ASBESTOS & LEAD BASED
PAINT SURVEY REPORT
REPAIR ACTIVE VEHICLE BARRIERS, POST 4
JOINT BASE CHARLESTON, SC
PROJECT NUMBER: DKGV 13-2150
23 FEBRUARY 2017
Contract No.: FA4418-15-D-0007
Task Order: 0001
CEMS No.: 15-154C
Asbestos & Lead Paint Survey Report Building 3210
Weapons Station-Joint Base Charleston, South Carolina North Charleston, South Carolina
February 21, 2017 Terracon Project No. EN177060
Prepared for:
CEMS Engineering, Inc.
Charleston, South Carolina
Prepared by:
Terracon Consultants, Inc.
North Charleston, South Carolina
Inspected by:
Craig C. Langford (SC ASB-22775)
Terracon Consul tants, Inc. 1450 Fif th Street, West North Char leston, South Carol ina 29405 P [843] 884 1234 F [843] 884 9234 terracon.com
February 21, 2017
CEMS Engineering, Inc.
540 East Bay Street Charleston, South Carolina 29403
Attn: Russell Patterson Email: rpatterson@cems-ae.com
Re: Asbestos and Lead Paint Survey Report Building 3210 -Weapons Station-Joint Base Charleston North Charleston, South Carolina 29405 Terracon Project No. EN177060 CEMS Project No. 15-154C, AVB Post 4
Dear Mr. Thompson:
Terracon Consultants, Inc. (Terracon) is pleased to present the results of the asbestos and lead paint survey performed on February 6, 2017 of Building 3210 located on the Weapons Station-Joint Base Charleston in North Charleston, South Carolina. We understand that this survey was requested due to the planned demolition of the structure.
Terracon appreciates the opportunity to provide environmental consulting services for the CEMS Engineering, Inc. If you should have any questions regarding this report, or if you need assistance with bid documents or project oversight during the demolitions, please contact the undersigned at (843) 884-1234.
Sincerely, Terracon Consultants, Inc.
Craig C. Langford Gene Partin, CHMM Senior Staff Industrial Hygienist Approved Project Reviewer
Responsive ■ Resourceful ■ Reliable
TABLE OF CONTENTS
EXECUTIVE SUMMARY
1.0 INTRODUCTION
2.0 BUILDING DESCRIPTION
3.0 ASBESTOS SURVEY
3.1 Regulatory Overview
3.2 Visual Assessment
3.3 Physical Assessment
3.4 Sample Collection
3.5 Sample Analysis
3.6 Findings and Recommendations
4.0 LEAD-BASED PAINT SURVEY
4.1 Regulatory Overview
4.2 Sampling and Analytical Protocol ................... Error! Bookmark not defined.
4.3 Findings and Recommendations
5.0 LIMITATIONS / GENERAL COMMENTS
LIST OF APPENDICES
APPENDIX A - TABLES
Table 1 – Asbestos Survey Sample Summary
APPENDIX B – LABORATORY REPORTS
Asbestos Analytical Laboratory Data
APPENDIX C – INSPECTORS CREDENTIALS
Asbestos and LBP Survey Report Building 3210 ■ North Charleston, South Carolina February 21, 2017 ■ Terracon Project No. EN177060
Responsive ■ Resourceful ■ Reliable 1
EXECUTIVE SUMMARY
This executive summary is intended as an overview for the convenience of the reader. The report should be reviewed in its entirety prior to making any decisions regarding this site.
Terracon Consultants, Inc. (Terracon) conducted an asbestos and lead paint survey of Building 3210 located on the Weapons Station-Joint Base Charleston in North Charleston, South Carolina.
The structure is approximately 120 square-feet, constructed of decorative concrete block walls, concrete floor and a pitched, shingled roof. The date of construction is unknown. It was our understanding that structure is scheduled for demolition. The purpose of this survey was to sample and identify suspect asbestos-containing materials (ACM) and provide information regarding the identity, location, condition and approximate quantities of ACM in both interior and exterior building components.
The survey was performed on February 6, 2017 by a South Carolina Department of Health and Environmental Control (SCDHEC) licensed asbestos inspector in general accordance with our CEMS work order dated January 23, 2017 and the sampling protocols established in EPA 40 CFR 763 (Asbestos Hazard Emergency Response Act, AHERA) and the SCDHEC Regulation 61-86.1 Standards of Performance for Asbestos Projects.
Nine (9) bulk samples were collected from homogeneous areas of suspect ACM. Based on the results of laboratory analysis, none of the suspect materials sampled contained asbestos at concentrations greater than one percent (>1%); therefore they are non-ACM.
