FA441722QC027- Bldg. 90021 IDS-ACS Questions & Answers

9 Feb 2022

Line Solicitation Reference Section Solicitation Statement From Client

Systems Questions Customer's Response

1 General Proposal Due Date

With the current COVID-19 situation, will the Hurlburt

Field AFB allow for an extension to the due date to ensure the vendor can submit the best proposal possible?

The RFQ will be extended to 17 Feb at 1:00PM CST.

The RFQ will not be revised.

2 1.3 Equipment

The X-10 lock shall be provided by the Government for the contractor’s use in installation.

Is there a path to wire the X10 lock or was a cable already ran for connection to the ACS?

According to Wright Brother construction project manager, here is contractor installed conduit above the ceiling that provides a pathway for connection to the ACS

3 1.3 Equipment 3 Vindicator door access system (door identification reader).

The current system is a Hirsch system that would require all new panels and a new server. It is also located in an unclass comm room. Would the government consider leaving the Hirsch system in and just expanding it?

Waiting on 505CCW/IP office input.

4 1.3 Equipment 3 Vindicator door access system (door identification reader).

Are there conduit paths established to get to the downstairs door needing ACS? Are there conduit paths established to get to the 2nd floor doors needing ACS?

There is a conduit above the ceiling that provides a pathway for connection to the ACS and to the 2nd floor

What is the classification of the area? I.E open storage secret, SCIF, or SAP.

Currently area in Controlled Access Area (CAA) but once

IDS-ACS is installed and certified, 705TRS will coordinate with base resource protection off and 1 SOW/IP to recertify area and an Secret open storage area

Are you looking for 1 year maintenance or just 1 year warranty on parts and workmanship?

1 year warranty on parts and workmanship.

Is the intent to have Vindicator ACS on all three

(3) doors mentioned in the

SOW?

3 doors requires ACS systems, New main entry door with X-

10 lock, old RM201 entry door that will become an emergency exit, and 1st floor interior entry door.

FA441722QC027- Bldg. 90021 IDS-ACS Questions & Answers

9 Feb 2022

What specific credentials will be used on this system?

Credentials will be users CAC or 505CCW/IP provide swipe badge

Will the end user be supplying the credentials?

a) If the end user is NOT supplying the credentials, please provide the part number and ordering information for the cards needed.

Credentials will be users CAC or 505CCW/IP provide swipe badge