FTEV_12-1069_DRAWINGS_4_Aug_2017.pdf

PDF 11 MB Posted

Attached to
Repair 12. 47 KV Electrical Basewide Federal contract opportunity
Solicitation number
FA4417-17-R-0010
Issued by
Department of the Air Force Special Operations Command

About this file

Revised Drawings

View the file

Other files for this federal contract opportunity

Other files attached to Repair 12. 47 KV Electrical Basewide, newest first.
File Type Posted
QUESTION_AND_ANSWER_CONCERNING_PROPOSAL_SUBMISSION.docx DOCX document
FA441717R00100002.pdf PDF
ADDENDUM_1.pdf PDF
FTEV_12-1069_SPECIFICATIONS_-_4_Aug_2017.pdf PDF
Questions_and_Answers.pdf PDF
Amendment_1.pdf PDF
Site_Visit_BRIEF_17R0010.pdf PDF
17-R-0010_PreProposal_Sign_In_Sheet_19_July.pdf PDF
Sol_Atch_5_-_Financial_Worksheet,_17R0010.pdf PDF
Sol_Atch_2-_FTEV_12-1069_DRAWINGS_Final.pdf PDF
FA4417-17-R-0010.pdf PDF
Sol_Atch_3-_Wage_Det,_17R0010.pdf PDF
Sol_Atch_1-_FTEV_12-1069,_Specifications_Final.pdf PDF
Sol_Atch_6,_,_Add_Contract_Reqs,_17R0010.pdf PDF
Sol_Atch_4_-_PPQ,_17R0010.pdf PDF
Synopsis.pdf PDF
Show all 16

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

91325

91307

99105

99007

J

J753

J

J940

J

J108

T

P

K

V

A

T

P

K

V

A

J

J580

N

ELECTRICAL SITE PLAN - SHEET 2 - BASE BID

SCALE: 1" = 50'-0"

P9

P8

P7

P6

P5

X

X

X

X

X

X

X

X

X

X

X

X

J

J

J

J

WORK NOTES:

INSTALL NEW PRIMARY JUNCTION CABINET.

INSTALL NEW PRIMARY CIRCUIT J BY DIRECTIONAL BORE METHOD. NEW PRIMARY CIRCUIT SHALL BE 3 - 500 MCM

COPPER, 15 KV, TYPE EPR W/ 133% INSULATION & 1/3 CONCENTRIC NEUTRAL IN TWO WAY 5" DUCTBANK.

X

X

J

P4

SCALE: 1" = 10'-0"

LARGE SCALE PLAN - BUILDING 91310

N

X

X

E

O

S

T

P

J

X

X

E

U

S

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

BUILDING 91310

99004

99005

E

U

S

S

EXISTING ASPHALT PAVING

EXISTING ASPHALT PAVING

EXISTING

CONCRETE

SLAB

EXISTING ALUMINUM AWNING

TRENCH & BACKFILL THROUGH

EXISTING GRASS AREA.

4 # 1/0 - 2" PVC, SCH. 40 CONDUIT.

EXISTING PANELBOARD

150 A., 3 P. MAIN BREAKER,

208Y/120 V., 3Ø

INSTALL 4 # 1/0 - 2" RIGID GALV. STEEL

CONDUIT EXPOSED ON WALL BELOW

ROOF. INSTALL WEATHERPROOF "LB"

FITTINGS AT CORNERS OF BUILDING.

4 # 1/0 - 2" RIGID GALV. STEEL

CONDUIT EXPOSED ON WALL.

REMOVE EXISTING OVERHEAD SERVICE DROP &

WEATHERHEAD. REMOVE EXISTING SERVICE MAST TO

A POINT JUST ABOVE ROOF & CAP EXISTING CONDUIT.

E

O

S

X

X

X

X

X

X

X

X

X

X

EXISTING UNDERGROUND

SECONDARY SERVING LIFT

STATION TO REMAIN.

SINGLE LINE DIAGRAM - LAY DOWN YARD SERVICE

NO SCALE

US

M

KWH METER - SINGLE PHASE METERS SHALL BE SENSUS

FLEXNET TYPE W/ KYZ PULSE INITIATION HARDWARE. AT

THE CONTRACTOR'S OPTION, CURRENT TRANSFORMERS

MAY BE EXTERNAL OR INTERNAL TO THE METER.

PAD MOUNT TRANSFORMER -

25 KVA, 1Ø, 7.2/12.47 KV PRIMARY

TO 240/120 V. SECONDARY

SEE PAD MOUNT TRANSFORMER

DETAILS, SHEET E-19.1 # 2 COPPER, 15 KV, TYPE EPR W/ 133%

INSULATION & FULL CONCENTRIC NEUTRAL IN

TWO WAY 4" CONCRETE ENCASED DUCTBANK.

EXISTING PRIMARY

JUNCTION CABINET

3 # 1 COPPER, TYPE THWN IN 1 1/2"

PVC, SCH. 40 CONDUIT.

EXISTING PANELBOARD

REMOVE EXISTING SERVICE MAST &

CAP EXISTING CONDUIT ABOVE PANEL.

WEATHERPROOF

"LB" FITTING

EXISTING ASPHALT PAVING

REMOVE EXISTING METER &

DISCONNECT SWITCH ON

EXISTING PRIMARY POLE.

X

PULL EXISTING 3 # 2 PRIMARY CABLES OUT OF EXISTING 4" DUCT. INTERCEPT EXISTING 4" DUCTBANK BELOW GRADE &

EXTEND TO NEW PRIMARY JUNCTION CABINET. INSTALL NEW PRIMARY CIRCUIT FROM JUNCTION CABINET TO EXISTING

PAD MOUNTED TRANSFORMER. NEW PRIMARY CIRCUIT SHALL BE 3 # 2 COPPER, 15 KV, TYPE EPR W/ 133% INSULATION

& 1/3 CONCENTRIC NEUTRAL IN TWO WAY 4" CONCRETE ENCASED DUCTBANK. REMOVE EXISTING PRIMARY POLE RISER.

X

4 PULL EXISTING 3 # 2 PRIMARY CABLES OUT OF EXISTING 4" DUCT. INTERCEPT EXISTING 4" DUCTBANK BELOW GRADE &

EXTEND TO NEW PRIMARY JUNCTION CABINET. INSTALL NEW PRIMARY CIRCUIT FROM JUNCTION CABINET TO EXISTING

PAD MOUNTED TRANSFORMER. NEW PRIMARY CIRCUIT SHALL BE 3 # 2 COPPER, 15 KV, TYPE EPR W/ 133% INSULATION &

1/3 CONCENTRIC NEUTRAL IN TWO WAY 4" CONCRETE ENCASED DUCTBANK. REMOVE EXISTING PRIMARY POLE RISER.

5 REMOVE EXISTING PRIMARY POLE.

6 REMOVE EXISTING OVERHEAD PRIMARY CONDUCTORS.

X

3 # 1 COPPER, TYPE THWN IN 1 1/2"

RIGID GALV. STEEL CONDUIT.

7 REMOVE EXISTING OVERHEAD SECONDARY CONDUCTORS.

8 REMOVE EXISTING UNDERGROUND SECONDARY CONDUCTORS. REMOVE EXISTING CONDUIT WHERE EXPOSED.

ABANDON EXISTING CONDUIT BELOW GRADE.

E

O

S

R E

P A

I R

K

V

E

L E

C T

R I C

A L

B A

S E

W I D

E

OF

FTEV 12-1069

S

P E

C A

IL

O

P E

R A

T

IO

N S

C

IV

IL

E

N G

IN

E

E R

S Q

U A

D R

O N

A

IR

F O

R C

E S

P E

C

IA

L O

P E

R A

T

IO

N S

C O

M M

A N

D

H U

R L

B U

R T

F

IE

L D

, F L

O R

ID

A

JRH

EWW/JRH

25 JUNE 2015

E-2

E L

E C

T R

I C

A L

S

T

E

P

L A

N

S

H E

E T

B

A S

E

B

I D

R

E V

I S

D

M

T

N

O T

J

J854

J

J988

S55

J

J633

J

J775

J

J536

S54

S56

T633-1

225KVA

T775-1

150KVA

ELECTRICAL SITE PLAN - SHEET 3 - BASE BID

SCALE: 1" = 50'-0"

P12

P11

P10

X

X

X

X

X

X

X

X

X

J

J

WORK NOTES:

INSTALL NEW PRIMARY JUNCTION CABINET.

INSTALL NEW PRIMARY CIRCUIT J BY DIRECTIONAL BORE METHOD. NEW PRIMARY CIRCUIT SHALL BE 3 - 500 MCM COPPER, 15 KV, TYPE

EPR W/ 133% INSULATION & 1/3 CONCENTRIC NEUTRAL IN TWO WAY 5" DUCTBANK.

PULL EXISTING 3 - 500 MCM PRIMARY CABLES OUT OF EXISTING 5" DUCT AND ABANDON EXISTING DUCTBANK BELOW GRADE. REMOVE

EXISTING PRIMARY POLE RISER.

4 INSTALL NEW PRIMARY CIRCUIT J BY TRENCH & BACKFILL METHOD. NEW PRIMARY CIRCUIT SHALL BE 3 - 500 MCM COPPER, 15 KV, TYPE

EPR W/ 133% INSULATION & 1/3 CONCENTRIC NEUTRAL IN TWO WAY 5" CONCRETE ENCASED DUCTBANK.

X

X

APPROXIMATE EDGE OF WETLANDS AREA

6 REMOVE EXISTING OVERHEAD PRIMARY CONDUCTORS.

7 REMOVE EXISTING DOWN GUY.

REMOVE EXISTING PRIMARY POLE.

POLE DEMOLITION NOTE:

PRIMARY POLES LOCATED WITHIN THE WETLAND AREAS SHALL BE CUT OFF JUST ABOVE GRADE, AND LAYED DOWN IN THE WETLAND AREA. PRIMARY POLES LOCATED OUTSIDE OF THE WETLAND

AREAS SHALL BE PULLED OUT OF THE GROUND AND REMOVED FROM THE SITE. ALL EXISTING POLE

LINE HARDWARE AND CONDUCTORS SHALL BE REMOVED FROM THE EXISTING POLES.

R E

P A

K

V

E

L E

C T

R I C

A L

B A

S E

W I D

E

OF

FTEV 12-1069

JRH

EWW/JRH

25 JUNE 2015

E-3

E L

E C

T R

I C

T

E

P

L A

N

S

H E

A S

E

B

J820

J

J327

T327-1

150KVA

EM131

T327-3

150KVA

EM129

EM130

J

J311

S48

S63

S47

J

J383

J

J803

T383-1

300KVA

ELECTRICAL SITE PLAN - SHEET 4 - BASE BID

SCALE: 1" = 50'-0"

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

G24

G23

G22

G21

G20

G19

G18

G17

G16

J

J

J

1 INSTALL NEW PRIMARY CIRCUIT I BY DIRECTIONAL BORE METHOD. NEW PRIMARY CIRCUIT SHALL BE 3 - 500 MCM COPPER, 15 KV, TYPE EPR W/ 133% INSULATION &

1/3 CONCENTRIC NEUTRAL IN TWO WAY 5" DUCTBANK.