Paint was not observed on any buildings materials within the structure, therefore paint chip samples for lead analysis were not collected.
Responsive ■ Resourceful ■ Reliable 2
ASBESTOS & LEAD PAINT SURVEY REPORT
Building 3210 -Weapons Station-Joint Base Charleston
North Charleston, South Carolina 29405 Terracon Project No. EN177060
CEMS Project No. 15-154C, AVB Post 4 INSPECTION DATE: February 6, 2017
REPORT DATE: February 21, 2016
1.0 INTRODUCTION
Terracon Consultants, Inc. (Terracon) conducted an asbestos and lead paint survey of Building 3210 located on the Weapons Station-Joint Base Charleston in North Charleston, South Carolina.
The structure is approximately 120 square-feet, constructed of decorative concrete block walls, concrete floor and a pitched, shingled roof. The survey was conducted on February 6, 2017, by a South Carolina Department of Health and Environmental Control (SCDHEC) licensed building inspector in general accordance with our CEMS work order dated January 23, 2017.
We understand the asbestos survey was requested due to the scheduled demolition of the building. Environmental Protection Agency (EPA) regulation 40 CFR 61, Subpart M, National Emission Standards for Hazardous Air Pollutants (NESHAP), prohibits the release of asbestos fibers to the atmosphere during renovation/demolition activities. NESHAP requires that potentially regulated asbestos-containing building materials be identified, classified and quantified prior to planned disturbances or demolition activities.
Suspect ACM was sampled in general accordance with the sampling protocols outlined in EPA Regulation 40 CFR 763 Subpart E763.86 (Asbestos Hazard Emergency Response Act, AHERA) and SCDHEC Regulation 61-86.1 Standards of Performance for Asbestos Projects. Interior and exterior building components were surveyed and homogeneous areas of suspect asbestos-containing materials (ACM) were visually identified and documented. Although reasonable effort was made to survey accessible suspect materials, additional suspect but un-sampled materials could be located in walls, in voids or in other concealed areas. Samples were delivered to an accredited laboratory for analysis by Polarized Light Microscopy (PLM) and Transmission Electron Microscopy (TEM), as required.
2.0 BUILDING DESCRIPTION
The structure is approximately 120 square-feet constructed of decorative concrete block walls, concrete floor, and a pitched, shingled roof. The date of construction is unknown. Interior finishes consist of decorative concrete block walls, wood panel ceiling, and a concrete floor.
The building is heated and cooled by a window unit.
February 21, 2017 ■ Terracon Project No. EN177060
Responsive ■ Resourceful ■ Reliable 3
3.0 ASBESTOS SURVEY
The asbestos survey was conducted by SCDHEC licensed Asbestos Building Inspector(s) Mr.
Craig C. Langford (License No. ASB-22775, exp. 8/02/17). A copy of Mr. Langford’s license is included in Appendix C. The survey was conducted on February 6, 2017 in general accordance with the sampling protocols established by EPA Regulation 40 CFR 763 Subpart E 763.86, AHERA and SCDHEC R61-86.1. A summary of survey activities is provided below.
3.1 Regulatory Overview
An ACM is defined as any material containing asbestos of any type in an amount greater than one percent (1%). The asbestos NESHAP (40 CFR Part 61, Subpart M) regulates asbestos fiber emissions and asbestos waste disposal practices. It also requires the identification and classification of existing building materials prior to demolition or renovation activity. Under NESHAP, asbestos-containing building materials are classified as either friable, Category I non-friable or Category II non-friable ACM. Friable materials are those that, when dry, may be crumbled, pulverized or reduced to powder by hand pressure. Category I non friable ACM includes packing materials, gaskets, resilient floor coverings and asphalt roofing products containing more than 1 percent (%) asbestos. Category II non-friable ACM are non-friable materials other than Category I materials that contain more than 1% asbestos.
Friable ACM, Category I and Category II non-friable ACM which is in poor condition and has become friable or which will be subjected to drilling, sanding, grinding, cutting or abrading and which could be crushed or pulverized during anticipated renovation/demolition activities are considered regulated ACM (RACM). RACM must be removed prior to renovation or demolition activities.
