FTEV_12-1096_DRAWINGS_PDF.pdf
PDF 1 MB Posted
- Attached to
- Repair Runway Edge Lighting Federal contract opportunity
- Solicitation number
- FA4417-13-R-0020
About this file
Attachment 2 - Drawings
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Follow_up_-_question__27.docx | DOCX document | |
| 13-R-0020_Questions_and_Answers.doc | DOC document | |
| Site_Visit_Sign_In_Sheet-FBO.pdf | ||
| Site_Visit_BRIEF.pdf_-_FBO.pdf | ||
| Attach_3 _13-R-0020 _Wage_Determination.docx | DOCX document | |
| FTEV_12-1096_SPECIFICATIONS_Final_(2).pdf | ||
| Attach_5 _13-R-0020 _Financial_Questionnaire.docx | DOCX document | |
| Attach_4 _13-R-0020 _Past_Performance_Questionnaire.docx | DOCX document | |
| FA4417-13-R-0020_-_Solicitation.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LOCATION MAP
N.T.S.
LOCATION MAP & INDEX OF DRAWINGS
ELECTRICAL SITE PLAN - AREA 1
T-1
E-1
E-2
E-3
E-4
SHEET # TITLE
INDEX OF DRAWINGS
B
E
D
E
L
S
T
R
E
E
T
LUKASIK AVE.
T
E
R
R
Y
A
V
E
M c
C
L
E
N
R
E
E
T
B
E
N
N
E
V
E
MAIN GATE
HAUL ROUTE
E-5
E-6
E-7
E-8
ELECTRICAL SITE PLAN - AREA 2
ELECTRICAL SITE PLAN - AREA 3
ELECTRICAL SITE PLAN - AREA 4
ELECTRICAL SITE PLAN - AREA 5
ELECTRICAL SITE PLAN - AREA 6
ELECTRICAL SITE PLAN - AREA 7
ELECTRICAL SITE PLAN - AREA 8
ELECTRICAL PLAN - AIRFIELD LIGHTING VAULTE-9
ELEVATION - REGULATOR SWITCHGEAR 1E-10
WIRING DIAGRAM - RUNWAY CIRCUIT AE-11
WIRING DIAGRAM - RUNWAY CIRCUIT BE-12
RUNWAY
REPAIR RUNWAY EDGE LIGHTING
HURLBURT FIELD, FLORIDA
FTEV 12-1096
DETAILS - RUNWAY EDGE LIGHTSE-13
DETAILS - DISTANCE REMAINING MARKERSE-14
DETAILS - HOLD SIGNE-15
AIRFIELD
VAULT
9073090727
90724
B E
D E
L
S
T R
E E
T
KEY PLAN - AREA 1
N.T.S.
MATCH LINE 1
ELECTRICAL LEGEND:
EXISTING LIGHT BASE W/ BLANK COVER - TO REMAIN.
EXISTING HANDHOLE OR MANHOLE - TO REMAIN.
EXISTING CONDUIT OR DUCTBANK - TO REMAIN - PROVIDE NEW WIRING, AS NOTED.
EXISTING DISTANCE REMAINING MARKER - REMOVE EXISTING MARKER & INSTALL NEW MARKER -
NUMERAL INDICATES GRAPHIC ON SIGN FACE - SEE "DETAIL - DISTANCE REMAINING MARKER," SHEET E-14.
WORK NOTES:
AIRFIELD LIGHTING VAULT - SEE
PLAN, SHEET E-9.
EXISTING CABLE TRENCH
EXISTING ELEVATED MEDIUM INTENSITY RUNWAY EDGE LIGHT - TO REMAIN.
CONTRACTOR HAS THE OPTION OF PULLING NEW SERIES LIGHTING CIRCUIT
CONDUCTORS IN EXISTING DUCTBANK AT THIS LOCATION. EXISTING DUCT CONTAINS
CABLES WHICH MUST REMAIN IN PLACE.
1 PULL OUT EXISTING EDGE LIGHT CIRCUITS & PULL NEW 4 # 6 L-824 TYPE C CABLES & 2
# 6 XHHW GROUND CONDUCTORS IN EXISTING DUCT. EXISTING DUCTS CONTAIN
CABLES WHICH MUST REMAIN IN PLACE.
GENERAL NOTES:
1. CONTRACTOR SHALL PULL ALL EXISTING RUNWAY EDGE LIGHT SERIES LIGHTING CIRCUIT
CONDUCTORS OUT OF EXISTING DUCTS. CABLES SHALL NOT BE ABANDONED IN PLACE.