WORK NOTES:

EXISTING RETENTION POND

2 PULL EXISTING 3 - 500 MCM PRIMARY CABLES OUT OF EXISTING 5" DUCT AND ABANDON EXISTING DUCTBANK BELOW GRADE. REMOVE EXISTING PRIMARY POLE RISER.

3 PULL EXISTING 3 - 500 MCM PRIMARY CABLES OUT OF EXISTING 5" DUCT AND ABANDON EXISTING DUCTBANK IN PLACE.

ABANDON EXISTING MANHOLE IN PLACE.4

X X

REUSE EXISTING 5" DUCTS STUBBED OUT FROM EXISTING SWITCH5

INSTALL NEW PRIMARY JUNCTION CABINET ON CONCRETE PAD.6

EXISTING GULF POWER CO. OVERHEAD PRIMARY AND PRIMARY

POLES TO REMAIN. EXISTING GULF POWER PRIMARY CROSSES

UNDER EXISTING OVERHEAD CIRCUIT I PRIMARY CONDUCTORS.

POLE DEMOLITION NOTE:

PRIMARY POLES LOCATED WITHIN THE WETLAND AREAS SHALL BE CUT OFF JUST ABOVE GRADE, AND LAYED DOWN IN THE WETLAND AREA. PRIMARY POLES LOCATED OUTSIDE OF THE WETLAND

AREAS SHALL BE PULLED OUT OF THE GROUND AND REMOVED FROM THE SITE. ALL EXISTING POLE

LINE HARDWARE AND CONDUCTORS SHALL BE REMOVED FROM THE EXISTING POLES.

INSTALL NEW DIRECT BURIAL PRIMARY JUNCTION CABINET ADJACENT TO EXISTING GRAVEL DRIVE. SEE DETAIL, THIS SHEET.7

APPROXIMATE LOCATION OF WETLANDS AREA

DIRECT BURIAL PRIMARY JUNCTION CABINET DETAIL

NOTES:

PLAN VIEW

TO BRADY # 84876.

WELDED. PROVIDE RED ADHESIVE SIGN W/ LETTERS "DANGER

HIGH VOLTAGE." SIGN SHALL BE 12"W X 9"H. & SHALL BE EQUAL

ALL GROUND CONNECTIONS SHALL BE BRAZED OR EXOTHERMIC

1'-0"

MIN.

FIBERGLASS PRIMARY JUNCTION CABINET

W/ 3 - 4 POINT, 600 A. JUNCTIONS.

PROVIDE FAULTED CIRCUIT

INDICATORS FOR ALL CIRCUITS

LEAVING EACH CABINET.

PROVIDE GROUND BUS ASSEMBLY AT EACH

GROUND NUT. CONNECT ALL NEUTRALS TO

INDIVIDUAL LUGS ON BUS. INTERCONNECT

BUSSES W/ # 3/0 GROUND CONDUCTOR.

# 3/0 BARE COPPER GROUND

HDPE PRIMARY DUCTS

HDPE TO PVC, SCH. 40 COUPLINGS

PVC, SCH. 40 ELBOWS (TYP.)

GRAVEL

CAP ALL SPARE CONDUITS.

TYPICAL PRIMARY CONDUIT

FIBERGLASS SUB-BASE

STAINLESS STEEL HARDWARE

FURNISHED W/ JUNCTION CABINET

PRIMARY JUNCTION CABINET

3/4" X 20'-0" COPPERCLAD

GROUND ROD (TYP. - 4)

# 3/0 BARE COPPER GROUND

REMOVE EXISTING PRIMARY POLE.

REMOVE EXISTING OVERHEAD PRIMARY CONDUCTORS.

REMOVE EXISTING DOWN GUY.

GRAVEL

FRONT VIEW

SIDE VIEW

3500 PSI CONCRETE

GRADE

3500 PSI CONCRETE - POUR 9"±

AROUND ALL FOUR SIDES OF

JUNCTION CABINET.

GRADE SLOPES AWAY

FROM GRAVEL DRIVE

GRAVEL DRIVE

INSTALL JUNCTION CABINET SO

THAT FLANGE IS APPROXIMATELY

LEVEL WITH GRAVEL DRIVE.

FIBERGLASS PRIMARY JUNCTION CABINET

W/ 3 - 4 POINT, 600 A. JUNCTIONS.

11 CONTRACTOR MAY HAVE TO DIG DIRECTIONAL BORE ENTRANCE AND EXIT PITS IN GRAVEL DRIVE. CONTRACTOR SHALL

COMPACT BACKFILL TO 95% AND PROVIDE NEW GRAVEL AFTER PITS HAVE BEEN BACKFILLED.

12 12

12 INSTALL PIPE BOLLARD AT CORNERS OF JUNCTION CABINET ADJACENT TO GRAVEL DRIVE. SEE "DETAIL - PIPE BOLLARD,"

SHEET E-20.

R E

P A

K

V

E

L E

C T

R I C

A L

B A

S E

W I D

E

25 JUNE 2015

E-4

E L

E C

T R

I C

T

E

P

L A

N

S

H E

A S

E

B

T911-1

75KVA

T193-1

1000KVA

T788-1

1000KVA

T549-1

150KVA

J

J549

J

J788

T193-2

45KVA

J

J193

T951-1

300KVA

J

J951

S29

VR1

J J443

J J911

JJ805

T805-1

1000KVA

T276-2

1500KVA

T911-2

150KVA

ELECTRICAL SITE PLAN - SHEET 5 - BASE BID

SCALE: 1" = 50'-0"

J

J

EXISTING TENNIS COURTS

EXISTING RETENTION POND

1 INSTALL NEW PRIMARY CIRCUIT I BY DIRECTIONAL BORE METHOD. NEW PRIMARY CIRCUIT SHALL

BE 3 - 500 MCM COPPER, 15 KV, TYPE EPR W/ 133% INSULATION & 1/3 CONCENTRIC NEUTRAL IN

TWO WAY 5" DUCTBANK.

WORK NOTES:

INSTALL NEW PRIMARY JUNCTION CABINET.2

APPROXIMATE LOCATION OF WETLANDS AREA

R E

P A

K

V

E

L E

C T

R I C

A L

B A

S E

W I D

E

25 JUNE 2015

E-5

E L

E C

T R

I C

T

E

P

L A

N

S

H E

A S

E

B

TP-G26A

91168

J

J181

J

J424

J

J456

T456-1

500KVA

N

ELECTRICAL SITE PLAN - SHEET 6 - BASE BID

SCALE: 1" = 50'-0"

X

X

X

X

X

X

X

X

X

X

X

X

X

G28

G27A

G27

G26

G25

J

J

J

WORK NOTES:

EXISTING TENNIS COURTS

1 INSTALL NEW PRIMARY CIRCUIT I BY DIRECTIONAL BORE METHOD. NEW PRIMARY CIRCUIT SHALL BE 3 - 500 MCM COPPER, 15 KV, TYPE EPR W/ 133% INSULATION & 1/3

CONCENTRIC NEUTRAL IN TWO WAY 5" DUCTBANK.

2 PULL EXISTING 3 - 500 MCM PRIMARY CABLES OUT OF EXISTING 5" DUCT AND ABANDON EXISTING DUCTBANK BELOW GRADE. REMOVE EXISTING PRIMARY POLE RISER.

3 INSTALL NEW PRIMARY JUNCTION CABINET.

X

X

X

G26A

T

4 INSTALL NEW PRIMARY CIRCUIT I BY TRENCH & BACKFILL METHOD. NEW PRIMARY CIRCUIT SHALL BE 1 # 2 COPPER, 15 KV, TYPE EPR W/ 133% INSULATION & FULL

CONCENTRIC NEUTRAL IN TWO WAY 4" CONCRETE ENCASED DUCTBANK.

5 INSTALL NEW 50 KVA, 1Ø PAD MOUNTED TRANSFORMER. SEE "SINGLE LINE DIAGRAM - CONTRACTOR YARD SERVICE," THIS SHEET.

6 INSTALL NEW UNDERGROUND SECONDARY & SERVICE PANEL. SEE "SINGLE LINE DIAGRAM - CONTRACTOR YARD SERVICE," THIS SHEET.

SINGLE LINE DIAGRAM - CONTRACTOR YARD SERVICE

NO SCALE

US

M

NEW PANEL "MP"

PAD MOUNT TRANSFORMER -

50 KVA, 1Ø, 7.2/12.47 KV PRIMARY

TO 240/120 V. SECONDARY

SEE PAD MOUNT TRANSFORMER

DETAILS, SHEET E-19.1 # 2 COPPER, 15 KV, TYPE EPR W/ 133%

INSULATION & FULL CONCENTRIC NEUTRAL IN

TWO WAY 4" CONCRETE ENCASED DUCTBANK.

PRIMARY JUNCTION

CABINET

A

P

S

P A

R E

A

S

P A

R E

A

S

P A

R E

A

S

P A

R E

A

S

P A

R E

A

S

P A

R E

300 A., 2 P., 10 KAIC

MAIN BREAKER

7 REMOVE EXISTING 25 KVA, 1Ø POLE MOUNTED TRANSFORMER, SERVICE MASTS, WEATHERHEADS, METER/POWER PANEL, DISCONNECT SWITCHES & ASSOCIATED CONDUIT

& WIRING MOUNTED ON EXISTING PRIMARY POLE.

POLE DEMOLITION NOTE:

PRIMARY POLES LOCATED WITHIN THE WETLAND AREAS SHALL BE CUT OFF JUST ABOVE GRADE, AND LAYED DOWN IN THE WETLAND AREA. PRIMARY POLES LOCATED OUTSIDE OF THE WETLAND

AREAS SHALL BE PULLED OUT OF THE GROUND AND REMOVED FROM THE SITE. ALL EXISTING POLE

LINE HARDWARE AND CONDUCTORS SHALL BE REMOVED FROM THE EXISTING POLES.

3 - 350 MCM COPPER, TYPE THWN IN

3" PVC, SCH. 80 CONDUIT.

# 2 COPPER IN 1/2" PVC, SCH. 80 CONDUIT TO

3/4" X 20'-0" COPPERCLAD GROUND ROD.

3"±

NEW MAIN PANEL

GRADE

3500 PSI CONCRETE

1 5/8" X 1 5/8", 12 GAUGE,

HOT-DIPPED GALVANIZED

STEEL CHANNEL (TYP.)

CONDUIT & WIRING AS SHOWN

ON SINGLE LINE DIAGRAM

DETAIL - NEW MAIN PANEL SERVICE ASSEMBLY

N.T.S.

24±

6'-0"±

NEW PANELBOARD SHALL BE FURNISHED

WITH A NEMA 3R OUTDOOR ENCLOSURE.