In the state of South Carolina, asbestos activities are regulated by the SCDHEC under the SCDHEC Regulation 61-86.1 Standards of Performance for Asbestos Projects. The SCDHEC require that any asbestos-related activity conducted in a public building be performed by personnel licensed by the SCDHEC. The owner or operator must provide the SCDHEC with written notification of planned abatement and removal activities prior to the commencement of those activities. The SCDHEC requires 4 day notification for non-friable projects and 10 day notification for RACM projects. Asbestos abatement must be performed by SCDHEC-licensed asbestos abatement contractors. A SCDHEC-licensed Project Designer shall prepare a written abatement design for each abatement renovation project involving the removal of greater than 3,000 square, 1,500 linear, or 656 cubic feet of RACM. Third-party air monitoring must be conducted during the abatement of friable (regulated) ACM. The SCDHEC asbestos regulations can be found at http://www.scdhec.gov.
The Occupational Safety and Health Administration (OSHA) Asbestos Standard for Construction Industry (29 CFR 1926.1101) regulates workplace exposure to asbestos. The OSHA standard requires that employee exposure to airborne asbestos fibers be maintained below 0.1 asbestos
February 21, 2017 ■ Terracon Project No. EN177060
Responsive ■ Resourceful ■ Reliable 4 fibers per cubic centimeter of air (0.1 f/cc) for an eight-hour timed weighed average. The OSHA standard classifies construction and maintenance activities, which could disturb ACM, and specifies work practices and precautions which employers must follow when engaging in each class of regulated work. A full copy of the OSHA asbestos standard for general industry may be found at OSHA’s website (www.osha.gov) and should be referenced for specific information.
3.2 Visual Assessment
Our survey activities began with visual observation of the interior and exterior of the building to identify apparent homogeneous areas of suspect ACM. A homogeneous area consists of building materials, which appear similar throughout in terms of color, texture and date of application.
Building materials which were not identified as concrete, glass, wood, masonry, metal or rubber were considered suspect ACM.
3.3 Physical Assessment
A physical assessment of each homogeneous area of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the EPA as a material, which can be crumbled, pulverized or reduced to powder by hand pressure when dry. Friability was assessed by physically touching suspect materials.
3.4 Sample Collection
Based on our visual observations, bulk samples of suspect ACM were collected in general accordance with SCDHEC sample collection protocols. Random samples of suspect materials were collected in each homogeneous area. Bulk samples were collected using wet methods as applicable to reduce the potential for fiber release. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker.
The selection of sample locations and frequency of sampling was based on Terracon’s observations and the assumption that like materials in the same area are homogeneous in content.
A summary of the suspect ACM samples collected during the survey is presented in Table 1 in Appendix A.
February 21, 2017 ■ Terracon Project No. EN177060
Responsive ■ Resourceful ■ Reliable 5
3.5 Sample Analysis
Bulk samples were submitted under chain of custody to EMSL Analytical, Inc. of Kernersville, North Carolina for analysis by Polarized Light Microscopy (PLM) with dispersion staining techniques per EPA EPA/600/R-93/116. The percentage of asbestos, where applicable, was determined by microscopical visual estimation. EMSL is accredited under the National Voluntary Laboratory Accreditation Program (NVLAP).
Per the SCDHEC Regulation 61-86.1 Standards of Performance for Asbestos Projects, negative results for non-friable organically bound (NOB) materials such as flooring and roofing shall be verified with at least one TEM analysis. The additional analysis was performed by TEM in accordance with EPA/600/R-93/116 Section 2.5.5.1.
3.6 Findings and Recommendations
Table 1 in the Appendix A summarizes the results of the visual inspection, estimated quantities, and laboratory analyses. Asbestos laboratory analytical reports are included in Appendix B
Based on the results of laboratory analysis, none of the suspect materials sampled contained asbestos at concentrations greater than one percent (>1%); therefore they are non-ACM.
A copy of this report must be submitted to SCDHEC at least ten (10) working days prior to demolition when applying for a demolition permit. Federal, state and local regulations should be referred to in order to verify compliance before any actions are initiated on an ACM.
In accordance with OSHA's Asbestos Standard, the employer shall notify affected employees and contractors of the presence and location of asbestos-containing materials and test results. A full copy of the OSHA asbestos standard for general industry may be found at OSHA’s website (www.osha.gov) and should be referenced for specific information.
It should be noted that suspect materials, other than those identified during the February 6, 2017 survey may exist within the structure. Should suspect materials other than those which were identified during this survey be uncovered during or prior to the abatement and demolition process, those materials should be assumed asbestos-containing until sampling and analysis can confirm or refute their asbestos content. Should future sampling indicate that the other material is asbestos containing, Terracon recommends removal of the asbestos-containing materials by a South Carolina licensed asbestos abatement contractor prior to renovation/demolition of the building.