2. CONTRACTOR SHALL BOND NEW GROUND CONDUCTORS TO EXISTING GROUND RODS IN EACH
MANHOLE AND HANDHOLE WHERE GROUND RODS EXIST. CONNECTIONS TO GROUND RODS
SHALL BE BY EXOTHERMIC WELD. CONTRACTOR SHALL BOND NEW GROUND CONDUCTORS TO
GROUND LUGS IN EXISTING LIGHT BASES. THE CONTRACTOR SHALL SUPPLY NEW GROUND LUGS
IN LIGHT BASES WHERE THEY DO NOT CURRENTLY EXIST.
3. CONTRACTOR SHALL PROVIDE CABLE TAGS ON ALL NEW CONDUCTORS IN EACH MANHOLE AND
HANDHOLE. CABLES SHALL BE TAGGED IN WHERE THEY ENTER THE MANHOLE, AND WHERE THEY
EXIT THE MANHOLE. NEW CONDUCTORS MAY HAVE TO BE PULLED INTO EXISTING DUCTS THAT
CONTAIN EXISTING CABLES. EXISTING CABLES SHALL REMAIN.
4. EXISTING MANHOLES AND HANDHOLES MAY CONTAIN MEDIUM VOLTAGE (2400 V.) CABLES. THESE
CIRCUITS CANNOT BE DE-ENERGIZED.
5. THE CONTRACTOR MAY HAVE TO WORK ON THE RUNWAY EDGE LIGHT AND TAXIWAY AREAS ON
NIGHTS AND WEEKENDS TO MINIMIZE INTERRUPTIONS TO FLYING MISSIONS ON THE AIRFIELD.
THE CONTRACTOR MUST PERFORM WORK ON THE THRESHOLDS ON WEEKENDS. WORK ON THE
THRESHOLDS WILL NOT BE PERMITTED DURING NORMAL FLYING HOURS.
6. CONTRACTOR SHALL PROVIDE THE FOLLOWING EQUIPMENT AND SHALL DELIVER THE EQUIPMENT
TO THE AIRFIELD LIGHTING VAULT AND TURN THE EQUIPMENT OVER TO THE GOVERNMENT:
ONE (1) TOUGH-BOOK LAPTOP COMPUTER W/ WINDOWS 8 OPERATING SYSTEM, 4 GB RAM, 1 GB
VIDEO RAM, 500 GB HARD DRIVE & 15.4" TOUCH SCREEN MONITOR. THE COMPUTER SHALL BE
FURNISHED WITH THE LATEST VERSION OF MICROSOFT OFFICE SUITE SOFTWARE.
TWO (2) L-804 VOLTAGE DRIVEN (120 VAC) ELEVATED RUNWAY GUARD LIGHTS WITH FAA TRAFFIC
SIGNAL YELLOW LED LAMPS, INTEGRAL PHOTOCELL, AND ON/OFF SWITCH. RUNWAY GUARD
LIGHTS SHALL BE MANUFACTURED BY ADB AIRFIELD SOLUTIONS, CATALOG # ERGL-21121. NO
SUBSTITUTIONS WILL BE PERMITTED.
FIVE (5) L-810 DUAL LIGHT OBSTRUCTION LIGHT FIXTURES, 120 VAC, WITHOUT LAMPS.
OBSTRUCTION LIGHTS SHALL BE MANUFACTURED BY ADB AIRFIELD SOLUTIONS, CATALOG #
44C1007-3. NO SUBSTITUTIONS WILL BE PERMITTED.
ONE (1) 30 KW, 480 V. L-828 FERRORESONANT CONSTANT CURRENT REGULATOR POWER PACK
FOR INSTALLATION IN SWITCHGEAR REGULATOR SYSTEM. REGULATOR SHALL BE
MANUFACTURED BY ADB AIRFIELD SOLUTIONS, CATALOG # PPF2030-535. NO SUBSTITUTIONS
WILL BE PERMITTED.
TWENTY (20) SIZE 1, STYLE 2 GUIDANCE SIGN LED LAMP RETROFIT KITS FOR ONE MODULE
GUIDANCE SIGNS, COMPLETE WITH 45 W. ISOLATION TRANSFORMER, CONNECTOR KIT,
EXTENSION CORDS AND HEAT SHRINK KIT. LED RETROFIT KITS SHALL BE MANUFACTURED BY
LUMACURVE, CATALOG # S20-1-L. NO SUBSTITUTIONS WILL BE PERMITTED.