BOND GROUND BUS TO NEUTRAL BUS. ALL

BRANCH BREAKERS SHALL BE RATED 10 KAIC.

APPROXIMATE LOCATION OF WETLANDS AREA

APPROXIMATE LOCATION OF WETLANDS AREA

REMOVE EXISTING PRIMARY POLE.

REMOVE EXISTING OVERHEAD PRIMARY CONDUCTORS.

REMOVE EXISTING DOWN GUY.

3'-0"

6"

12" Ø

KWH METER - SINGLE PHASE METERS SHALL BE SENSUS

FLEXNET TYPE W/ KYZ PULSE INITIATION HARDWARE. AT

THE CONTRACTOR'S OPTION, CURRENT TRANSFORMERS

MAY BE EXTERNAL OR INTERNAL TO THE METER.

R E

P A

K

V

E

L E

C T

R I C

A L

B A

S E

W I D

E

OF

FTEV 12-1069

S

P E

C A

IL

O

P E

R A

T

IO

N S

C

IV

IL

E

N G

IN

E

E R

S Q

U A

D R

O N

A

IR

F O

R C

E S

P E

C

IA

L O

P E

R A

T

IO

N S

C O

M M

A N

D

H U

R L

B U

R T

F

IE

L D

, F L

O R

ID

A

JRH

EWW/JRH

25 JUNE 2015

E-6

E L

E C

T R

I C

T

E

P

L A

N

S

H E

A S

E

B

I D

R

E V

I S

T

T

ELECTRICAL SITE PLAN - SHEET 7 - BASE BID

SCALE: 1" = 50'-0"

J

1 INSTALL NEW PRIMARY CIRCUIT F BY DIRECTIONAL BORE METHOD. NEW PRIMARY CIRCUIT SHALL BE 3 - 500 MCM

COPPER, 15 KV, TYPE EPR W/ 133% INSULATION & 1/3 CONCENTRIC NEUTRAL IN TWO WAY 5" DUCTBANK.

WORK NOTES:

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

S49

J

J704

JJ411

J

J181

T181-1

150KVA

J

J959

T959-1

75KVA

J

J511

T511-3

500KVA

T511-1

75KVA

J

J259

T511-2

75KVA

J

J278

S51

JJ523

T516-1

225KVA

J

J276

T276-1

225KVA

T276-3

1000KVA

T276-2

1500KVA

2 INSTALL NEW PRIMARY JUNCTION CABINET.

3 PULL EXISTING 3 - 250 MCM PRIMARY CABLES OUT OF EXISTING 5" DUCT AND PULL NEW PRIMARY CABLES INTO

EXISTING 5" DUCT (CIRCUIT I.) NEW PRIMARY CABLES SHALL BE 3 - 500 MCM COPPER, 15 KV, TYPE EPR W/ 133%

INSULATION & 1/3 CONCENTRIC NEUTRAL.

3 3

R E

P A

K

V

E

L E

C T

R I C

A L

B A

S E

W I D

E

25 JUNE 2015

E-7

E L

E C

T R

I C

T

E

P

L A

N

S

H E

A S

E

B

J958

J

J852

EM16

EM15

EM133

EM134

T45-1

50KVA

S45

J

J769

ELECTRICAL SITE PLAN - SHEET 8 - BASE BID

SCALE: 1" = 50'-0"

1 PULL EXISTING 3 - 350 MCM ALUMINUM PRIMARY CABLES OUT OF EXISTING 5" DUCT AND ABANDON EXISTING DUCTBANK IN PLACE (CIRCUIT I.)

WORK NOTES:

INSTALL NEW PRIMARY CIRCUIT I BY DIRECTIONAL BORE METHOD. NEW PRIMARY CIRCUIT SHALL BE 3 - 500 MCM COPPER, 15 KV, TYPE EPR

W/ 133% INSULATION & 1/3 CONCENTRIC NEUTRAL IN TWO WAY 5" DUCTBANK.

X

X

X

X

X

3 PULL EXISTING 3 - 350 MCM ALUMINUM PRIMARY CABLES OUT OF EXISTING 5" DUCT AND PULL IN NEW PRIMARY CABLES INTO EXISTING 5"

DUCT (CIRCUIT I.) NEW PRIMARY CIRCUIT SHALL BE 3 - 500 MCM COPPER, 15 KV, TYPE EPR W/ 133% INSULATION & 1/3 CONCENTRIC NEUTRAL.

4 CORE DRILL EXISTING MANHOLE WALL AS REQUIRED FOR NEW CONDUIT ENTRANCE INTO EXISTING MANHOLE. INSTALL NON-SHRINK GROUT

AROUND CONDUIT PENETRATION.

X

X

EXISTING TREE LINE

EXISTING TREE LINE

R E

P A

K

V

E

L E

C T

R I C

A L

B A

S E

W I D

E

25 JUNE 2015

E-8

E L

E C

T R

I C

T

E

P

L A

N

S

H E

A S

E

B

EM18

EM17

EM142

EM143

N

ELECTRICAL SITE PLAN - SHEET 9 - BASE BID

SCALE: 1" = 50'-0"

EM

EM

EM

EM

EM

1 PULL EXISTING 3 - 350 MCM ALUMINUM PRIMARY CABLES OUT OF EXISTING 5" DUCT AND ABANDON EXISTING DUCTBANK IN PLACE (CIRCUIT I.)

INSTALL NEW 6'-0" X 6'-0" X 6'-0" DEEP PRECAST CONCRETE MANHOLE W/ SPRING LOADED DOUBLE DOOR LID.3

INSTALL NEW PRIMARY CIRCUIT I BY DIRECTIONAL BORE METHOD. NEW PRIMARY CIRCUIT SHALL BE 3 - 500 MCM COPPER, 15 KV, TYPE EPR

W/ 133% INSULATION & 1/3 CONCENTRIC NEUTRAL IN TWO WAY 5" DUCTBANK.

WORK NOTES:

ABANDON EXISTING MANHOLE IN PLACE.4

HIGHWAY 98

X

X

X

X

X

X

X

X

X

X

X

X

X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X

X

X

EXISTING WETLAND AREA

EXISTING WETLAND AREA

EXISTING TREE LINE

EXISTING TREE LINE

EXISTING AIRFIELD LIGHTING CIRCUITS

APPROX. 600'-0" BETWEEN MANHOLES

ON EITHER SIDE OF THIS EXISTING

WETLANDS AREA

5 INSTALL NEW PRIMARY CIRCUIT I BY DIRECTIONAL BORE METHOD. NEW PRIMARY CIRCUIT SHALL BE 3 - 500 MCM COPPER, 15 KV, TYPE EPR

W/ 133% INSULATION & 1/3 CONCENTRIC NEUTRAL IN TWO WAY 6" DUCTBANK.

EXISTING ARCHAELOGICAL AREA

NOTE:

NO WORK WILL BE PERMITTED IN THE ARCHAELOGICAL SITES.

R E

P A

K

V

E

L E

C T

R I C

A L

B A

S E

W I D

E

OF

FTEV 12-1069

S

P E

C A

IL

O

P E

R A

T

IO

N S

C

IV

IL

E

N G

IN

E

E R

S Q

U A

D R

O N

A

IR

F O

R C

E S

P E

C

IA

L O

P E

R A

T

IO

N S

C O

M M

A N

D

H U

R L

B U

R T

F

IE

L D

, F L

O R

ID

A

JRH

EWW/JRH

25 JUNE 2015

E-9

E L

E C

T R

I C

T

E

P

L A

N

S

H E

A S

E

B

I D

A

D D

W

R

K

N

O

JJ829

J978

EM141

ELECTRICAL SITE PLAN - SHEET 10 - BASE BID

SCALE: 1" = 50'-0"

EM

1 PULL EXISTING 3 - 500 MCM ALUMINUM PRIMARY CABLES OUT OF EXISTING 5" DUCT AND ABANDON EXISTING

DUCTBANK IN PLACE (CIRCUIT I.)

INSTALL NEW 6'-0" X 6'-0" X 6'-0" DEEP PRECAST CONCRETE MANHOLE W/ SPRING LOADED DOUBLE DOOR LID.3

INSTALL NEW PRIMARY CIRCUIT I BY DIRECTIONAL BORE METHOD. NEW PRIMARY CIRCUIT SHALL BE 3 - 500

MCM COPPER, 15 KV, TYPE EPR W/ 133% INSULATION & 1/3 CONCENTRIC NEUTRAL IN TWO WAY 5" DUCTBANK.

WORK NOTES:

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

4 PULL EXISTING 3 - 350 MCM ALUMINUM PRIMARY CABLES OUT OF EXISTING 5" DUCT AND PULL IN NEW

PRIMARY CIRCUIT (CIRCUIT I.) NEW PRIMARY CIRCUIT SHALL BE 3 - 500 MCM COPPER, 15 KV, TYPE EPR W/

133% INSULATION & 1/3 CONCENTRIC NEUTRAL.

EXISTING CONCRETE DITCH

EXISTING CONCRETE DITCH

EXISTING STREAM

EXISTING GUARD RAIL

5 CORE DRILL EXISTING MANHOLE WALL AS REQUIRED FOR NEW CONDUIT ENTRANCE INTO EXISTING

MANHOLE. INSTALL NON-SHRINK GROUT AROUND CONDUIT PENETRATION.

EXISTING WETLAND AREA

EM

EXISTING TREE LINE

EXISTING TREE LINE

EXISTING TREE LINE

EXISTING TREE LINE

EXISTING TREE LINE

6 INSTALL NEW PRIMARY CIRCUIT I BY DIRECTIONAL BORE METHOD. NEW PRIMARY CIRCUIT SHALL BE 3 - 500

MCM COPPER, 15 KV, TYPE EPR W/ 133% INSULATION & 1/3 CONCENTRIC NEUTRAL IN TWO WAY 6" DUCTBANK.

EXISTING ARCHAELOGICAL AREA

EXISTING ARCHAELOGICAL AREA

NOTE:

NO WORK WILL BE PERMITTED IN THE ARCHAELOGICAL SITES.

APPROX. 600'-0" BETWEEN MANHOLES

ON EITHER SIDE OF THIS EXISTING

WETLANDS AREA

R E

P A

K

V

E

L E

C T

R I C

A L

B A

S E

W I D

E

25 JUNE 2015

E-10

E L

E C

T R

I C

T

E

P

L A

N

S

H E

B

A S

E

B

JJ688

EM43

S25

EM44

JJ562

S59

J

J629

J

J867

T867-1

45KVA

T106-1

150KVA

EM45

JJ106

T106-2

750KVA

J

J684

T684-1

112.5KVA

T318-1

75KVA

ELECTRICAL SITE PLAN - SHEET 11 - BASE BID

SCALE: 1" = 50'-0"

WORK NOTES:

INSTALL NEW PRIMARY SWITCH. NEW SWITCH SHALL BE AN S&C, VISTA 431. NEW PRIMARY CIRCUIT TO JUNCTION CABINET J318 SHALL BE

CONNECTED TO THE VFI WAY IN THE NEW SWITCH. LEAVE VFI SWITCH IN NORMALLY OPEN POSITION.

