1-0_FA4427-12-R-0108_Atch_4_Bay_D_Submittals.pdf

PDF 387 KB Posted

Attached to
Renovate Bays D, E, &F of Building 237, Travis AFB, CA
Solicitation number
FA4427-12-R-0108
Issued by

About this file

Bay D Material Submittals

View the file

Other files

File Type Posted
1-5_FA4427-12-R-0108_Atch_7_SID_1-7-2013.pdf PDF
0-9_FA4427-12-R-0108-02_Atch_3_Wage_Determination_Applicability_1-11-2013.doc DOC document
0-5_FA4427-12-R-0108-02_Atch_1_Bay_F_Specifications_1-7-2013.pdf PDF
0-4_FA4427-12-R-0108-02_Atch_1_Bay_E_Specifications_1-7-2013.pdf PDF
0-3_FA4427-12-R-0108-02_Atch_1_Bay_D_Specifications_1-7-2013.pdf PDF
0-2_FA4427-12-R-0108-02_Fill-In_B_thru_K.doc DOC document
0-1_FA4427-12-R-0108-02_Bldg_237_Amendment_02_Corrections.pdf PDF
12R0108_Question_and_Answer_1.pdf PDF
Amendment_001.pdf PDF
Pre-Proposal_Site_Visit.pdf PDF
0-5_FA4427-12-R-0108_Atch_1_Bay_F_Specifications.pdf PDF
1-3_FA4427-12-R-0108_Atch_5_Past_Performance_Ltr_and_Questionnaire.docx DOCX document
0-7_FA4427-12-R-0108_Atch_2_Bay_E_Drawings.pdf PDF
0-3_FA4427-12-R-0108_Atch_1_Bay_D_Specifications.pdf PDF
0-9_FA4427-12-R-0108_Atch_3_Wage_Determination_Applicability.doc DOC document
0-8_FA4427-12-R-0108_Atch_2_Bay_F_Drawings.pdf PDF
1-1_FA4427-12-R-0108_Atch_4_Bay_E_Submittals.pdf PDF
0-1_FA4427-12-R-0108_Bldg_237_Solicitation.pdf PDF
0-2_FA4427-12-R-0108_Fill-In_B_thru_K.doc DOC document
0-6_FA4427-12-R-0108_Atch_2_Bay_D_Drawings.pdf PDF
1-2_FA4427-12-R-0108_Atch_4_Bay_F_Submittals.pdf PDF
1-4_FA4427-12-R-0108_Atch_6_Subcontractor_Consent_Form.docx DOCX document
0-4_FA4427-12-R-0108_Atch_1_Bay_E_Specifications.pdf PDF
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Line Act-ivity

Trans-mittal

Specification

Section

SD

SD Description Item Submitted Paragraph

Classi-fication:

GOVT or

A/E

Revwr

Submit Approval

Needed

By

Material

Needed

By

Action

Code

Date Of

Action

Date

FWD to

APPR /

Auth -

Date

RCD

From

CONTR

Date

FWD To

Other

Revwr

Date

RCD

From

Other

Revwr

Action

Code

Date Of

Action

Mailed To

CONTR/

Date

RCD

From

APPR

Authority

Remarks

1 01 11 00 01 Preconstruction Submittals Utility Outage Requests 1.10.1

2 01 11 00 01 Preconstruction Submittals Utility Connection Requests 1.10.1

3 01 11 00 01 Preconstruction Submittals Excavation Permits 1.10.2

4 01 11 00 01 Preconstruction Submittals Welding Permits 1.10.2

5 01 11 00 07 Certificates Energy Performance Rating 1.7.1.1

6 01 33 00 01 Preconstruction Submittals Submittal Register 1.9 G

7 01 35 26 01 Preconstruction Submittals Accident Prevention Plan (APP) 1.6 G A

8 01 35 26 01 Preconstruction Submittals Activity Hazard Analysis (AHA) 1.7 G A

9 01 35 26 01 Preconstruction Submittals Crane Operators G A

10 01 35 26 06 Test Reports Reports 1.11

11 01 35 26 06 Test Reports Accident Reports 1.11.1

12 01 35 26 06 Test Reports Gas Protection

13 01 35 26 07 Certificates Confined Space Entry Permit 1.8

14 01 35 26 07 Certificates License Certificates

15 01 35 26 07 Certificates Contractor Safety Self-Evaluation

Checklist

G A

16 01 35 26 07 Certificates Certificate of Compliance 1.11.3

17 01 45 00.10 20 01 Preconstruction Submittals QC Plan 1.6 G

18 01 50 00 01 Preconstruction Submittals Construction site plan 1.4

19 01 50 00 01 Preconstruction Submittals Traffic control plan 3.3.1

20 01 74 19 01 Preconstruction Submittals Waste Management Plan 1.6 G

21 01 74 19 11 Closeout Submittals Records 1.7

22 01 78 00 03 Product Data As-Built Record of Equipment and

Materials

1.3.2

23 01 78 00 03 Product Data Warranty Management Plan 1.7.1

24 01 78 00 03 Product Data Warranty Tags 1.7.5

25 01 78 00 03 Product Data Final Cleaning 1.9

26 01 78 00 03 Product Data Spare Parts Data 1.4

27 01 78 00 08 Manufacturer’s Instructions Preventative Maintenance 1.5

28 01 78 00 08 Manufacturer’s Instructions Condition Monitoring (Predictive

Testing)

1.5

CONTRACTOR

SCHEDULE DATES

CONTRACTOR

ACTION

APPROVING AUTHORITY

TITLE: Renovate Bldg 237, Bay D

SUBMITTAL REGISTERLOCATION: Travis Air Force Base, California

CONTRACT NO:

2 SEP 2011

Atch # 4 - D BAY

Trans-mittal

Specification

Section

SD

SD Description Item Submitted Paragraph

Classi-fication:

GOVT or

A/E

Revwr

Submit Approval

Needed

By

Material

Needed

By

Action

Code

Date Of

Action

Date

FWD to

APPR /

Auth -

Date

RCD

From

CONTR

Date

FWD To

Other

Revwr

Date

RCD

From

Other

Revwr

Action

Code

Date Of

Action

Mailed To

CONTR/

Date

RCD

From

APPR

Authority

Remarks

CONTRACTOR

SCHEDULE DATES

CONTRACTOR

ACTION

APPROVING AUTHORITY

TITLE: Renovate Bldg 237, Bay D

SUBMITTAL REGISTERLOCATION: Travis Air Force Base, California

CONTRACT NO:

29 01 78 00 08 Manufacturer’s Instructions Inspection 1.5

30 01 78 00 08 Manufacturer’s Instructions Instructions 1.7.1

31 01 78 00 10 Operation and Maintenance

Data

Operation and Maintenance

Manuals

1.8

32 01 78 00 11 Closeout Submittals Record Drawings 1.3.1

33 01 78 00 11 Closeout Submittals Certification of EPA Designated

Items

1.6 G

34 01 78 00 11 Closeout Submittals Interim Form DD1354 1.10 G

35 01 78 00 11 Closeout Submittals Checklist for Form DD1354 1.10 G

36 02 41 00 01 Preconstruction Submittals Existing Conditions 1.9 G

37 02 41 00 07 Certificates Demolition Plan 1.2.1 G

38 02 41 00 07 Certificates Notification 1.6 G

39 02 41 00 11 Closeout Submittals Receipts 3.2.4

40 02 82 16.00 20 03 Product Data Local exhaust equipment 3.1.4 G

41 02 82 16.00 20 03 Product Data Vacuums 3.1.5 G

42 02 82 16.00 20 03 Product Data Respirators 3.1.1.1 G

43 02 82 16.00 20 03 Product Data Pressure differential automatic recording instrument

3.1.4 G

44 02 82 16.00 20 03 Product Data Amended water 1.2.2 G

45 02 82 16.00 20 03 Product Data Material Safety Data Sheets

(MSDS) for all materials

1.3.8 G

46 02 82 16.00 20 06 Test Reports Air sampling results 1.5.5 G

47 02 82 16.00 20 06 Test Reports Pressure differential recordings for local exhaust system

1.5.6 G

48 02 82 16.00 20 06 Test Reports Asbestos disposal quantity report 3.3.3.2 G

49 02 82 16.00 20 06 Test Reports Clearance sampling 3.2.5.3 G

50 02 82 16.00 20 07 Certificates Asbestos hazard abatement plan 1.3.9 G

51 02 82 16.00 20 07 Certificates Testing laboratory 1.3.10 G

52 02 82 16.00 20 07 Certificates Private qualified person documentation

1.5.1 G

53 02 82 16.00 20 07 Certificates Contractor's license 1.5.4 G

54 02 82 16.00 20 07 Certificates Competent person 1.5.2 G

55 02 82 16.00 20 07 Certificates Worker's license 1.5.3 G

2 SEP 2011

Trans-mittal

Specification

Section

SD

SD Description Item Submitted Paragraph

Classi-fication:

GOVT or

A/E

Revwr

Submit Approval

Needed

By

Material

Needed

By

Action

Code

Date Of

Action

Date

FWD to

APPR /

Auth -

Date

RCD

From

CONTR

Date

FWD To

Other

Revwr

Date

RCD

From

Other

Revwr

Action

Code

Date Of

Action

Mailed To

CONTR/

Date

RCD

From

APPR

Authority

Remarks

CONTRACTOR

SCHEDULE DATES

CONTRACTOR

ACTION

APPROVING AUTHORITY

TITLE: Renovate Bldg 237, Bay D

SUBMITTAL REGISTERLOCATION: Travis Air Force Base, California

CONTRACT NO:

56 02 82 16.00 20 07 Certificates Landfill approval 1.3.11 G

57 02 82 16.00 20 07 Certificates Employee training 1.3.3 G

58 02 82 16.00 20 07 Certificates Medical certification 1.3.12 G

59 02 82 16.00 20 07 Certificates Waste shipment records 1.3.11 G

60 02 82 16.00 20 07 Certificates Respiratory Protection Program 1.3.6 G

61 02 82 16.00 20 07 Certificates Delivery tickets 1.3.11 G

62 02 82 16.00 20 07 Certificates Vacuums 3.1.5 G

63 02 82 16.00 20 07 Certificates Water filtration equipment 3.1.2.3 G

64 02 82 16.00 20 07 Certificates Ventilation systems 3.1.5 G

65 02 82 16.00 20 07 Certificates equipment used to contain airborne asbestos fibers