ELEVEN (11) SIZE 1, STYLE 2 GUIDANCE SIGN LED LAMP RETROFIT KITS FOR TWO MODULE
GUIDANCE SIGNS, COMPLETE WITH 45 W. ISOLATION TRANSFORMER, CONNECTOR KIT,
EXTENSION CORDS AND HEAT SHRINK KIT. LED RETROFIT KITS SHALL BE MANUFACTURED BY
LUMACURVE, CATALOG # S20-2-L. NO SUBSTITUTIONS WILL BE PERMITTED.
SIX (6) SIZE 1, STYLE 2 GUIDANCE SIGN LED LAMP RETROFIT KITS FOR THREE MODULE
GUIDANCE SIGNS, COMPLETE WITH 45 W. ISOLATION TRANSFORMER, CONNECTOR KIT,
EXTENSION CORDS AND HEAT SHRINK KIT. LED RETROFIT KITS SHALL BE MANUFACTURED BY
LUMACURVE, CATALOG # S20-3-L. NO SUBSTITUTIONS WILL BE PERMITTED.
ONE (1) SIZE 1, STYLE 2 GUIDANCE SIGN LED LAMP RETROFIT KIT FOR FOUR MODULE
GUIDANCE SIGN, COMPLETE WITH 100 W. ISOLATION TRANSFORMER, CONNECTOR KIT,
EXTENSION CORDS AND HEAT SHRINK KIT. LED RETROFIT KITS SHALL BE MANUFACTURED BY
LUMACURVE, CATALOG # S20-4-L. NO SUBSTITUTIONS WILL BE PERMITTED.
E
EXISTING FLUSH RUNWAY EDGE LIGHT - TO REMAIN.F
B
ELECTRICAL SITE PLAN - AREA 1
SCALE: 1" = 50'-0"
E L E
C T
R I C
A L
S
I T
E
P
L A
N
A
R E
KEY PLAN - AREA 2
T A
X I W
F
A
X
I W
C
L
O
S
E
D
T
A
X
I
W
D
M A
T C
H
L I N
E
ELECTRICAL SITE PLAN - AREA 2
SCALE: 1" = 50'-0"
SYMBOL INDICATES EDGE LIGHT
NUMBER AND CORRELATES
BETWEEN SITE PLAN AND WIRING
DIAGRAMS (TYP.)
EXISTING THRESHOLD
WORK NOTES:
1 PULL OUT EXISTING EDGE LIGHTING CIRCUITS & PULL NEW RUNWAY EDGE LIGHT
CIRCUITS A & B (4 # 6 L-824 TYPE C CABLES & 2 # 6 XHHW GROUNDS) IN EXISTING DUCT.
EXISTING DUCTS MAY CONTAIN CABLES WHICH MUST REMAIN IN PLACE.
2 PULL OUT EXISTING EDGE LIGHTING CIRCUITS & PULL NEW RUNWAY EDGE LIGHT
CIRCUITS A & B (2 # 6 L-824 TYPE C CABLES & 2 # 6 XHHW GROUNDS) IN EXISTING DUCT.
EXISTING DUCTS MAY CONTAIN CABLES WHICH MUST REMAIN IN PLACE.
PULL OUT EXISTING EDGE LIGHTING CIRCUIT & PULL NEW RUNWAY EDGE LIGHT
CIRCUIT A (2 # 6 L-824 TYPE C CABLES & 1 # 6 XHHW GROUND) IN EXISTING DUCT FROM
HANDHOLE TO LIGHT BASE.
PULL OUT EXISTING EDGE LIGHTING CIRCUIT & PULL NEW RUNWAY EDGE LIGHT
CIRCUIT B (2 # 6 L-824 TYPE C CABLES & 1 # 6 XHHW GROUND) IN EXISTING DUCT FROM
HANDHOLE TO LIGHT BASE.
E
E
E
F
E
F
E
E
L E
C T
R I C
A L
S
I T
E
P
L A
N
A
R E
KEY PLAN - AREA 3
T
A
X
I
W
MATCH LINE 1
M A
T C
H
L I N
E
M A
T C
H
L I N
E
ELECTRICAL SITE PLAN - AREA 3
SCALE: 1" = 50'-0"
SYMBOL INDICATES EDGE LIGHT
NUMBER AND CORRELATES
BETWEEN SITE PLAN AND WIRING
DIAGRAMS (TYP.)
WORK NOTES:
1 PULL OUT EXISTING EDGE LIGHTING CIRCUITS & PULL NEW RUNWAY EDGE LIGHT
CIRCUITS A & B (4 # 6 L-824 TYPE C CABLES & 2 # 6 XHHW GROUNDS) IN EXISTING DUCT.
EXISTING DUCTS MAY CONTAIN CABLES WHICH MUST REMAIN IN PLACE.