2 PULL EXISTING 3 # 2 PRIMARY CABLES OUT OF EXISTING 4" DUCT AND ABANDON EXISTING DUCTBANK IN PLACE (CIRCUIT D.)

3 INSTALL NEW PRIMARY CIRCUIT A BY DIRECTIONAL BORE METHOD FROM NEW PRIMARY SWITCH TO EXISTING JUNCTION CABINET J318.

NEW PRIMARY CIRCUIT SHALL BE 3 - 250 MCM COPPER, 15 KV, TYPE EPR W/ 133% INSULATION & 1/3 CONCENTRIC NEUTRAL IN TWO WAY 5"

DUCTBANK.

J

J318

X

X

X

X

X

X

X

X

S

X

X

X

INSTALL NEW PRIMARY CIRCUIT A BY TRENCH & BACKFILL METHOD FROM NEW PRIMARY SWITCH TO EXISTING JUNCTION CABINETJ684.

NEW PRIMARY CIRCUIT SHALL BE 3 - 250 MCM COPPER, 15 KV, TYPE EPR W/ 133% INSULATION & 1/3 CONCENTRIC NEUTRAL IN TWO WAY 5"

CONCRETE ENCASED DUCTBANK.

APPROXIMATE SCALE: 1" = 10'-0"

LARGE SCALE PLAN

EXISTING JUNCTION CABINET J684

EXISTING CONCRETE BOLLARD (TYP.)

SEE "LARGE SCALE PLAN," THIS SHEET.

EDGE OF ROAD

R E

P A

K

V

E

L E

C T

R I C

A L

B A

S E

W I D

E

25 JUNE 2015

E-11

E L

E C

T R

I C

T

E

P

L A

N

S

H E

B

A S

E

B

J103

EM8

T103-2

500KVA

J

J550

T550-1

225KVA

T103-1

1000KVA

EM2

S71

EM1

J

J303

J

J508

T508-1

150KVA

S18

J

J177

J

J866

EM9

J

J175

S19

T175-1

300KVA

EM30

J

J149

T413-1

500KVA

J

J233

J

J314

ELECTRICAL SITE PLAN - SHEET 12 - BID OPTION # 1

SCALE: 1" = 50'-0"

WORK NOTES:

PULL EXISTING 3 # 4/0 PRIMARY CABLES OUT OF EXISTING 5" DUCT AND PULL NEW PRIMARY CABLES INTO EXISTING 5" DUCT (CIRCUIT A.) NEW

PRIMARY CABLES SHALL BE 3 - 500 MCM COPPER, 15 KV, TYPE EPR W/ 133% INSULATION & 1/3 CONCENTRIC NEUTRAL.

2 REMOVE EXISTING PRIMARY SWITCH & INSTALL NEW PRIMARY SWITCH ON EXISTING CONRETE PAD. RECONNECT EXISTING PRIMARY CABLES

TO NEW SWITCH TERMINATIONS. NEW SWITCH SHALL BE AN S&C, PME-10.

X

X

3 PULL EXISTING 3 # 4/0 PRIMARY CABLES OUT OF EXISTING 4" DUCT AND ABANDON EXISTING DUCTBANK IN PLACE (CIRCUIT A.)

4 INSTALL NEW PRIMARY CIRCUIT A BY DIRECTIONAL BORE METHOD. NEW PRIMARY CIRCUIT SHALL BE 3 - 500 MCM COPPER, 15 KV, TYPE EPR W/

133% INSULATION & 1/3 CONCENTRIC NEUTRAL IN TWO WAY 5" DUCTBANK.

R E

P A

K

V

E

L E

C T

R I C

A L

B A

S E

W I D

E

25 JUNE 2015

E-12

E L

E C

T R

I C

T

E

P

L A

N

S

H E

B

T

I O

T175-2

500KVA

J

J510

J

J494

T510-1

112.5KVA

JJ285

S17

T619-1

225KVA

J

J971

S15

J

J339

J

J862

J J421

J J773

J

J790

J J121

S14

J

J460

J

J242

S26

J

J169

T169-1

150KVA

X

X

X

X

X

X

X X

X X

X X

X X

X

X

X

X

X

X

X

X

X

X

X

X

J

X

X

ELECTRICAL SITE PLAN - SHEET 13 - BID OPTION # 1

SCALE: 1" = 50'-0"

WORK NOTES:

PULL EXISTING 3 # 4/0 PRIMARY CABLES OUT OF EXISTING 4" DUCT AND ABANDON EXISTING DUCTBANK IN

PLACE (CIRCUIT A.)

INSTALL NEW PRIMARY CIRCUIT A BY DIRECTIONAL BORE METHOD. NEW PRIMARY CIRCUIT SHALL BE 3 - 500 MCM

COPPER, 15 KV, TYPE EPR W/ 133% INSULATION & 1/3 CONCENTRIC NEUTRAL IN TWO WAY 5" DUCTBANK.

INSTALL NEW PRIMARY JUNCTION CABINET.

INSTALL NEW PRIMARY CIRCUIT A BY TRENCH & BACKFILL METHOD. NEW PRIMARY CIRCUIT SHALL BE 3 # 2

COPPER, 15 KV, TYPE EPR W/ 133% INSULATION & 1/3 CONCENTRIC NEUTRAL IN TWO WAY 4" CONCRETE

ENCASED DUCTBANK.

INSTALL NEW PRIMARY CIRCUIT A BY TRENCH & BACKFILL METHOD. NEW PRIMARY CIRCUIT SHALL BE 3 # 4/0

COPPER, 15 KV, TYPE EPR W/ 133% INSULATION & 1/3 CONCENTRIC NEUTRAL IN TWO WAY 5" CONCRETE

ENCASED DUCTBANK.

REMOVE EXISTING STEEL JUNCTION CABINET & INSTALL NEW FIBERGLASS JUNCTION CABINET IN EXISTING

LOCATION. POUR EXTENSION TO CONCRETE PAD. SEE "DETAIL - CONCRETE PAD EXTENSIONS," THIS SHEET.

SCALE: 1/4" = 1'-0"

DETAIL - CONCRETE PAD EXTENSIONS

PRIMARY JUNCTION CABINET J494

PRIMARY JUNCTION CABINET J510

EXISTING COMMUNICATION PEDESTAL TO REMAIN

EXISTING CONCRETE PAD - 32" X 78 1/2"

EXISTING PRIMARY JUNCTION CABINET - REMOVE.

EXISTING CONDUITS TO REMAIN.

NEW CONCRETE PAD EXTENSION

NEW FIBERGLASS PRIMARY JUNCTION CABINET

LEAVE OPENING IN CONCRETE PAD EXTENSION WHERE

NEW PRIMARY DUCTS ENTER JUNCTION CABINET.

EXISTING CONDUITS - TO REMAIN.

EXISTING CONCRETE PAD - 35" X 78"

NEW CONCRETE PAD EXTENSION

EXISTING PRIMARY JUNCTION

CABINET - REMOVE.

NEW FIBERGLASS PRIMARY

JUNCTION CABINET

LEAVE OPENING IN CONCRETE PAD

EXTENSION WHERE NEW PRIMARY

DUCTS ENTER JUNCTION CABINET.

NOTE:

DIMENSIONS OF CONCRETE PAD EXTENSIONS SHALL BE ADJUSTED AS REQUIRED

BY THE PHYSICAL SIZE OF THE NEW JUNCTION CABINETS FURNISHED BY THE

CONTRACTOR.

R E

P A

K

V

E

L E

C T

R I C

A L

B A

S E

W I D

E

25 JUNE 2015

E-13

E L

E C

T R

I C

T

E

P

L A

N

S

H E

B

T

I O

T613-1

J

J613

J

J945

T613-3

750KVA

J

J597

S24

JJ488

T488-1

150KVA

JJ677

JJ405

EM40

EM41

J

J333

T333-1

500KVA

T984-1

112.5KVA

J

J865

J

J984

EM42

T865-1

100KVA

J

J539

T539-1

150KVA

J

J389

T389-1

1000KVA

ELECTRICAL SITE PLAN - SHEET 14 - BID OPTION # 2

SCALE: 1" = 50'-0"

WORK NOTES:

PULL EXISTING 3 - 250 MCM PRIMARY CABLES OUT OF EXISTING 5" DUCT AND PULL NEW PRIMARY CABLES INTO EXISTING 5" DUCT. NEW

PRIMARY CABLES SHALL BE 3 - 500 MCM COPPER, 15 KV, TYPE EPR W/ 133% INSULATION & 1/3 CONCENTRIC NEUTRAL.

R E

P A

K

V

E

L E

C T

R I C

A L

B A

S E

W I D

E

25 JUNE 2015

E-14

E L

E C

T R

I C

T

E

P

L A

N

S

H E

B

T

I O

S61

EM2

S22

S23 J

J216

J

J401

T401-2

75KVA

T401-1

225KVA

T23-2

150KVA

T23-1

750KVA

EM38

J

J607

J

J870

T870-1

25KVA

T870-3

150KVA

T870-2

300KVA

T607-1

1000KVA

T698-1

300KVA

J

J248

J

J698

T698-2

75KVA

T698-3

75KVA

J

J431

T431-1

225KVA

T553-2

75KVA

T553-1

500KVA

T613-2

500KVA

S6

S5

S4

S3

S2

S1 J J850

J J849

J J280

J J147

J J422

J J388

J

J233

J

J314

T248-1

300KVA

ELECTRICAL SITE PLAN - SHEET 15 - BID OPTION # 2

SCALE: 1" = 50'-0"

WORK NOTES:

PULL EXISTING 3 - 250 MCM PRIMARY CABLES OUT OF EXISTING 5" DUCT AND PULL NEW PRIMARY CABLES INTO EXISTING 5" DUCT (CIRCUIT D.)

NEW PRIMARY CABLES SHALL BE 3 - 500 MCM COPPER, 15 KV, TYPE EPR W/ 133% INSULATION & 1/3 CONCENTRIC NEUTRAL.

R E

P A

K

V

E

L E

C T

R I C

A L

B A

S E

W I D

E

25 JUNE 2015

E-15

E L

E C

T R

I C

T

E

P

L A

N

S

H E

B

T

I O

S61

EM2

S22

S23 J

J216

J

J401

T401-2

75KVA

T401-1

225KVA

T23-2

150KVA

T23-1

750KVA

EM38

J

J607

J

J870

T870-1

25KVA

T870-3

150KVA

T870-2

300KVA

T607-1

1000KVA

T698-1

300KVA

J

J248

J

J698

T698-2

75KVA

T698-3

75KVA

J

J431

T431-1

225KVA

T553-2

75KVA

T553-1

500KVA

T613-2

500KVA

S6

S5

S4

S3

S2

S1 J J850

J J849

J J280

J J147

J J422

J J388

J

J233

J

J314

T248-1

300KVA

ELECTRICAL SITE PLAN - SHEET 16 - BID OPTION # 3

SCALE: 1" = 50'-0"

WORK NOTES:

1 PULL EXISTING 3 - 350 MCM ALUMINUM PRIMARY CABLES OUT OF EXISTING 5" DUCT AND ABANDON EXISTING DUCTBANK IN PLACE (CIRCUIT F.)