3.1 G

66 02 82 16.00 20 07 Certificates Notifications 1.3.4

67 02 82 16.00 20 11 Closeout Submittals Notifications 1.3.4 G

68 02 82 16.00 20 11 Closeout Submittals Rental equipment 1.6.1 G

69 02 82 16.00 20 11 Closeout Submittals Respirator program records 1.3.6.1 G

70 02 82 16.00 20 11 Closeout Submittals Permits and licenses 1.3.4 G

71 05 50 13 02 Shop Drawings Security Bar G

72 05 50 13 03 Product Data Security Bar G

73 07 21 16 03 Product Data Blanket insulation 2.1

74 07 21 16 03 Product Data Sill sealer insulation

75 07 21 16 03 Product Data Vapor retarder

76 07 21 16 03 Product Data Pressure sensitive tape

77 07 21 16 03 Product Data Accessories 2.3

78 07 21 16 03 Product Data Certification

79 07 21 16 08 Manufacturer’s Instructions Insulation 3.3.1

80 07 92 00 03 Product Data Sealants 2.1

81 07 92 00 03 Product Data Primers 2.2

82 07 92 00 03 Product Data Bond breakers 2.3

83 07 92 00 03 Product Data Backstops 2.4

2 SEP 2011

Trans-mittal

Specification

Section

SD

SD Description Item Submitted Paragraph

Classi-fication:

GOVT or

A/E

Revwr

Submit Approval

Needed

By

Material

Needed

By

Action

Code

Date Of

Action

Date

FWD to

APPR /

Auth -

Date

RCD

From

CONTR

Date

FWD To

Other

Revwr

Date

RCD

From

Other

Revwr

Action

Code

Date Of

Action

Mailed To

CONTR/

Date

RCD

From

APPR

Authority

Remarks

CONTRACTOR

SCHEDULE DATES

CONTRACTOR

ACTION

APPROVING AUTHORITY

TITLE: Renovate Bldg 237, Bay D

SUBMITTAL REGISTERLOCATION: Travis Air Force Base, California

CONTRACT NO:

84 07 92 00 07 Certificates Sealant 3.3.6

85 08 11 13 02 Shop Drawings Doors 2.1 G

86 08 11 13 02 Shop Drawings Doors 2.1 G

87 08 11 13 02 Shop Drawings Frames 2.5 G

88 08 11 13 02 Shop Drawings Frames 2.5 G

89 08 11 13 02 Shop Drawings Accessories 2.3

90 08 11 13 02 Shop Drawings Weatherstripping 2.7

91 08 11 13 03 Product Data Doors 2.1 G

92 08 11 13 03 Product Data Frames 2.5 G

93 08 11 13 03 Product Data Accessories 2.3

94 08 11 13 03 Product Data Weatherstripping 2.7

95 08 14 00 02 Shop Drawings Doors 2.1 G

96 08 14 00 03 Product Data Doors 2.1 G

97 08 14 00 03 Product Data Accessories 2.2

98 08 14 00 03 Product Data warranty 1.4

99 08 14 00 03 Product Data Sound transmission class rating 2.1.2 G

100 08 14 00 03 Product Data Fire resistance rating 2.1.3 G

101 08 14 00 03 Product Data Certification

102 08 14 00 04 Samples Doors 2.1

103 08 14 00 04 Samples Door finish colors 2.3.6.2 G

104 08 14 00 06 Test Reports Split resistance 2.4

105 08 14 00 06 Test Reports Cycle-slam 2.4

106 08 14 00 06 Test Reports Hinge loading resistance 2.4

107 08 71 00 02 Shop Drawings Hardware schedule 1.3 G

108 08 71 00 02 Shop Drawings Keying system 2.3.5

109 08 71 00 03 Product Data Hardware items 2.3 G

110 08 71 00 08 Manufacturer’s Instructions Installation 3.1

111 08 71 00 10 Operation and Maintenance

Data

Hardware Schedule 1.3 G

2 SEP 2011

Trans-mittal

Specification

Section

SD

SD Description Item Submitted Paragraph

Classi-fication:

GOVT or

A/E

Revwr

Submit Approval

Needed

By

Material

Needed

By

Action

Code

Date Of

Action

Date

FWD to

APPR /

Auth -

Date

RCD

From

CONTR

Date

FWD To

Other

Revwr

Date

RCD

From

Other

Revwr

Action

Code

Date Of

Action

Mailed To

CONTR/

Date

RCD

From

APPR

Authority

Remarks

CONTRACTOR

SCHEDULE DATES

CONTRACTOR

ACTION

APPROVING AUTHORITY

TITLE: Renovate Bldg 237, Bay D

SUBMITTAL REGISTERLOCATION: Travis Air Force Base, California

CONTRACT NO:

112 08 71 00 11 Closeout Submittals Key Bitting 1.4

113 09 29 00 03 Product Data Impact Resistant Gypsum Board 2.1.2

114 09 29 00 03 Product Data Accessories 2.1.6

115 09 29 00 03 Product Data Certification

116 09 29 00 03 Product Data Gypsum Board 2.1.1

117 09 29 00 07 Certificates Asbestos Free Materials 2.1 G

118 09 29 00 08 Manufacturer’s Instructions Material Safety Data Sheets 2.1

119 09 29 00 10 Operation and Maintenance

Data

Manufacturer maintenance instructions

2.1

120 09 29 00 10 Operation and Maintenance

Data

Waste Management 3.9

121 09 51 00 02 Shop Drawings Approved Detail Drawings 1.2

122 09 51 00 03 Product Data Acoustical Ceiling Systems 1.2.1

123 09 51 00 03 Product Data Certification

124 09 51 00 04 Samples Acoustical Units 2.1

125 09 51 00 04 Samples Acoustic Ceiling Tiles 2.1.1

126 09 51 00 06 Test Reports Fire Resistive Ceilings 1.2.1

127 09 51 00 06 Test Reports Ceiling Attenuation Class and Test 1.2.2

128 09 51 00 07 Certificates Acoustical Units 2.1

129 09 51 00 07 Certificates Acoustic Ceiling Tiles 2.1.1

130 09 65 00 02 Shop Drawings Resilient Flooring and Accessories 2.8 G

131 09 65 00 03 Product Data Resilient Flooring and Accessories 2.8 G

132 09 65 00 03 Product Data Adhesives 2.4

133 09 65 00 03 Product Data Vinyl Composition Tile 2.1

134 09 65 00 03 Product Data Wall Base 2.2

135 09 65 00 04 Samples Resilient Flooring and Accessories 2.8 G

136 09 65 00 06 Test Reports Moisture, Alkalinity and Bond Tests 3.3 G

137 09 65 00 08 Manufacturer’s Instructions Surface Preparation 3.2 G

138 09 65 00 08 Manufacturer’s Instructions Installation 3.1 G

139 09 65 00 10 Operation and Maintenance

Data

Resilient Flooring and Accessories 2.8 G

2 SEP 2011

Trans-mittal

Specification

Section

SD

SD Description Item Submitted Paragraph

Classi-fication:

GOVT or

A/E

Revwr

Submit Approval

Needed

By

Material

Needed

By

Action

Code

Date Of

Action

Date

FWD to

APPR /

Auth -

Date

RCD

From

CONTR

Date

FWD To

Other

Revwr

Date

RCD

From

Other

Revwr

Action

Code

Date Of

Action

Mailed To

CONTR/

Date

RCD

From

APPR

Authority

Remarks

CONTRACTOR

SCHEDULE DATES

CONTRACTOR

ACTION

APPROVING AUTHORITY

TITLE: Renovate Bldg 237, Bay D

SUBMITTAL REGISTERLOCATION: Travis Air Force Base, California

CONTRACT NO:

140 09 65 00 11 Closeout Submittals Resilient Flooring and Accessories 2.8

141 09 65 00 11 Closeout Submittals Adhesives 2.4

130 09 68 00 02 Shop Drawings Installation 3.4 G

131 09 68 00 02 Shop Drawings Moldings 2.5 G

132 09 68 00 03 Product Data Carpet 2.1 G

133 09 68 00 03 Product Data Carpet Cushion 2.3 G

134 09 68 00 03 Product Data Moldings 2.5 G

135 09 68 00 03 Product Data Surface Preparation 3.1 G

136 09 68 00 03 Product Data Installation 3.4 G

137 09 68 00 03 Product Data Regulatory Requirements 1.3 G

138 09 68 00 04 Samples Carpet 2.1 G

139 09 68 00 04 Samples Moldings 2.5 G

140 09 68 00 06 Test Reports Moisture and Alkalinity Tests 3.2 G

141 09 68 00 07 Certificates Carpet 2.1 G

142 09 68 00 07 Certificates Regulatory Requirements 1.3 G

143 09 68 00 10 Operation and Maintenance

Data

Carpet 2.1 G

144 09 68 00 10 Operation and Maintenance

Data

Cleaning and Protection 3.5 G

145 09 68 00 10 Operation and Maintenance

Data

Maintenance Service

146 09 68 00 11 Closeout Submittals Carpet 2.1

147 09 68 00 11 Closeout Submittals Adhesives and Concrete Primer 2.4

148 09 90 00 02 Shop Drawings Piping identification 3.7

149 09 90 00 02 Shop Drawings stencil 3.7

150 09 90 00 03 Product Data Certification

151 09 90 00 03 Product Data Environmental Data

152 09 90 00 03 Product Data Materials 2.1

153 09 90 00 03 Product Data Coating 2.1 G

154 09 90 00 03 Product Data Manufacturer's Technical Data

Sheets

2.1

155 09 90 00 03 Product Data Sealant

2 SEP 2011

Trans-mittal

Specification

Section

SD

SD Description Item Submitted Paragraph

Classi-fication:

GOVT or

A/E

Revwr

Submit Approval

Needed

By

Material

Needed

By

Action

Code

Date Of

Action

Date

FWD to

APPR /

Auth -

Date

RCD

From

CONTR

Date

FWD To

Other

Revwr

Date

RCD

From

Other

Revwr

Action

Code

Date Of

Action

Mailed To

CONTR/

Date

RCD

From

APPR

Authority

Remarks

CONTRACTOR

SCHEDULE DATES

CONTRACTOR

ACTION

APPROVING AUTHORITY

TITLE: Renovate Bldg 237, Bay D

SUBMITTAL REGISTERLOCATION: Travis Air Force Base, California

CONTRACT NO:

156 09 90 00 04 Samples Color G

157 09 90 00 04 Samples Textured Wall Coating System 1.4.2 G

158 09 90 00 04 Samples Sample Textured Wall Coating

System Mock-Up

1.4.3 G

159 09 90 00 07 Certificates Applicator's qualifications 1.3

160 09 90 00 07 Certificates Qualification Testing 1.4.1.2 G

161 09 90 00 08 Manufacturer’s Instructions Application instructions 3.2.1

162 09 90 00 08 Manufacturer’s Instructions Mixing 3.5.2

163 09 90 00 08 Manufacturer’s Instructions Manufacturer's Material Safety

Data Sheets

1.7.2

164 09 90 00 10 Operation and Maintenance

Data

Coatings 2.1 G

165 13 48 00.00 10 02 Shop Drawings Coupling and Bracing 3.1

166 13 48 00.00 10 02 Shop Drawings Flexible Couplings or Joints 3.3

167 13 48 00.00 10 02 Shop Drawings Equipment Requirements 1.3

168 13 48 00.00 10 02 Shop Drawings Contractor Designed Bracing 1.2.4

169 13 48 00.00 10 03 Product Data Coupling and Bracing 3.1

170 13 48 00.00 10 03 Product Data Equipment Requirements 1.3

171 13 48 00.00 10 03 Product Data Contractor Designed Bracing 1.2.4

172 13 48 00.00 10 07 Certificates Flexible Ball Joints 2.2

173 13 48 00 02 Shop Drawings Bracing 3.1 G

174 13 48 00 02 Shop Drawings Resilient Vibration Isolation Devices 3.4 G

175 13 48 00 02 Shop Drawings Equipment Requirements 1.3 G

176 13 48 00 03 Product Data Bracing 3.1 G

177 13 48 00 03 Product Data Equipment Requirements 1.3 G

178 13 48 00 06 Test Reports Anchor Bolts 3.3 G

179 22 00 00 03 Product Data Fixtures 2.4

180 22 00 00 03 Product Data Service sinks 2.4.1

181 22 00 00 03 Product Data Backflow prevention assemblies 3.7.1.1 G

182 22 00 00 06 Test Reports Tests, Flushing and Disinfection 3.7

2 SEP 2011

Trans-mittal

Specification

Section

SD

SD Description Item Submitted Paragraph

Classi-fication:

GOVT or

A/E

Revwr

Submit Approval

Needed

By

Material

Needed

By

Action

Code

Date Of

Action

Date

FWD to

APPR /

Auth -

Date

RCD

From

CONTR

Date

FWD To

Other

Revwr

Date

RCD

From

Other

Revwr

Action

Code

Date Of

Action

Mailed To

CONTR/

Date

RCD

From

APPR

Authority

Remarks

CONTRACTOR

SCHEDULE DATES

CONTRACTOR

ACTION

APPROVING AUTHORITY

TITLE: Renovate Bldg 237, Bay D

SUBMITTAL REGISTERLOCATION: Travis Air Force Base, California

CONTRACT NO:

183 22 00 00 06 Test Reports Test of Backflow Prevention

Assemblies

3.7.1.1

184 22 00 00 06 Test Reports AE

185 22 00 00 07 Certificates Materials and Equipment 1.3

186 22 00 00 07 Certificates Bolts 2.1.1

187 22 00 00 10 Operation and Maintenance

Data

Plumbing System 3.7.1

188 22 00 00 10 Operation and Maintenance

Data

AE

189 23 00 00 02 Shop Drawings Detail Drawings 1.4.5 G

190 23 00 00 03 Product Data Metallic Flexible Duct

191 23 00 00 03 Product Data Insulated Nonmetallic Flexible Duct

Runouts

2.8.1.1

192 23 00 00 03 Product Data Duct Connectors 2.8.1.1

193 23 00 00 03 Product Data Duct Access Doors 2.8.2

194 23 00 00 03 Product Data Fire Dampers 2.8.3

195 23 00 00 03 Product Data Manual Balancing Dampers 2.8.4

196 23 00 00 03 Product Data Manual Balancing Dampers 2.8.5

197 23 00 00 03 Product Data Automatic Smoke-Fire Dampers 2.8.7

198 23 00 00 03 Product Data Automatic Smoke Dampers

199 23 00 00 03 Product Data Acoustical Duct Liner 2.8.11

200 23 00 00 03 Product Data Diffusers 2.8.12.1

201 23 00 00 03 Product Data Registers and Grilles 2.8.12.3

202 23 00 00 03 Product Data Louvers

203 23 00 00 03 Product Data Air Vents, Penthouses, and

Goosenecks

204 23 00 00 03 Product Data Ceiling Exhaust Fans

205 23 00 00 03 Product Data Air Handling Units G

206 23 00 00 03 Product Data Diagrams 1.2.1.2 G

207 23 00 00 06 Test Reports Performance Tests 3.12 G

208 23 00 00 07 Certificates Certification

209 23 00 00 08 Manufacturer’s Instructions Manufacturer's Installation

Instructions

3.2

2 SEP 2011

Trans-mittal

Specification

Section

SD

SD Description Item Submitted Paragraph

Classi-fication:

GOVT or

A/E

Revwr

Submit Approval

Needed

By

Material

Needed

By

Action

Code

Date Of

Action

Date

FWD to

APPR /

Auth -

Date

RCD

From

CONTR

Date

FWD To

Other

Revwr

Date

RCD

From

Other

Revwr

Action

Code

Date Of

Action

Mailed To

CONTR/

Date

RCD

From

APPR

Authority

Remarks

CONTRACTOR

SCHEDULE DATES

CONTRACTOR

ACTION

APPROVING AUTHORITY

TITLE: Renovate Bldg 237, Bay D

SUBMITTAL REGISTERLOCATION: Travis Air Force Base, California

CONTRACT NO:

210 23 00 00 08 Manufacturer’s Instructions Operation and Maintenance

Training

3.14.2

211 23 00 00 10 Operation and Maintenance

Data

Operation and Maintenance

Manuals

3.14.1

212 23 00 00 10 Operation and Maintenance

Data

Fire Dampers 2.8.3 G

213 23 00 00 10 Operation and Maintenance

Data

Manual Balancing Dampers 2.8.4 G

214 23 00 00 10 Operation and Maintenance

Data

Manual Balancing Dampers 2.8.5 G

215 23 00 00 10 Operation and Maintenance

Data

Automatic Smoke-Fire Dampers 2.8.7 G

216 23 00 00 10 Operation and Maintenance

Data

Automatic Smoke Dampers G

217 23 00 00 10 Operation and Maintenance

Data

Ceiling Exhaust Fans G

218 23 00 00 10 Operation and Maintenance

Data

Air Handling Units G

219 23 03 00.00 20 03 Product Data Certification

220 23 05 93 01 Preconstruction Submittals TAB Firm 1.5.4.1

221 23 05 93 01 Preconstruction Submittals TAB team assistants 1.2

222 23 05 93 01 Preconstruction Submittals TAB team engineer 1.2

223 23 05 93 01 Preconstruction Submittals TAB team field leader 1.2

224 23 05 93 02 Shop Drawings TAB Schematic Drawings and

Report Forms

1.3.2

225 23 05 93 03 Product Data Equipment and Performance Data 1.3

226 23 05 93 03 Product Data TAB Related HVAC Submittals 1.5.4.4

227 23 05 93 03 Product Data TAB Procedures 1.5.2

228 23 05 93 03 Product Data Calibration 1.5.2

229 23 05 93 03 Product Data Systems Readiness Check 1.3.2

230 23 05 93 03 Product Data TAB Execution 1.5.5

231 23 05 93 03 Product Data TAB Verification

232 23 05 93 06 Test Reports TAB Work Execution Schedule 3.6 G

233 23 05 93 06 Test Reports TAB Procedures Summary G

234 23 05 93 06 Test Reports Design review report 1.3.2 G

235 23 05 93 06 Test Reports Design review report 1.7.3.1 G

2 SEP 2011

Trans-mittal

Specification

Section

SD

SD Description Item Submitted Paragraph

Classi-fication:

GOVT or

A/E

Revwr

Submit Approval

Needed

By

Material

Needed

By

Action

Code

Date Of

Action

Date

FWD to

APPR /

Auth -

Date

RCD

From

CONTR

Date

FWD To

Other

Revwr

Date

RCD

From

Other

Revwr

Action

Code

Date Of

Action

Mailed To

CONTR/

Date

RCD

From

APPR

Authority

Remarks

CONTRACTOR

SCHEDULE DATES

CONTRACTOR

ACTION

APPROVING AUTHORITY

TITLE: Renovate Bldg 237, Bay D

SUBMITTAL REGISTERLOCATION: Travis Air Force Base, California

CONTRACT NO:

236 23 05 93 06 Test Reports Design review report 3.6 G

237 23 05 93 06 Test Reports TAB report for Season 1 1.5.6.2 G

238 23 05 93 06 Test Reports TAB report for Season 1 3.6 G

239 23 05 93 06 Test Reports TAB report for Season 2 1.5.6.2 G

240 23 05 93 06 Test Reports TAB report for Season 2 3.6 G

241 23 05 93 07 Certificates Independent TAB agency and personnel qualifications

1.5.1 G

242 23 05 93 07 Certificates Completed Season 1 Pre-TAB

Work Checklist

3.6

243 23 05 93 07 Certificates Completed Season 1 Pre-TAB

Work Checklist

3.6

244 23 05 93 07 Certificates TAB Firm 1.5.4.1

245 23 05 93 07 Certificates TAB Submittal and Work Schedule 1.7.1

246 23 05 93 07 Certificates TAB Submittal and Work Schedule 1.7.3

247 23 05 93 07 Certificates Design review report 1.3.2

248 23 05 93 07 Certificates Design review report 1.7.3.1

249 23 05 93 07 Certificates Design review report 3.6

250 23 05 93 07 Certificates Prerequisite HVAC Work Check

Out List

251 23 07 00 02 Shop Drawings Duct Insulation Systems 3.2

252 23 07 00 03 Product Data Certification 1.4.2

253 23 07 00 03 Product Data Duct Insulation Systems 3.2 G

254 23 07 00 04 Samples Thermal Insulation 2.2.1.3

255 23 07 00 08 Manufacturer’s Instructions Duct Insulation Systems 3.2 G

256 23 31 13.00 40 01 Preconstruction Submittals Material, Equipment, and Fixture

Lists

1.5

257 23 31 13.00 40 01 Preconstruction Submittals Records of Existing Conditions 1.5

258 23 31 13.00 40 02 Shop Drawings Connection Diagrams 1.3

259 23 31 13.00 40 02 Shop Drawings Connection Diagrams 1.6

260 23 31 13.00 40 02 Shop Drawings Record Drawings 1.6

261 23 31 13.00 40 03 Product Data Equipment and Performance Data 1.2

262 23 31 13.00 40 03 Product Data Galvanized Steel Ductwork

Materials

2.1.1

2 SEP 2011

Trans-mittal

Specification

Section

SD

SD Description Item Submitted Paragraph

Classi-fication:

GOVT or

A/E

Revwr

Submit Approval

Needed

By

Material

Needed

By

Action

Code

Date Of

Action

Date

FWD to

APPR /

Auth -

Date

RCD

From

CONTR

Date

FWD To

Other

Revwr

Date

RCD

From

Other

Revwr

Action

Code

Date Of

Action

Mailed To

CONTR/

Date

RCD

From

APPR

Authority

Remarks

CONTRACTOR

SCHEDULE DATES

CONTRACTOR

ACTION

APPROVING AUTHORITY

TITLE: Renovate Bldg 237, Bay D

SUBMITTAL REGISTERLOCATION: Travis Air Force Base, California

CONTRACT NO:

263 23 31 13.00 40 03 Product Data Brazing Materials 2.1.2

264 23 31 13.00 40 03 Product Data Mill-Rolled Reinforcing and

Supporting Materials

2.1.3

265 23 31 13.00 40 03 Product Data Round Sheet Metal Duct Fittings 2.2.1

266 23 31 13.00 40 03 Product Data Round, High-Pressure, Double-

Wall Sheet Metal Ducts

267 23 31 13.00 40 03 Product Data Turning Vanes 2.2.4

268 23 31 13.00 40 03 Product Data Sound Traps

269 23 31 13.00 40 03 Product Data Flexible Connectors 2.2.6

270 23 31 13.00 40 03 Product Data Flexible Connectors 2.2.6

271 23 31 13.00 40 03 Product Data Flexible Duct Materials 2.2.9

272 23 31 13.00 40 03 Product Data Power Operated Dampers 2.2.12

273 23 31 13.00 40 03 Product Data Fire Dampers and Wall Collars 2.2.13

274 23 31 13.00 40 03 Product Data Gravity Backdraft and Relief

Dampers

2.2.11

275 23 31 13.00 40 03 Product Data Manual Volume Dampers 2.2.10

276 23 31 13.00 40 05 Design Data Design Analysis and Calculations 1.2

277 23 31 13.00 40 05 Design Data Design Analysis and Calculations 1.3

278 23 31 13.00 40 06 Test Reports Ductwork Leakage Tests

279 23 31 13.00 40 06 Test Reports Operational Tests 3.4.1

280 23 31 13.00 40 07 Certificates Listing of Product Installations 3.2

281 23 31 13.00 40 07 Certificates Galvanized Steel Ductwork

Materials

2.1.1

282 23 31 13.00 40 07 Certificates Brazing Materials 2.1.2

283 23 31 13.00 40 07 Certificates Mill-Rolled Reinforcing and

Supporting Materials

2.1.3

284 23 31 13.00 40 07 Certificates Round Sheet Metal Duct Fittings 2.2.1

285 23 31 13.00 40 07 Certificates Round, High-Pressure, Double-

Wall Sheet Metal Ducts

286 23 31 13.00 40 07 Certificates Turning Vanes 2.2.4

287 23 31 13.00 40 07 Certificates Dampers 2.2.5

288 23 31 13.00 40 07 Certificates Sound Traps

289 23 31 13.00 40 07 Certificates Flexible Connectors 2.2.6

2 SEP 2011

Trans-mittal

Specification

Section

SD

SD Description Item Submitted Paragraph

Classi-fication:

GOVT or

A/E

Revwr

Submit Approval

Needed

By

Material

Needed

By

Action

Code

Date Of

Action

Date

FWD to

APPR /

Auth -

Date

RCD

From

CONTR

Date

FWD To

Other

Revwr

Date

RCD

From

Other

Revwr

Action

Code

Date Of

Action

Mailed To

CONTR/

Date

RCD

From

APPR

Authority

Remarks

CONTRACTOR

SCHEDULE DATES

CONTRACTOR

ACTION

APPROVING AUTHORITY

TITLE: Renovate Bldg 237, Bay D

SUBMITTAL REGISTERLOCATION: Travis Air Force Base, California

CONTRACT NO:

290 23 31 13.00 40 10 Operation and Maintenance

Data

Operation and Maintenance

Manuals

3.6

291 23 31 13.00 40 10 Operation and Maintenance

Data

Power Operated Dampers 2.2.12

292 23 31 13.00 40 10 Operation and Maintenance

Data

Fire Dampers and Wall Collars 2.2.13

293 23 74 33.00 40 02 Shop Drawings Packaged Unit

294 23 74 33.00 40 02 Shop Drawings Compressor

295 23 74 33.00 40 02 Shop Drawings Cooling Coil

296 23 74 33.00 40 02 Shop Drawings Controls

297 23 74 33.00 40 02 Shop Drawings Casing

298 23 74 33.00 40 02 Shop Drawings Condenser

299 23 74 33.00 40 02 Shop Drawings Installation Drawings 3.1

300 23 74 33.00 40 03 Product Data Equipment and Performance Data 1.3

301 23 74 33.00 40 03 Product Data Air-Conditioning Systems 3.2.1

302 23 74 33.00 40 03 Product Data Compressor

303 23 74 33.00 40 03 Product Data Cooling Coil

304 23 74 33.00 40 03 Product Data Fans

305 23 74 33.00 40 03 Product Data Controls

306 23 74 33.00 40 03 Product Data Casing

307 23 74 33.00 40 03 Product Data Filters

308 23 74 33.00 40 03 Product Data Condenser

309 23 74 33.00 40 03 Product Data Vibration Isolation

310 23 74 33.00 40 07 Certificates Listing of Product Installations 3.1

311 23 74 33.00 40 10 Operation and Maintenance

Data

Operation and Maintenance

Manuals

3.3

312 26 05 00.00 40 01 Preconstruction Submittals Material, Equipment, and Fixture

Lists

1.5

313 26 05 00.00 40 01 Preconstruction Submittals Conduits, Raceway sand Fittings 3.1

314 26 05 00.00 40 01 Preconstruction Submittals Wire and Cable 2.2

315 26 05 00.00 40 01 Preconstruction Submittals Splices and Connectors 2.3

316 26 05 00.00 40 01 Preconstruction Submittals Switches 2.4

2 SEP 2011

Trans-mittal

Specification

Section

SD

SD Description Item Submitted Paragraph

Classi-fication:

GOVT or

A/E

Revwr

Submit Approval

Needed

By

Material

Needed

By

Action

Code

Date Of

Action

Date

FWD to

APPR /

Auth -

Date

RCD

From

CONTR

Date

FWD To

Other

Revwr

Date

RCD

From

Other

Revwr

Action

Code

Date Of

Action

Mailed To

CONTR/

Date

RCD

From

APPR

Authority

Remarks

CONTRACTOR

SCHEDULE DATES

CONTRACTOR

ACTION

APPROVING AUTHORITY

TITLE: Renovate Bldg 237, Bay D

SUBMITTAL REGISTERLOCATION: Travis Air Force Base, California

CONTRACT NO:

317 26 05 00.00 40 01 Preconstruction Submittals Receptacles 2.5

318 26 05 00.00 40 01 Preconstruction Submittals Outlets, Outlet Boxes, and Pull

Boxes

2.6

319 26 05 00.00 40 01 Preconstruction Submittals Circuit Breakers 2.7

320 26 05 00.00 40 01 Preconstruction Submittals Lamps and Lighting Fixtures 2.8

321 26 05 00.00 40 03 Product Data Conduits, Raceway sand Fittings 3.1

322 26 05 00.00 40 03 Product Data Wire and Cable 2.2

323 26 05 00.00 40 03 Product Data Splices and Connectors 2.3

324 26 05 00.00 40 03 Product Data Switches 2.4

325 26 05 00.00 40 03 Product Data Receptacles 2.5

326 26 05 00.00 40 03 Product Data Outlets, Outlet Boxes, and Pull

Boxes

2.6

327 26 05 00.00 40 03 Product Data Circuit Breakers 2.7

328 26 05 00.00 40 03 Product Data Lamps and Lighting Fixtures 2.8

329 26 05 00.00 40 03 Product Data Spare Parts 1.4

330 26 05 00.00 40 03 Product Data Certification 1.5

331 26 05 00.00 40 06 Test Reports Continuity Test 3.9

332 26 05 00.00 40 06 Test Reports Phase-Rotation Tests 3.9

333 26 05 00.00 40 06 Test Reports Insulation Resistance Test 3.9

334 26 05 00.00 40 08 Manufacturer’s Instructions Manufacturer's Instructions 1.5

335 26 05 48.00 10 02 Shop Drawings Lighting Fixtures in Buildings 3.2

336 26 05 48.00 10 03 Product Data Lighting Fixtures in Buildings 3.2

337 26 05 48.00 10 03 Product Data Contractor Designed Bracing 1.2.4

338 26 51 00 03 Product Data Fluorescent lighting fixtures 2.1

339 26 51 00 03 Product Data AE

340 26 51 00 03 Product Data Fluorescent electronic ballasts 1.6.1

341 26 51 00 03 Product Data Fluorescent lamps 2.1.2

342 26 51 00 03 Product Data Exit signs 2.3

343 26 51 00 03 Product Data Emergency lighting equipment 2.4

344 26 51 00 03 Product Data Occupancy sensors 2.5

2 SEP 2011

Trans-mittal

Specification

Section

SD

SD Description Item Submitted Paragraph

Classi-fication:

GOVT or

A/E

Revwr

Submit Approval

Needed

By

Material

Needed

By

Action

Code

Date Of

Action

Date

FWD to

APPR /

Auth -

Date

RCD

From

CONTR

Date

FWD To

Other

Revwr

Date

RCD

From

Other

Revwr

Action

Code

Date Of

Action

Mailed To

CONTR/

Date

RCD

From

APPR

Authority

Remarks

CONTRACTOR

SCHEDULE DATES

CONTRACTOR

ACTION

APPROVING AUTHORITY

TITLE: Renovate Bldg 237, Bay D

SUBMITTAL REGISTERLOCATION: Travis Air Force Base, California

CONTRACT NO:

345 26 51 00 06 Test Reports Operating test 3.3

346 26 51 00 10 Operation and Maintenance

Data

Lighting Control System 1.4.1 G AE

347 26 51 00 10 Operation and Maintenance

Data

Operational Service

348 28 31 74.00 20 02 Shop Drawings System floor plans 1.6.3.1 G

349 28 31 74.00 20 02 Shop Drawings System wiring diagrams 1.6.3.2 G

350 28 31 74.00 20 02 Shop Drawings Conductor wire marker schedule 3.1 G

351 28 31 74.00 20 03 Product Data Control panel G

352 28 31 74.00 20 03 Product Data Storage batteries 2.1.3.1 G

353 28 31 74.00 20 03 Product Data Battery charger 2.1.3.2 G

354 28 31 74.00 20 03 Product Data Manual pull stations 2.2.1 G

355 28 31 74.00 20 03 Product Data Heat detectors 2.2.2 G

356 28 31 74.00 20 03 Product Data Open-area (spot-type) smoke detectors

G

357 28 31 74.00 20 03 Product Data Duct smoke detectors 2.2.3 G

358 28 31 74.00 20 03 Product Data Alarm horns 2.2.4.1 G

359 28 31 74.00 20 03 Product Data Visible appliances 2.2.4.2 G

360 28 31 74.00 20 03 Product Data Wiring 2.2.8 G

361 28 31 74.00 20 03 Product Data Conduit 2.2.5

362 28 31 74.00 20 03 Product Data Outlet boxes 2.2.6

363 28 31 74.00 20 03 Product Data Fittings for conduit and outlet boxes 2.2.7

364 28 31 74.00 20 05 Design Data Power calculations 1.4.1.1 G

365 28 31 74.00 20 06 Test Reports 2-wire smoke detectors G

366 28 31 74.00 20 06 Test Reports Preliminary testing 3.2.1 G

367 28 31 74.00 20 06 Test Reports Final acceptance testing 3.2.2 G

368 28 31 74.00 20 07 Certificates Qualifications of installer 1.6.1 G

369 28 31 74.00 20 10 Operation and Maintenance

Data

Fire alarm system 2.1.1 G

370 28 31 74.00 20 11 Closeout Submittals System as-built drawings 1.6.3.3 G

2 SEP 2011

File details come from the government source that posted it. Updated .