feeder.
Could not service
808 hot 9.5 0 5000+ 2500 Injection site chill 10.6 0.2 2234 550 hot 1 west alum 10 0.16 3630 1340 100 hot 2 east 10 0.2 1650 1600 chill W 10 3.2 4500 1340 chill E 10.1 0.7 2690 950 hot
Unservicea ble. Might be replaced soon.
818 hot 1 10.3 0.02 3574 850 Out of service hot 2 10.2 0.1 3390 1000
819 hot 9.6 0.71 1885 750 Out of service hot 8.8 0.45 2109 1200 system not running chemical is very concentrat
ed. Pot feeder is leaking chill 9.2 1.1 434 200 leaking lid, cannot dose
854 hot 8.9 0.01 2700 1200 chill 9.9 0.3 3000 1300
859 hot 9.4 0.35 4700 1600 chill 9.6 0 2000 950
861 hot 9.5 9.5 2460 1000 chill 10.5 0 3500 1200
877 hot 290 9 167.5 100 Injection site chill 9.9 0.1 3820 950
882 hot 9.5 0.8 1783 650 Out of service
902 chill 9.9 1.2 1283 350 N/A out of service
904 hot 9.3 1.9 408 100 cannot treat
921 hot 8.9 1.1 500 100 nitrate chill 10.5 2.1 4600 1200
924 hot 8.9 0.2 1776 1300
925 hot 9.8 0.92 1040 400 Added nitrite chill 11.14 0.3 4850 1740
942 hot 8.3 0.76 1650 1200 chill 7.1 0.9 7000 1300
971 hot 10.3 0.3 4800 800 hot 10.9 0.55 430 100 could not dose Injection site chill 10.8 1.4 1170 100.5 Injection hot alum 9.82 0.6 1602 100
Building looked empty, gates open no one there please advise chill 8.2 0.3 1934 800
Building looked empty, gates open no one there please advise
1212 hot 9 0 2000 1600 chill 10.4 1.2 2780 700
1219 hot 9.5 0.6 1922 600 chill 10 5 1973 900
1301 hot 10.3 0.65 1965 900 chill 10.5 0.2 5740 1600 hot/chill 9.2 1.4 530 200
Could not add to system due to pot feeder lid.
chill 7.5 3.2 400 100 system seems to feed both/ n hot 8.5 0.62 2271 200
Could not drain pot feeder
1308 hot 9.3 0.2 4099 1000 chill 9.2 0.65 2109 850 system feeder seems to feed both hot/chill 7.98 0.2 1899 850 system spigot is stuck and seems to be close to breaking could not does
1318 hot 9.1 0.8 1892 850 chill 10.2 0.5 1582 600 chill 8.48 1,2 2457 700 under constructio n hot 8.25 0.8 361 1892 200 850 under constructio n chill 8.72 0.5 1892 800 under constructio n hot 8.7 0.42 680 1782 250 700 under constructio n chill 8.6 0.1 2891 750 system replaceme nt hot 8.4 0.23 1892 850 system replaceme nt
1348 hot 8.2 0.24 2819 400 Added nitrate
1350 hot 9 0.32 2412 800 chill 9.67 0 2713 650
1351 hot 8.7 0.11 2130 2371 900 1050 chill 8.83 0.4 2357 950 pot feeder seal is broken, chemical still in system hot 9.4 0.9.5 2891 850 400 not running, no water running throw system chill 9.2 0.59 2861 1050
Leaking pot feeder lid.
Chemical still in system hot 8.5 1.1 258 0 added chemical but left the lines cosed due to leaking preassure valve chill 9.5 0.6 3223 750
1354 hot alum 10.3 0.2 2192 40 chill alum 9.2 2.1 2100 60
1355 hot alum 9.9 0.7 1882 45 chill alum 9.4 1.2 1782 50 hot 9.4 1.2 351 2381 800 900
Mechanica l room cannot be opened chill 7 0.22 1830 2291 700 800
Mechanica l room cannot be opened
7690 chill 1 8.3 0.4 2760 650 hot 8.6 0.85 416 100 Leaking valves
7766 chill 9.2 0.7 5000 1200 hot alum 8 2.8 461 150 100
System uses molybdat e