3 INSTALL NEW PRIMARY JUNCTION CABINET.

INSTALL NEW PRIMARY CIRCUIT F BY DIRECTIONAL BORE METHOD. NEW PRIMARY CIRCUIT SHALL BE 3 - 500 MCM COPPER, 15 KV, TYPE

EPR W/ 133% INSULATION & 1/3 CONCENTRIC NEUTRAL IN TWO WAY 5" DUCTBANK.

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

R E

P A

K

V

E

L E

C T

R I C

A L

B A

S E

W I D

E

25 JUNE 2015

E-16

E L

E C

T R

I C

T

E

P

L A

N

S

H E

B

T

I O

T175-2

J

J510

J

J494

T510-1

112.5KVA

JJ285

S17

T188-1

225KVA

T188-2

225KVA

J J188

J J310

JJ619

J J747

J J617

T747-1

225KVA

T747-2

500KVA

T619-1

225KVA

J

J418

J

J971

S15

J

J339

J

J862

J J421

J J773

J

J790

J J121

S14

J

J460

J

J242

S26

J

J169

T169-1

150KVA

T465-2

1000KVA

J

J465

T465-1

1000KVA

S90

J J100

ELECTRICAL SITE PLAN - SHEET 17 - BID OPTION # 3

SCALE: 1" = 50'-0"

WORK NOTES:

PULL EXISTING 3 - 350 MCM ALUMINUM PRIMARY CABLES OUT OF EXISTING 5" DUCT AND ABANDON EXISTING

DUCTBANK IN PLACE (CIRCUIT F.)

INSTALL NEW PRIMARY CIRCUIT F BY DIRECTIONAL BORE METHOD. NEW PRIMARY CIRCUIT SHALL BE 3 - 500

MCM COPPER, 15 KV, TYPE EPR W/ 133% INSULATION & 1/3 CONCENTRIC NEUTRAL IN TWO WAY 5" DUCTBANK.

REMOVE EXISTING PRIMARY JUNCTION CABINET & CONCRETE PAD.

INSTALL NEW PRIMARY JUNCTION CABINET.

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

R E

P A

K

V

E

L E

C T

R I C

A L

B A

S E

W I D

E

25 JUNE 2015

E-17

E L

E C

T R

I C

T

E

P

L A

N

S

H E

B

T

I O

J J687

T687-1

112.5KVA

J J689

T689-1

150KVA

J

J252

T252-1

150KVA

T689-2

750KVA

T90-1

225KVA

T90-2

75KVA

J

J710

J

J975

S85

T975-1

75KVA

T85-1

75KVA

T710-1

50KVA

J

J415

J

J635

J

J145

JJ756

T756-3

500KVA

T756-1

25KVA

T756-2

225KVA

J

JJ932

S30

S42

ELECTRICAL SITE PLAN - SHEET 18 - BID OPTION # 3

SCALE: 1" = 50'-0"

WORK NOTES:

J

J615

J J317

J

J515

J

J238

J

J

PULL EXISTING 3 - 350 MCM ALUMINUM PRIMARY CABLES OUT OF EXISTING 5" DUCT AND ABANDON EXISTING DUCTBANK IN PLACE (CIRCUIT F.)

INSTALL NEW PRIMARY CIRCUIT F BY DIRECTIONAL BORE METHOD. NEW PRIMARY CIRCUIT SHALL BE 3 - 500 MCM COPPER, 15 KV, TYPE EPR W/

133% INSULATION & 1/3 CONCENTRIC NEUTRAL IN TWO WAY 5" DUCTBANK.

REMOVE EXISTING PRIMARY JUNCTION CABINET & INSTALL NEW STEEL JUNCTION CABINET ON EXISTING CONCRETE PAD. SEE "STEEL JUNCTION

CABINET NOTE," THIS SHEET.

INSTALL NEW PRIMARY JUNCTION CABINET.

5 REMOVE EXISTING PRIMARY SWITCH & CONCRETE PAD AFTER NEW CIRCUIT IS ENERGIZED. REMOVE CONDUITS TO A POINT BELOW GRADE &

ABANDON IN PLACE.

6 REMOVE (2) EXISTING ABANDONED PRIMARY SWITCHES & CONCRETE PADS. REMOVE CONDUITS TO A POINT BELOW GRADE & ABANDON IN PLACE.

7 INSTALL NEW PRIMARY SWITCH. NEW SWITCH SHALL BE AN S&C, VISTA 431.

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

S46

X

X

X

X

X

X

X

X

X

X

X

INSTALL NEW PRIMARY CIRCUIT F BY DIRECTIONAL BORE METHOD. NEW PRIMARY CABLES SHALL BE 3 - 250 MCM COPPER, 15 KV, TYPE EPR W/

133% INSULATION & 1/3 CONCENTRIC NEUTRAL IN TWO WAY 5" DUCTBANK.

8 INSTALL NEW PRIMARY CIRCUIT F BY TRENCH & BACKFILL METHOD. NEW PRIMARY CABLES SHALL BE 3 - 500 MCM COPPER, 15 KV, TYPE EPR W/

133% INSULATION & 1/3 CONCENTRIC NEUTRAL IN TWO WAY 5" CONCRETE ENCASED DUCTBANK.

INSTALL NEW PRIMARY CIRCUIT F BY TRENCH & BACKFILL METHOD. NEW PRIMARY CABLES SHALL BE 3 - 250 MCM COPPER, 15 KV, TYPE EPR W/

133% INSULATION & 1/3 CONCENTRIC NEUTRAL IN TWO WAY 5" CONCRETE ENCASED DUCTBANK.

STUB OUT TWO 5" PVC CONDUITS APPROXIMATELY 5'-0" BEYOND THE PRIMARY JUNCTION CABINET CONCRETE PAD.11

STEEL JUNCTION CABINET NOTE:

REMOVE EXISTING STEEL JUNCTION CABINET & INSTALL A NEW STEEL JUNCTION CABINET W/ THREE 4-POINT JUCTIONS ON THE

EXISTING CONCRETE PAD. RECONNECT ALL EXISTING PRIMARY ELBOWS TO NEW JUNCTIONS IN CABINET. CONTRACTOR SHALL FURNISH

A JUNCTION CABINET THAT HAS JUNCTION POINTS MOUNTED AT THE SAME ELEVATIONS AS THE EXISTING JUNCTIONS SO THAT EXISTING

CABLES WILL REACH NEW TERMINATION POINTS. EXISTING JUNCTION CABINET WAS MANUFACTURED BY MAYSTEEL.

SEE "LARGE SCALE PLAN," THIS SHEET.

APPROXIMATE SCALE: 1" = 10'-0"

LARGE SCALE PLAN

S30

S42

S46

X

X

X

X

X

X

X

X

X

X

X

X

EXISTING ASPHALT PARKING LOT

EXISTING TREE

EXISTING TREES IN

LANDSCAPED AREA

R E

P A

K

V

E

L E

C T

R I C

A L

B A

S E

W I D

E

25 JUNE 2015

E-18

E L

E C

T R

I C

T

E

P

L A

N

S

H E

B

T

I O

DETAIL - TWO WAY 4" CONCRETE ENCASED DUCTBANK

3"

3500 P.S.I. CONCRETE

NO SCALE

3" 3"

3"

4" PVC CONDUIT (TYP.)

3"

RIGID STEEL 90 DEGREE ELBOW (TYP.)

PAD MOUNT TRANSFORMER DETAILS

TWO WAY 4" CONCRETE ENCASED

DUCTBANK - SEE DETAIL, THIS SHEET

NOTES:

NOT TO SCALE

SECTION A

TYPICAL "T-TAP"

#4 BARS AT 12" O.C. EACH WAY (TYP.)

TYPICAL SECONDARY CONDUIT

W/ SHOP DRAWINGS.

VERIFY CONDUIT STUB-UP LOCATION

#3/0 IN SECONDARY SECTION

2#4 CONT. (TYP.)

CAP ALL SPARE CONDUITS.

TYPICAL PRIMARY CONDUIT

4"

12"

8"

12"

7"

5"

PLAN VIEW

TERMINATE W/ GROUNDING

NOT TO SCALE

BUSHINGS & BOND TO GROUND.

8" MINIMUM

6" TYPICAL

G

G

#3/0 IN PRIMARY SECTION

G

CONCRETE PAD

G

G

A

RIGID STEEL TO PVC, SCH. 80

CONDUIT ADAPTER (TYP.)

#3/0 GROUND GRID

#3/0 BARE COPPER GROUND

BOLTS PER MANUFACTURER'S

CONCRETE PAD W/ ANCHOR

SECURE TRANSFORMER TO

GRID (TYPICAL)

SPECIFICATIONS

OUTLINE OF TRANSFORMER

G

PROVIDE OPENING IN CONC. SLAB

FOR PRIMARY AND SECONDARY

CONDUITS. FILL OPENING W/ GRAVEL.

E19E19

NOT TO SCALE

PRIMARY JUNCTION CABINET DETAIL

DETAILS," THIS SHEET.

JUNCTION CABINET INSTALLATION

4 POINT, 600 A. DEADBREAK JUNCTIONS

CONCRETE PAD - SEE "PRIMARY

HINGED SWING LID (SHOWN IN OPEN POSITION)

SECTION B

PRIMARY JUNCTION CABINET

NOTES:

NOT TO SCALE

12" MINIMUM

6" TYPICAL

CONCRETE PAD

#2/0 TO CASE GROUND

#3/0 BARE COPPER GROUND

#3/0 GROUND GRID

GRID (TYPICAL)

SECURE JUNCTION CABINET TO

SPECIFICATIONS

CONCRETE PAD W/ ANCHOR

BOLTS PER MANUFACTURER'S

PLAN VIEW

NOT TO SCALE

G

OUTLINE OF JUNCTION CABINET

G

G

B

G

RIGID GALV. STEEL ELBOWS (TYP.)

BUSHINGS & BOND TO GROUND.

TERMINATE W/ GROUNDING

TYPICAL PRIMARY CONDUIT

CAP ALL SPARE CONDUITS.

6"

4"

VERIFY CONDUIT STUB-UP LOCATION

REBAR - 12" O.C. EACH WAY.

3500 PSI CONCRETE W/ # 4

10"

W/ SHOP DRAWINGS.

TOOLED EDGES

FOR PRIMARY CONDUITS

PROVIDE OPENING IN CONC. SLAB

G

G

TYPICAL "T-TAP"

18"

3/4" X 20'-0" COPPERCLAD GROUND

ROD - 18" BELOW GRADE (TYP. - 4.)

