Q A FA441722QC027 - Building 90021 IDS-ACS.pdf
PDF 503 KB Posted
- Attached to
- Building 90021 IDS-ACS Federal contract opportunity
- Solicitation number
- FA441722QC027
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FA441722QC027 - Consolidated Questions and Answers 22Feb22.pdf | ||
| SOW - FA441722QC027 Bldg 90021 IDS-ACS.pdf | ||
| RFQ - FA441722QC027 Bldg 90021 IDS-ACS.pdf | ||
| BNJ - Vindicator_Redacted.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FA441722QC027- Bldg. 90021 IDS-ACS Questions & Answers
9 Feb 2022
Line Solicitation Reference Section Solicitation Statement From Client
Systems Questions Customer's Response
1 General Proposal Due Date
With the current COVID-19 situation, will the Hurlburt
Field AFB allow for an extension to the due date to ensure the vendor can submit the best proposal possible?
The RFQ will be extended to 17 Feb at 1:00PM CST.
The RFQ will not be revised.
2 1.3 Equipment
The X-10 lock shall be provided by the Government for the contractor’s use in installation.
Is there a path to wire the X10 lock or was a cable already ran for connection to the ACS?
According to Wright Brother construction project manager, here is contractor installed conduit above the ceiling that provides a pathway for connection to the ACS
3 1.3 Equipment 3 Vindicator door access system (door identification reader).
The current system is a Hirsch system that would require all new panels and a new server. It is also located in an unclass comm room. Would the government consider leaving the Hirsch system in and just expanding it?
Waiting on 505CCW/IP office input.
4 1.3 Equipment 3 Vindicator door access system (door identification reader).
Are there conduit paths established to get to the downstairs door needing ACS? Are there conduit paths established to get to the 2nd floor doors needing ACS?
There is a conduit above the ceiling that provides a pathway for connection to the ACS and to the 2nd floor
What is the classification of the area? I.E open storage secret, SCIF, or SAP.
Currently area in Controlled Access Area (CAA) but once
IDS-ACS is installed and certified, 705TRS will coordinate with base resource protection off and 1 SOW/IP to recertify area and an Secret open storage area
Are you looking for 1 year maintenance or just 1 year warranty on parts and workmanship?
1 year warranty on parts and workmanship.
Is the intent to have Vindicator ACS on all three
(3) doors mentioned in the
SOW?
3 doors requires ACS systems, New main entry door with X-
10 lock, old RM201 entry door that will become an emergency exit, and 1st floor interior entry door.
FA441722QC027- Bldg. 90021 IDS-ACS Questions & Answers
9 Feb 2022
What specific credentials will be used on this system?
Credentials will be users CAC or 505CCW/IP provide swipe badge
Will the end user be supplying the credentials?
a) If the end user is NOT supplying the credentials, please provide the part number and ordering information for the cards needed.
Credentials will be users CAC or 505CCW/IP provide swipe badge
File details come from the government source that posted it. Updated .