RFI ANSWERS Part 2.pdf
PDF 111 KB Posted
- Solicitation number
- FA442724R0029
About this file
This document is a continuation of Answers to an RFI (Request for Information) related to the Repair Generator and Transfer Switch, B10 solicitation (FA442724R0029) issued by the Department of the Air Force Air Mobility Command.
The RFI Answers Part 2 provides clarification on the generator breaker that is not scoped to be removed, contrary to the initial understanding. The document references the NEC (National Electrical Code) 700.1 and 700.2, which specify requirements for emergency systems. It also includes an attached image with comments to help explain the circuit breaker configuration. The RFI response advises that the generator breaker (MSA-2, 600A, 3P) is not to be removed, and the circuit breaker to be bypassed and labeled as "spare" is MSA-1 (1000A, 3P), which provides power to the fire pump.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Repair Generator and Transfer Switch, B10 RFI Answers Part 2
• After studying you Addendum DWGs. I know it is a late for question. I have completed several projects with backup generators in the last 10 years. What you are say about eliminating the generator breaker in my opinion is dangerously wrong. Mike Holt, I have used for study on many projects he is a recognized expert in the field. Please refer to pages 6 and 7 NEC 700.1 & 700.2.
o The generator breaker (MSA-2, 600A, 3P) is not scoped to be removed. The circuit breaker to be bypassed and labeled as “spare” is MSA-1 (1000A, 3P) which provides power to the fire pump. I attached an image with comments.