PVC TO RIGID GALV.

COUPLING IN CONCRETE.

STEEL COUPLING - ENCASE

INSTALLATION DETAILS

PRIMARY SWITCH INSTALLATION DETAILS

SECTION C

NOTES:

NOT TO SCALE

12" MINIMUM

6" TYPICAL

CONCRETE PAD

#2/0 TO CASE GROUND

#3/0 BARE COPPER GROUND

#3/0 GROUND GRID

GRID (TYPICAL)

SECURE JUNCTION CABINET TO

SPECIFICATIONS

CONCRETE PAD W/ ANCHOR

BOLTS PER MANUFACTURER'S

PLAN VIEW

NOT TO SCALE

G

OUTLINE OF JUNCTION CABINET

G

G

C

G

RIGID GALV. STEEL ELBOWS (TYP.)

BUSHINGS & BOND TO GROUND.

TERMINATE W/ GROUNDING

TYPICAL PRIMARY CONDUIT

CAP ALL SPARE CONDUITS.

6"

4"

VERIFY CONDUIT STUB-UP LOCATION

REBAR - 12" O.C. EACH WAY.

3500 PSI CONCRETE W/ # 4

10"

W/ SHOP DRAWINGS.

TOOLED EDGES

FOR PRIMARY CONDUITS

PROVIDE OPENING IN CONC. SLAB

G

G

TYPICAL "T-TAP"

18"

3/4" X 20'-0" COPPERCLAD GROUND

ROD - 18" BELOW GRADE (TYP. - 4.)

PVC TO RIGID GALV.

COUPLING IN CONCRETE.

STEEL COUPLING - ENCASE

FIBERGLASS PRIMARY JUNCTION CABINET

PROVIDE FAULTED CIRCUIT INDICATORS

FOR ALL ACTIVE JUNCTIONS.

FINISH GRADE

BURIED ELECTRICAL

DUCTBANK WARNING TAPE

12"

12"

ALL GROUND CONNECTIONS MAY BE EXOTHERMICALLY WELDED OR MAY

USE UL LISTED, NON-REVERSIBLE COMPRESSION CONNECTORS. PROVIDE

ENGRAVED RED BAKELITE SIGN W/ 2 1/2" HIGH LETTERS "DANGER - HIGH

VOLTAGE." SIGN SHALL BE 12" W. X 9" HIGH. SECURE TO DOOR OF HOUSING

W/ BRASS SCREWS.

ALL GROUND CONNECTIONS MAY BE EXOTHERMICALLY WELDED OR MAY

USE UL LISTED, NON-REVERSIBLE COMPRESSION CONNECTORS. PROVIDE

ENGRAVED RED BAKELITE SIGN W/ 2 1/2" HIGH LETTERS "DANGER - HIGH

VOLTAGE." SIGN SHALL BE 12" W. X 9" HIGH. SECURE TO DOOR OF HOUSING

W/ BRASS SCREWS.

ALL GROUND CONNECTIONS MAY BE EXOTHERMICALLY WELDED OR MAY USE UL

LISTED, NON-REVERSIBLE COMPRESSION CONNECTORS. PROVIDE ENGRAVED RED

BAKELITE SIGN W/ 2 1/2" HIGH LETTERS "DANGER - HIGH VOLTAGE." SIGN SHALL BE

12" W. X 9" HIGH. SECURE TO DOOR OF HOUSING W/ BRASS SCREWS.

PARKING STANDS AND BUSHINGS

TWO WAY 5" CONCRETE ENCASED

DUCTBANK - SEE DETAIL, THIS SHEET

TWO WAY 5" CONCRETE ENCASED

DUCTBANK - SEE DETAIL, THIS SHEET

E19E19

E19E19

E19E19

E19E19

E19E19

DETAIL - TWO WAY 5" CONCRETE ENCASED DUCTBANK

3"

3500 P.S.I. CONCRETE

NO SCALE

3" 3"

3"

5" PVC CONDUIT (TYP.)

3"

FINISH GRADE

BURIED ELECTRICAL

DUCTBANK WARNING TAPE

12"

12"

3/4" X 20'-0" COPPERCLAD GROUND

ROD - 18" BELOW GRADE (TYP. - 4.)

PROVIDE GROUND BUS ASSEMBLY AT EACH

GROUND NUT. CONNECT ALL NEUTRALS TO

INDIVIDUAL LUGS ON BUS. INTERCONNECT

BUSSES W/ # 3/0 GROUND CONDUCTOR.

E-19

P R

I M

A R

Y

E

Q U

I P

M E

T

A I L

S

R E

P A

K

V

E

L E

C T

R I C

A L

B A

S E

W I D

E

OF

FTEV 12-1069

S

P E

C A

IL

O

P E

R A

T

IO

N S

C

IV

IL

E

N G

IN

E

E R

S Q

U A

D R

O N

A

IR

F O

R C

E S

P E

C

IA

L O

P E

R A

T

IO

N S

C O

M M

A N

D

H U

R L

B U

R T

F

IE

L D

, F L

O R

ID

A

JRH

EWW/JRH

25 JUNE 2015

R

E V

I S

C

N

C

E

N C

A S

E M

E

PRECAST MANHOLE NOTES:

DETAIL - 6' X 6' PRECAST MANHOLE

N.T.S.

1. MANHOLE SHALL BE DESIGNED IN ACCORDANCE WITH ACI 318, AASHTO

14TH EDITION AND ASTM C857 WHERE APPLICABLE.

2. DESIGNED FOR HS-20 LOADING.

3. MANHOLE SHALL BE PLACED ON 12" BASE OF CRUSHED PEA GRAVEL FOR

EVEN LOAD DISTRIBUTION AND EASE OF INSTALLATION.

4. CONDUIT PENETRATIONS THRU MANHOLE WALLS SHALL OCCUR NEAR

CORNERS OF MANHOLE. INSTALL WATERTIGHT SEAL BETWEEN CONDUIT

AND MANHOLE WALL.

5. PROVIDE 12" DIAMETER SUMP IN CENTER OF MANHOLE FLOOR.

6. CONCRETE - MINIMUM 28 DAY CONCRETE COMPRESSIVE STRENGTH

SHALL BE 4000 PSI.

7. PROVIDE TWO PULLING EYES IN MANHOLE ON OPPOSITE WALLS FROM

DUCT ENTRANCES. PROVIDE TWO CABLE RACKS ON THREE WALLS. DO

NOT INSTALL CABLE RACKS ON WALL WITH DEADBREAK JUNCTIONS.

8. TOP OF MANHOLE SHALL BE 1" ABOVE FINISHED GRADE.

9. INTERIOR DIMENSIONS OF MANHOLE SHALL BE 72" X 72" X 72."

MANHOLE LID NOTES:

1. DESIGNED FOR HS-20 LOADING.

2. FRAME DESIGNED FOR INSTALLATION IN PRECAST HANDHOLE.

3. FRAME AND LID SHALL BE CONSTRUCTED OF ALUMINUM.

4. DOORS SHALL BE HINGED, SPRING LOADED AND SHALL SWING OPEN 90°.

5. DOOR SHALL HAVE "ELECTRIC" IN BEADED WELDED LETTERS.

P

U

L

L

I

G

O

C

K

Y

P

D

U

R

M

I

N

A

T

I

O

Y

P

A

A

ELEVATION

PLAN VIEW - 6' X 6' PRECAST MANHOLE

N.T.S.

600 AMP, 4 POINT DEADBREAK JUNCTION (TYP. - 3)

CABLE RACK (TYP. - 6)

# 3/0 BARE COPPER GROUND WIRE LOOP

3/4" X 20'-0" COPPERCLAD GROUND ROD

BOND GROUND WIRE TO ROD W/ EXOTHERMIC

CONNECTION

BOND GROUND WIRE TO JUNCTION W/ GROUND LUG

TWO WAY 5" DUCTBANK - INSTALL CONDUIT

ENTRANCES NEAR CORNERS OF MANHOLE.

600 AMP, 4 POINT DEADBREAK JUNCTION (TYP. - 3)

BOND GROUND WIRE TO GROUND WIRE W/

EXOTHERMIC CONNECTION

C

O

V

H

A

S

T

A

L

L

E

D

F

N

H

O

L

L

INSTALL TOP JUNCTION JUST BELOW MANHOLE

COVER FRAME. INSTALL LOWER JUNCTIONS

APPROXIMATELY 3" BELOW TOP JUNCTION.

PARKING STAND (TYP.)

SELECTED BY CONTRACTING OFFICER.

2 COATS OF PAINT W/ COLOR AS

6" RIGID GALV. STEEL CONDUIT -

FILL W/ CONCRETE. PRIME AND PAINT

FORM CONCRETE INTO DOME SHAPE.

1'-0"

NOT TO SCALE

DETAIL - PIPE BOLLARD

3'-0"

3500 PSI CONCRETE

4'-0"

GRADE

E-20

M A

N H

O L

E

D

E T

A I L

S

R E

P A

K

V

E

L E

C T

R I C

A L

B A

S E

W I D

E

25 JUNE 2015

T801-2

300KVA

208/120

T689-2

750KVA

208/120

T747-1

225KVA

208/120

J

J285

S14 N.O.

500MCM

S17

500MCM

J J242

4/0

J

J525

T525-1

2000KVA

480/277

2/0

350MCMAL

S15

250MCM

J

J460

350MCMAL

4/0

JJ117

EM117

#2

S92

#2

#2

J

J243

250MCM

J J971

350MCMAL

T243-1

500KVA

480/277

#2

JJ795

T795-1

500KVA

208/120

#2

250MCM

J

J329

T329-1

300KVA

208/120

#2

250MCM

250MCM

S39

250MCM

CCAP BANK

JJ338

T338-1

225KVA

208/120

#2

250MCM

250MCM

J

J874

JJ774

#2

250MCM

#2#2

T874-1

150KVA

208/120

T874-2

300KVA

480/277

250MCM

J J370

250MCM

J

J120

250MCM

T670-1

500KVA

480/277

#2

250MCM

JJ670

T120-2

1000KVA

480/277

#2

T120-1

500KVA

208/120

#2

J

J614

#2

T120-3

150KVA

208/120

#2

T120-4

750KVA

480/277

#2

T120-5

300KVA

208/120

#2

T614-1

750KVA

480/277

250MCM

J J116

#2

T116-1

75KVA

240/120

250MCM

S40

T40-1

500KVA

480/277

#2

250MCM

J J985

T985-1

1000KVA

480/277

#2

J J601

250MCM

250MCM

250MCM

J

J169

S26

N.O.

250MCM

250MCM

#2

T169-1

150KVA

208/120

J J687

250MCM

#2

T687-1

112.5KVA

208/120

500MCM

J

J225

500MCM

J

J932

500MCM

500MCM

S30

S46

S42

N.O.

N.O.

N.O.