February 21, 2017 ■ Terracon Project No. EN177060
Responsive ■ Resourceful ■ Reliable 6
4.0 LEAD-BASED PAINT SURVEY
4.1 Regulatory Overview
Lead is regulated by the EPA, SCDHEC and OSHA. The EPA and SCDHEC regulate lead use, removal, and disposal, and OSHA regulates lead exposure to workers. The EPA defines LBP as paint, varnish, stain, or other applied coating that contains lead equal to or greater than 1.0 mg/cm2, 5,000 mg/kg, or 0.5% by dry weight as determined by laboratory analysis. The SCDHEC regulations 61-107.19 require that painted demolition debris with a lead concentration greater than 0.06% by weight be disposed in a permitted Class II landfill. For the purpose of the OSHA lead standard, lead includes metallic lead, all inorganic lead compounds, and organic lead soaps. The complete OSHA standard for compliance can be found on OSHA’s website (www.osha.gov). A synopsis of the OSHA regulations (29 CFR 1926.62) and the applicability are as follows:
The OSHA Lead Standard for Construction (29 CFR 1926.62) applies to all construction work where an employee may be occupationally exposed to lead. All work related to construction, alteration, or repair (including painting and decorating) is included. The lead-in-construction standard applies to any detectable concentration of lead in paint, as even small concentrations of lead can result in unacceptable employee exposures depending upon on the method of removal and other workplace conditions. Under this standard, construction includes, but is not limited to, the following:
§ Demolition or salvage of structures where lead or materials containing lead are present § Removal or encapsulation of materials containing lead § New construction, alteration, repair, or renovation of structures, substrates, or portions containing lead, or materials containing lead § Installation of products containing lead § Lead contamination/emergency clean-up § Transportation, disposal, storage, or containment of lead or materials containing lead on the site or location at which construction activities are performed § Maintenance operations associated with construction activities described above
4.2 Findings and Recommendations
Paint was not observed on any buildings materials within the structure, therefore paint chip samples were not collected. Materials, concrete brick and wood trim, appeared to be tinted/colored during manufacture.
February 21, 2017 ■ Terracon Project No. EN177060
Responsive ■ Resourceful ■ Reliable 7
5.0 LIMITATIONS / GENERAL COMMENTS
This survey was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions and recommendations expressed in this report are based on conditions observed during our survey of the building.
The information contained in this report is relevant to the date on which this survey was performed, and should not be relied upon to represent conditions at a later date. This report has been prepared on behalf of and exclusively for use by CEMS for specific application to their project as discussed. Terracon does not warrant the work of regulatory agencies, laboratories or other third parties supplying information, which may have been used in the preparation of this report. No warranty, expressed or implied is made.
This report is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding further investigation or remediation deemed necessary.
CEMS Project – AVB Post 4 Buidling 3210 – Weapons Station-JBC Terracon Project No. EN177060
Photo #1 View of Front of Building Photo #2 View of Floor
Photo #3 View of Ceiling Photo #4 View of Ceiling
Photo #5 View of exterior Photo #6 View of rear of building
APPENDIX A
TABLES
WC-01 Exterior Windows PLM None Detected
WC-02 Exterior Windows PLM None Detected
WC-03 Exterior Windows TEM None Detected
RM-01 Roof Shingle PLM None Detected
RM-02 Roof Shingle PLM None Detected
RM-03 Roof Shingle TEM None Detected
RM-01 Roof Felt PLM None Detected
RM-02 Roof Felt PLM None Detected
RM-03 Roof Felt TEM None Detected
SF - Square Feet LF - Linear Feet
HA - Homogeneous Area PLM - Polarized Light Microscopy
TEM - Transmission Electron Microscopy
1) Quantities listed above are applicable to the path of construction only, they are not conclusive for the entire building.
2) Quantities listed above are estimates to be used for inspection purposes only and should be field-verified for all other uses.
Estimated Quantity
(Square Feet)
TABLE 1
ASBESTOS RESULTS SAMPLE SUMMARY
CEMS PROJECT - AVB POST 4
CHARLESTON, SOUTH CAROLINA
TERRACON PROJECT NO. EN177060
BUILDING 3210
Sample Number
Sample Description HASample Location Analysis
Method Classification
Friable/Non- Friable & Current
Condition
Caulking
Shingle
Category I Non-friable/Good
Category I
Felt
HA-01
HA-02
HA-03
Analytical Results
Category I
150 LF
Non-friable/Good 120 SF
Non-friable/Good 120 SF
APPENDIX B
LABORATORY REPORTS
EMSL Analytical, Inc.
