This document contains questions and responses regarding a solicitation for an Indefinite Delivery/Indefinite Quantity construction contract for civil works at Hurlburt Field, Florida. The contract has a guaranteed minimum value of $25,000 to be fulfilled by an initial task order, with a maximum ceiling of $26 million over the life of the basic contract. A site visit for a seed project to repair sewer lines in Basin 2 will take place on March 20, 2024, with requests for base access due by March 18. The disclosure of magnitude for the seed project is between $250,000 and $500,000. The solicitation requires a bid bond of at least 20% of the bid price up to a maximum of $3 million, and has a 100% small business set-aside with firm fixed price and EPA pricing for task orders.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CIVIL WORKS IDIQ AND SEED PROJECT
FA441724R0004
QUESTIONS AND RESPONSES
QUESTION 1. Bid Bonds - It is typical to require a 20% bid or $XXX maximum amount cap. I do not see a bid bond request anywhere in the solicitation. Can you please provide clarification?
GOVT RESPONSE: Refer to Solicitation Front Page Block 13(b) – An offer Guarantee IS required. Also refer to Section L Clause 52.228-1 (pg 57). The Bid Bond is at least 20% of the bid price but shall not exceed $3M (Ref FAR 52-228-1).
The Bid Bond amount will be added to the solicitation in an Amendment after the site visit.
QUESTION 2. Seed Project - The SOW states that we are replacing two 8” PVC sanitary sewer lines with two 10” PVC lines. Drawings C101 and C102 show the abandonment of one 8” line.
Drawings C201 and C202 show installing one 8” PVC line, while drawing C203 shows 10” PVC. Please clarify.
GOVT RESPONSE: There are two (2) 8” VCP (Vitrified Clay Pipes) to be abandoned in place between three existing manholes (Between MH 7-6 to MH 7-3 and between MH 7-3 to MH 7-20).
Drawing sheet C101 shows two arrows at MH 7-6. The top arrow SHOULD have directly pointed to MH 7-6 in lieu of the 8” PVC pipe entering said MH 7-6. The remaining arrow correctly points to the 8” VCP to be abandoned.
Drawing sheet C202 near MH 7-20, it SHOULD read “ Install 10” PVC sewer line with 45 degree coupling into MH 7-20”, in lieu of the 8” PVC sewer Line as stated.
Drawing sheet C203 is correct.
Revised drawings will be added to the solicitation in an Amendment after the site visit.