500MCM

J J635

500MCM

250MCM

250MCM

J J689

500MCM

350MCMAL

J

J415

#2

T689-1

150KVA

208/120

#2

250MCM

J

J252

#2

J

J162

T162-1

150KVA

208/120

#2

T252-1

150KVA

480/277

250MCM

J

J697

#2#2

T697-1

112.5KVA

208/120

#2

T697-2

75KVA

208/120

250MCM

JJ924

250MCM

J

J801

T801-3

50KVA

240/120

#2#2#2

S85

250MCM

250MCM

J

J710

T710-1

50KVA

240/120

OOS

#2

250MCM

T85-1

75KVA

208/120

250MCM

J

J145

250MCM

J

J756

#2

T756-1

25KVA

240/120

T756-2

225KVA

208/120

#2

T756-3

500KVA

208/120

#2

#2

T601-1

150KVA

208/120

250MCM

J

J235

250MCM

J

J875

S41

#2

T41-1

75KVA

208/120

#2

T41-2

75KVA

208/120

JJ317

J

J615

500MCM

EM47

500MCM

J

J282

J

J238

J J515

500MCM

500MCM

J

J315

500MCM

500MCM

J

J987

J

J199

500MCM

J

J499

500MCM

JJ206

500MCM 350MCMAL

T499-4

1500KVA

480/277

250MCM 250MCM

T499-3

500KVA

480/277

T499-2

500KVA

208/120

250MCM

J

J293

250MCM

J

J430

T430-1

150KVA

208/120

#2

J

J143

#2

T143-2

225KVA

208/120

#2

T143-1

150KVA

208/120

#2

J

J842

#2

#2

T842-1

75KVA

208/120

S43

500MCM 250MCM

J

J576

500MCM

J

J302

#2

T302-2

50KVA

240/120

#2

T302-3

50KVA

240/120

#2

250MCM

J

J946

#2#2

T302-1

750KVA

480/277

T302-4

150KVA

208/120

OOS

500MCM

250MCM

J

J519

J

J542

T542-6

75KVA

208/120

#2

250MCM

#2

T542-1

112.5KVA

208/120

#2

T542-2

500KVA

208/120

J

J907

T907-2

112.5KVA

208/120

#2

250MCM

#2

T907-1

225KVA

208/120

#2

T907-3

150KVA

208/120

#2

T907-4

150KVA

208/120

#2

T907-5

150KVA

208/120

#2

J

J889

T889-1

750KVA

208/120

#2

J

J671

T519-1

150KVA

208/120

#2

250MCM

T671-1

300KVA

208/120

#2

250MCM

J

J694

#2

T694-1

300KVA

480/277

250MCM

JJ656

500MCM

#2

J

J651

T651-1

150KVA

208/120

#2

500MCM

S44

#2#2

T44-1

300KVA

208/120

T44-2

150KVA

208/120

500MCM

N.O.

N.O.

250MCM

J

J418

4 2

4 3

3 4

3 4

2 1

4 2

4N.O.

II

A A

B

G

C

F

3 1

2 3

2 3

2 1

1 3

2 3

1250MCM

J

J465

250MCM

J

J462

250MCM

J

J101

JJ619

250MCM

T619-1

225KVA

208/120

#2

250MCM

J J310

250MCM

J

J747

250MCM

J

J617

T747-2

500KVA

208/120

#2#2

250MCM

J

J188

T188-1

225KVA

208/120

#1 #2

T188-2

225KVA

208/120

250MCM

250MCM

T465-1

1000KVA

480/277

250MCM

T465-2

1000KVA

480/277

S90

4 3

250MCM

J

J100

T100-1

1000KVA

480/277

250MCM

250MCM

T462-1

75KVA

208/120

250MCM

T462-2

500KVA

208/120

250MCM

T90-1

225KVA

208/120

250MCM

T90-2

75KVA

208/120

250MCM

J

J205

T205-1

750KVA

480/277

250MCM

250MCM

J

J301

T301-1

1500KVA

480/277

#2

250MCM

JJ975

T975-1

75KVA

208/120

#2

#2

T101-2

150KVA

208/120

#2

T101-1

150KVA

208/120

F

C

250MCM

T774-1

75KVA

208/120

T801-1

75KVA

208/120

HARTSON STREET

C O

Y

V E

N U

E

C O

E

N U

E

T E

R R

Y

A

V E

N U

E

O N

E I L L

A

V E

N U

E

HWY 98

250MCM

250MCM

N.O.

T329-2

#2

EM300

T499-1

225KVA

480/277

T92-1

225KVA

480/277

T92-2

500KVA

480/277

#2

T92-3

500KVA

208/120

T92-4

500KVA

480/277

#2

PRIMARY RISER DIAGRAM - SHEET 3

(MODIFICATIONS TO BASE RISER)

NO SCALE

X X

X

X

X

X X

X

X X

X X X X X X X

X X

X X

X

X X

X X

X

X

4/0

MCM

4/0

500MCM

X

X

X

JJ

J

J

350MCMAL

500MCM

250MCM

250MCM

250MCM

INSTALL NEW SWITCH

500MCM

500MCM

350MCMAL

500MCM

250MCM

500MCM

500MCM

BID OPTION # 3 - SEE

SHEETS E-16, E-17 & E-18.

SEE SHEET E-21 FOR

CONTINUATION.

BID OPTION # 1 -

SEE SHEETS

E-12 & E-13.

SEE SHEET E-21 FOR

CONTINUATION.

R E

P A

K

V

E

L E

C T

R I C

A L

B A

S E

W I D

E

OF

FTEV 12-1069

S

P E

C A

IL

O

P E

R A

T

IO

N S

C

IV

IL

E

N G

IN

E

E R

S Q

U A

D R

O N

A

IR

F O

R C

E S

P E

C

IA

L O

P E

R A

T

IO

N S

C O

M M

A N

D

H U

R L

B U

R T

F

IE

L D

, F L

O R

ID

A

JRH

EWW/JRH

25 JUNE 2015

E-22

P R

I M

A R

Y

R

I S

A

G R

H E

R

E V

I S

I M

A R

Y

R

O U

T I N

G

R

E V

I S

I T

P A

K

V

E

L E

C T

R I C

A L

B A

S E

W I D

E

25 JUNE 2015

E-24

P R

I M

A R

Y

R

I S

A

G R

H E

P A

K

V

E

L E

C T

R I C

A L

B A

S E

W I D

E

25 JUNE 2015

E-25

P R

I M

A R

Y

R

I S

A

G R

H E

P A

K

V

E

L E

C T

R I C

A L

B A

S E

W I D

E

25 JUNE 2015

E-26

P R

I M

A R

Y

R

I S

A

G R

H E

U .S

. 98/ M

IR

A C

LE

S

T R

IP

P

A R

K W

A Y

K E

R W

O O

D

R

O A

D

T

U

L

R

E

E

T

TULLY STREET ROUTE SURVEY

SEE SHEET 2

W

A

K

Y

L

I

E

M

A

N

I

E

A

V

E

N

U

E

HIGHWAY 98 ROUTE SURVEY

SEE SHEET 3-4

KERWOOD ROUTE SURVEY

SEE SHEET 5-7

WALKUP WAY ROUTE SURVEY

SEE SHEET 8-9

C C

H U

R L

B U

E

L D

F T

R

O U

R

V E

Y

T O

P O

G R

A P

H

R

V E

Y

N i n t h v e n u e

S u i e

P e n s a c o l a

F l o r i d a

T e l e p h o n e a x

R E

B O

L B

A T

T L

S

O C

I A

T E

S

T h i s d r a w i n g i s t h e p r o p e r t y o f

R e b o l B a t t l s s o c i a t e s a n d m y n o t b e r e p r o d u c e d w i t h o u t w r i t t e n p e r m i s s i o n

P R

E P

A R

R

R E

Q U

E S

T E

D

B

Y

D P

R O

J E

C T

P

A

K

V

E

L E

C T

R I C

S

E W

I D

E D

W G

E

L E

C F

T E

V

S

D

W G

P R

O J E

D R

A W

N

B

Y

C H

K

S C

A L E

F B

D A

T E

P G

S E

C T

I O

N

C O

U N

T Y

T O

W N

S H

I P

S T

A T

E

F

L O

R I D

A

N O

D

A T

E A

P P

R

R E

V I S

I O

N A

C T

I O

N

T

A K

E N

A

P

O R

T I O

N

O

F

R A

N G

E

G T

P

M A

N

S

O U

T H

S

T

O K

A L

O O

S A

P E

T E

R S

G

I N

E E

R I N

G

P E

T E

R S

G

I N

E E

R I N

G

SHEET 2 TULLY STREET

SHEET 3 HIGHWAY 98

SHEET 4 HIGHWAY 98

SHEET 5 KERWOOD DRIVE

SHEET 6 KERWOOD DRIVE

SHEET 7 KERWOOD DRIVE

SHEET 8 WALKUP WAY

SHEET 9 WALKUP WAY

P O

G R

A P

H

R

V E

Y

N i n e n u e

S u i

P e n s a c o l a

F l o r i d a

T e l e p h o n e x

R E

B O

L B

A T

T

S

O C

I A

T E

S

T h i s d r a w i n g i s t h e p r o p e r t y o f

R e b o l B a t t s o c i a t e s a y n o t b e r e p r o d u c e d w i t h o u t w r i t t e n p e r m i s s i o n

P R

E P

A R

R

R E

Q U

E S

T E

D

B

Y

D P

R O

J E

C T

P

A

K

V

E

L E

C T

R I C

S

E W

I D

E D

W G

E

L E

C F

T E

V

S

D

W G

P R

O J E

D R

A W

N

B

Y

C H

K

S C

A L E

F B

D A

T E

P G

S E

C T

I O

N

C O

U N

T Y

T O

W N

S H

I P

S T

A T

E

F

L O

R I D

A

N O

D

A T

E A

P P

R

R E

V I S

I O

N A

C T

I O

N

T

A K

E N

A

P

O R

T I O

N

O

F

R A

N G

E

G T

P

M A

N

S

O U

T H

S

T

O K

A L

O O

S A

P E

T E

R S

G

I N

E E

R I N

G

P E

T E

R S

G

I N

E E

R I N

G

P O

G R

A P

H

R

V E

Y

N i n e n u e

S u i

P e n s a c o l a

F l o r i d a

T e l e p h o n e x

R E

B O

L B

A T

T L

S

O C

I A

T E

S

T h i s d r a w i n g i s t h e p r o p e r t y o f

R e b o l B a t t s o c i a t e s a y n o t b e r e p r o d u c e d w i t h o u t w r i t t e n p e r m i s s i o n