706 Gralin Street Kernersville, NC 27284
Tel/Fax: (336) 992-1025 / (336) 992-4175 http://www.EMSL.com / greensborolab@emsl.com
021700778EMSL Order:
Customer ID: WPCE62
Customer PO: CEMS Bldg 3210
Project ID:
Attention: Phone:Craig Langford (843) 442-6658
Fax:Terracon, Inc. (843) 884-9234
Received Date:1450 Fifth Street West 02/07/2017 9:00 AM
Analysis Date:North Charleston, SC 29405 02/08/2017
Collected Date: 02/06/2017
Project: CEMS Bldg 3210
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
WC-01
021700778-0001
None DetectedNon-fibrous (Other)100%Cellulose<1%Gray
Non-Fibrous
Homogeneous
Window Caulk
WC-02
021700778-0002
None DetectedNon-fibrous (Other)100%Cellulose<1%Brown
Non-Fibrous
Homogeneous
Window Caulk
RM-01-Shingle
021700778-0004
None DetectedNon-fibrous (Other)92%Glass8%Gray/Red/Black
Fibrous
Homogeneous
Shingle/Felt
RM-01-Felt
021700778-0004A
None DetectedNon-fibrous (Other)30%Cellulose70%Black
Non-Fibrous
Homogeneous
Shingle/Felt
RM-02-Shingle
021700778-0005
None DetectedNon-fibrous (Other)92%Cellulose
Glass
<1%
8%
Brown/Tan/Black
Fibrous
Heterogeneous
Shingle/Felt
RM-02-Felt
021700778-0005A
None DetectedNon-fibrous (Other)30%Cellulose70%Black
Fibrous
Homogeneous
Shingle/Felt
Analyst(s)
Kristie Elliott (3)
Scott Combs (3)
Stephen Bennett, Laboratory Manager or Other Approved Signatory
EMSL maintains liability limited to cost of analysis . This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government . Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Kernersville, NC NVLAP Lab Code 102104-0, CA ELAP 2689, Virginia 3333-000228, West Virginia LT000321
Initial report from: 02/08/2017 13:56:10
Page 1 of 1ASB_PLM_0008 - 1.71 Printed: 2/8/2017 1:56 PM
EMSL Analytical, Inc.
706 Gralin Street Kernersville, NC 27284
Tel/Fax: (336) 992-1025 / (336) 992-4175 http://www.EMSL.com / greensborolab@emsl.com
EMSL Order: 021700778
Customer ID: WPCE62
Customer PO: CEMS Bldg 3210
Project ID:
Attention: Craig Langford Phone: (843) 442-6658
Terracon, Inc. Fax: (843) 884-9234
1450 Fifth Street West Received Date: 02/07/2017 9:00 AM
North Charleston, SC 29405 Analysis Date: 02/08/2017
Collected Date: 02/06/2017
CEMS Bldg 3210Project:
Test Report: Asbestos Analysis of Non-Friable Organically Bound Materials by TEM via
EPA/600/R-93/116 Section 2.5.5.1
Sample ID Description Appearance % Matrix Material % Non-Asbestos Fibers Asbestos Types
WC-03
021700778-0003
Window Caulk Gray/Black
Non-Fibrous
Homogeneous
99.5 Fibrous_Other No Asbestos Detected0.54
RM-03-Shingle
021700778-0006
Shingle/Felt Brown/Tan/Black
Fibrous
Heterogeneous
100 None No Asbestos Detected
RM-03A-Felt
021700778-0006A
Shingle/Felt Black
Fibrous
Heterogeneous
100 None No Asbestos Detected
Analyst(s)
Nicole Shutts (3) Stephen Bennett, Laboratory Manager or other approved signatory
This laboratory is not responsible for % asbestos in total sample when the residue only is submitted for analysis. The above report relates only to the items tested. This report may not be reproduced, except in full, without written approval by EMSL Analytical , Inc. Samples received in good condition unless otherwise noted. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample.
Samples analyzed by EMSL Analytical, Inc. Kernersville, NC
Initial report from: 02/08/2017 13:56:07
ASB_PLMEPANOB_0012 Printed 2/8/2017 1:56:23PM Page 1 of 1
OrderID: 021700778
Form 111—6/98
APPENDIX C
INSPECTOR CREDENTIALS
CRAIG C LANGFORD
CONSULTANT/BUILDING INSPECTOR ASB-22775 EXP 08/02/17
CONSULTANT/PROJECT DESIGNER PD-00032 EXP 08/11/17
AIR SAMPLER/MONITOR ASB-22599 08/03/17