P R

E P

A R

R

R E

Q U

E S

T E

D

B

Y

D P

R O

J E

C T

P

A

K

V

E

L E

C T

R I C

S

E W

I D

E D

W G

E

L E

C F

T E

V

S

D

W G

N O T

V A L I D

W I T H O U T

T H E

S I G N A T U R E

A N D

T H E

O R I G I N A L

R A I S E D

S E A L

O F

A

F L O R I D A

L I C E N S E D

S U R V E Y O R

A N D

M A P P E R

P R

O J E

D R

A W

N

B

Y

C H

K

S C

A L E

F B

D A

T E

P G

S E

C T

I O

N

C O

U N

T Y

T O

W N

S H

I P

S T

A T

E

F

L O

R I D

A

N O

D

A T

E A

P P

R

R E

V I S

I O

N A

C T

I O

N

T

A K

E N

A

P

O R

T I O

N

O

F

R A

N G

E

G T

P

M A

N

S

O U

T H

S

T

O K

A L

O O

S A

P E

T E

R S

G

I N

E E

R I N

G

P E

T E

R S

G

I N

E E

R I N

G

MATCHLINE STA 5+00 SEE THIS SHEET

S T

A R

T

O

F

U

S

R

O U

R

V E

Y

MATCHLINE STA 5+00 SEE THIS SHEET

M A

T C

H L

I N

E

S

E

P O

G R

A P

H

R

V E

Y

N i n e n u e

S u i

P e n s a c o l a

F l o r i d a

T e l e p h o n e x

R E

B O

L B

A T

T L

S

O C

I A

T E

S

T h i s d r a w i n g i s t h e p r o p e r t y o f

R e b o l B a t t s o c i a t e s a y n o t b e r e p r o d u c e d w i t h o u t w r i t t e n p e r m i s s i o n

P R

E P

A R

R

R E

Q U

E S

T E

D

B

Y

D P

R O

J E

C T

P

A

K

V

E

L E

C T

R I C

S

E W

I D

E D

W G

E

L E

C F

T E

V

S

D

W G

N O T

V A L I D

W I T H O U T

T H E

S I G N A T U R E

A N D

T H E

O R I G I N A L

R A I S E D

S E A L

O F

A

F L O R I D A

L I C E N S E D

S U R V E Y O R

A N D

M A P P E R

P R

O J E

D R

A W

N

B

Y

C H

K

S C

A L E

F B

D A

T E

P G

S E

C T

I O

N

C O

U N

T Y

T O

W N

S H

I P

S T

A T

E

F

L O

R I D

A

N O

D

A T

E A

P P

R

R E

V I S

I O

N A

C T

I O

N

T

A K

E N

A

P

O R

T I O

N

O

F

R A

N G

E

G T

P

M A

N

S

O U

T H

S

T

O K

A L

O O

S A

P E

T E

R S

G

I N

E E

R I N

G

P E

T E

R S

G

I N

E E

R I N

G

E N

D

O

F

U

S

R

O U

R

V E

Y

M A

T C

H L

I N

E

S

E

E T

M A

T C

H L

I N

E

S

E

A

T C

H L

I N

E

S

E

N i n e n u e

S u i

P e n s a c o l a

F l o r i d a

T e l e p h o n e x

R E

B O

L B

A T

T

S

O C

I A

T E

S

T h i s d r a w i n g i s t h e p r o p e r t y o f

R e b o l B a t t s o c i a t e s a y n o t b e r e p r o d u c e d w i t h o u t w r i t t e n p e r m i s s i o n

P R

E P

A R

R

R E

Q U

E S

T E

D

B

Y

D P

R O

J E

C T

P

A

K

V

E

L E

C T

R I C

S

E W

I D

E D

W G

E

L E

C F

T E

V

S

D

W G

P R

O J E

D R

A W

N

B

Y

C H

K

S C

A L E

F B

D A

T E

P G

S E

C T

I O

N

C O

U N

T Y

T O

W N

S H

I P

S T

A T

E

F

L O

R I D

A

N O

D

A T

E A

P P

R

R E

V I S

I O

N A

C T

I O

N

T

A K

E N

A

P

O R

T I O

N

O

F

R A

N G

E

G T

P

M A

N

S

O U

T H

S

T

O K

A L

O O

S A

P E

T E

R S

G

I N

E E

R I N

G

P E

T E

R S

G

I N

E E

R I N

G

T O

P O

G R

A P

H

R

V E

Y

START OF KERWOOD ROUTE SURVEY

MATCHLINE STA 5+00

SEE THIS SHEET

M A

T C

H L I N

E

S

E

MATCHLINE STA 5+00

SEE THIS SHEET

N i n e n u e

S u i

P e n s a c o l a

F l o r i d a

T e l e p h o n e x

R E

B O

L B

A T

T

S

O C

I A

T E

S

T h i s d r a w i n g i s t h e p r o p e r t y o f

R e b o l B a t t s o c i a t e s a y n o t b e r e p r o d u c e d w i t h o u t w r i t t e n p e r m i s s i o n

P R

E P

A R

R

R E

Q U

E S

T E

D

B

Y

D P

R O

J E

C T

P

A

K

V

E

L E

C T

R I C

S

E W

I D

E D

W G

E

L E

C F

T E

V

S

D

W G

P R

O J E

D R

A W

N

B

Y

C H

K

S C

A L E

F B

D A

T E

P G

S E

C T

I O

N

C O

U N

T Y

T O

W N

S H

I P

S T

A T

E

F

L O

R I D

A

N O

D

A T

E A

P P

R

R E

V I S

I O

N A

C T

I O

N

T

A K

E N

A

P

O R

T I O

N

O

F

R A

N G

E

G T

P

M A

N

S

O U

T H

S

T

O K

A L

O O

S A

P E

T E

R S

G

I N

E E

R I N

G

P E

T E

R S

G

I N

E E

R I N

G

T O

P O

G R

A P

H

R

V E

Y

M A

T C

H L I N

E

S

E

A

T C

H L I N

E

S

E

N i n e n u e

S u i

P e n s a c o l a

F l o r i d a

T e l e p h o n e x

R E

B O

L B

A T

T

S

O C

I A

T E

S

T h i s d r a w i n g i s t h e p r o p e r t y o f

R e b o l B a t t s o c i a t e s a y n o t b e r e p r o d u c e d w i t h o u t w r i t t e n p e r m i s s i o n

P R

E P

A R

R

R E

Q U

E S

T E

D

B

Y

D P

R O

J E

C T

P

A

K

V

E

L E

C T

R I C

S

E W

I D

E D

W G

E

L E

C F

T E

V

S

D

W G

P R

O J E

D R

A W

N

B

Y

C H

K

S C

A L E

F B

D A

T E

P G

S E

C T

I O

N

C O

U N

T Y

T O

W N

S H

I P

S T

A T

E

F

L O

R I D

A

N O

D

A T

E A

P P

R

R E

V I S

I O

N A

C T

I O

N

T

A K

E N

A

P

O R

T I O

N

O

F

R A

N G

E

G T

P

M A

N

S

O U

T H

S

T

O K

A L

O O

S A

P E

T E

R S

G

I N

E E

R I N

G

P E

T E

R S

G

I N

E E

R I N

G

T O

P O

G R

A P

H

R

V E

Y

M A

T C

H L I N

E

S

E

N

D

O

F

K

E R

W O

U

R

V

O

P O

G R

A P

H

R

V E

Y

N i n e n u e

S u i

P e n s a c o l a

F l o r i d a

T e l e p h o n e x

R E

B O

L B

A T

T

S

O C

I A

T E

S

T h i s d r a w i n g i s t h e p r o p e r t y o f

R e b o l B a t t s o c i a t e s a y n o t b e r e p r o d u c e d w i t h o u t w r i t t e n p e r m i s s i o n

P R

E P

A R

R

R E

Q U

E S

T E

D

B

Y

D P

R O

J E

C T

P

A

K

V

E

L E

C T

R I C

S

E W

I D

E D

W G

E

L E

C F

T E

V

S

D

W G

P R

O J E

D R

A W

N

B

Y

C H

K

S C

A L E

F B

D A

T E

P G

S E

C T

I O

N

C O

U N

T Y

T O

W N

S H

I P

S T

A T

E

F

L O

R I D

A

N O

D

A T

E A

P P

R

R E

V I S

I O

N A

C T

I O

N

T

A K

E N

A

P

O R

T I O

N

O

F

R A

N G

E

G T

P

M A

N

S

O U

T H

S

T

O K

A L

O O

S A

P E

T E

R S

G

I N

E E

R I N

G

P E

T E

R S

G

I N

E E

R I N

G

S T

A R

T

O

F

W

A L K

U

R

V E

Y

M A

T C

H L I N

E

S

E

E T

M A

T C

H L I N

E

S

E

E T

M A

T C

H L I N

E

S

E

P O

G R

A P

H

R

V E

Y

N i n e n u e

S u i

P e n s a c o l a

F l o r i d a

T e l e p h o n e x

R E

B O

L B

A T

T

S

O C

I A

T E

S

T h i s d r a w i n g i s t h e p r o p e r t y o f

R e b o l B a t t s o c i a t e s a y n o t b e r e p r o d u c e d w i t h o u t w r i t t e n p e r m i s s i o n

P R

E P

A R

R

R E

Q U

E S

T E

D

B

Y

D P

R O

J E

C T

P

A

K

V

E

L E

C T

R I C

S

E W

I D

E D

W G

E

L E

C F

T E

V

S

D

W G

P R

O J E

D R

A W

N

B

Y

C H

K

S C

A L E

F B

D A

T E

P G

S E

C T

I O

N

C O

U N

T Y

T O

W N

S H

I P

S T

A T

E

F

L O

R I D

A

N O

D

A T

E A

P P

R

R E

V I S

I O

N A

C T

I O

N

T

A K

E N

A

P

O R

T I O

N

O

F

R A

N G

E

G T

P

M A

N

S

O U

T H

S

T

O K

A L

O O

S A

P E

T E

R S

G

I N

E E

R I N

G

P E

T E

R S

G

I N

E E

R I N

G

E N

D

O

F

W

A L K

U

R

V E

Y

M A

T C

H L I N

E

S

E

A

T C

H L I N

E

S

E

E T

M A

T C

H L I N

E

S

E

FTEV 12-1069 T1
FTEV 12-1069 E1
FTEV 12-1069 E2
FTEV 12-1069 E3
FTEV 12-1069 E4
FTEV 12-1069 E5
FTEV 12-1069 E6
FTEV 12-1069 E7
FTEV 12-1069 E8
FTEV 12-1069 E9
FTEV 12-1069 E10
FTEV 12-1069 E11
FTEV 12-1069 E12
FTEV 12-1069 E13
FTEV 12-1069 E14
FTEV 12-1069 E15
FTEV 12-1069 E16
FTEV 12-1069 E17
FTEV 12-1069 E18
FTEV 12-1069 E19
FTEV 12-1069 E20
FTEV 12-1069 E21
FTEV 12-1069 E22
FTEV 12-1069 E23
FTEV 12-1069 E24
FTEV 12-1069 E25
FTEV 12-1069 E26
FTEV 12-1069 S1
FTEV 12-1069 S2
FTEV 12-1069 S3
FTEV 12-1069 S4
FTEV 12-1069 S5
FTEV 12-1069 S6
FTEV 12-1069 S7
FTEV 12-1069 S8
FTEV 12-1069 S9