2 PULL OUT EXISTING EDGE LIGHTING CIRCUITS & PULL NEW RUNWAY EDGE LIGHT
CIRCUITS A & B (2 # 6 L-824 TYPE C CABLES & 2 # 6 XHHW GROUNDS) IN EXISTING DUCT.
EXISTING DUCTS MAY CONTAIN CABLES WHICH MUST REMAIN IN PLACE.
PULL OUT EXISTING EDGE LIGHTING CIRCUIT & PULL NEW RUNWAY EDGE LIGHT
CIRCUIT A (2 # 6 L-824 TYPE C CABLES & 2 # 6 XHHW GROUND) IN EXISTING DUCT FROM
HANDHOLE TO LIGHT BASE.
5 CONNECT EXISTING RUNWAY EDGE LIGHT ISOLATION TRANSFORMER TO NEW EDGE
LIGHT CIRCUIT B.
PULL OUT EXISTING EDGE LIGHTING CIRCUIT & PULL NEW RUNWAY EDGE LIGHT
CIRCUIT B (2 # 6 L-824 TYPE C CABLES & 2 # 6 XHHW GROUND) IN EXISTING DUCT FROM
HANDHOLE TO LIGHT BASE.
E
E
E
E
E
E
E
E
F
E
E
E
E
E
L E
C T
R I C
A L
S
I T
E
P
L A
N
A
R E
KEY PLAN - AREA 4
T A
X I W
C
A
T C
H
L I N
E
M A
T C
H
L I N
E
ELECTRICAL SITE PLAN - AREA 4
SCALE: 1" = 50'-0"
SYMBOL INDICATES EDGE LIGHT
NUMBER AND CORRELATES
BETWEEN SITE PLAN AND WIRING
DIAGRAMS (TYP.)
WORK NOTES:
1 PULL OUT EXISTING EDGE LIGHTING CIRCUITS & PULL NEW RUNWAY EDGE LIGHT
CIRCUITS A & B (4 # 6 L-824 TYPE C CABLES & 2 # 6 XHHW GROUNDS) IN EXISTING DUCT.
EXISTING DUCTS MAY CONTAIN CABLES WHICH MUST REMAIN IN PLACE.
2 PULL OUT EXISTING EDGE LIGHTING CIRCUITS & PULL NEW RUNWAY EDGE LIGHT
CIRCUITS A & B (2 # 6 L-824 TYPE C CABLES & 2 # 6 XHHW GROUNDS) IN EXISTING DUCT.
EXISTING DUCTS MAY CONTAIN CABLES WHICH MUST REMAIN IN PLACE.
PULL OUT EXISTING EDGE LIGHTING CIRCUIT & PULL NEW RUNWAY EDGE LIGHT
CIRCUIT A (2 # 6 L-824 TYPE C CABLES & 1 # 6 XHHW GROUND) IN EXISTING DUCT FROM
HANDHOLE TO LIGHT BASE.
PULL OUT EXISTING EDGE LIGHTING CIRCUIT & PULL NEW RUNWAY EDGE LIGHT
CIRCUIT B (2 # 6 L-824 TYPE C CABLES & 1 # 6 XHHW GROUND) IN EXISTING DUCT FROM
HANDHOLE TO LIGHT BASE.
E
E
E
F
E
E
E
E
E
E
F
E
E
E
SEE "LARGE SCALE PLAN -
TAXIWAY CHARLIE," THIS SHEET,
FOR WORK IN THIS LOCATION.
LARGE SCALE PLAN - TAXIWAY CHARLIE
SCALE: 1" = 20'-0"
REMOVE EXISTING 5'-0" X 10'-0" CONCRETE
FOUNDATION & LIGHT BASE IN ITS ENTIRETY. REMOVE
EXISTING 2" CONDUIT TO A POINT BELOW GRADE
BEYOND FOUNDATION & ABANDON IN PLACE.
CUT & PATCH EXISTING ASPHALT SHOULDER FOR
INSTALLATION OF NEW SERIES LIGHTING CIRCUIT.
SEE DETAIL, SHEET E-15.
BREAK AWAY EXISTING CONCRETE RING AROUND TAXIWAY
LIGHT & EXTEND NEW 2" PVC CONDUIT INTO EXISTING LIGHT
BASE. INTERCEPT EXISTING SERIES LIGHTING CIRCUIT IN
LIGHT BASE & EXTEND TO NEW SIGN. INSTALL NON-SHRINK
GROUT AROUND NEW CONDUIT ENTRANCE INTO BASE CAN.
EXISTING TAXIWAY SERIES LIGHTING
CIRCUIT TO REMAIN
EXISTING TAXIWAY EDGE LIGHT TO REMAIN
EXISTING PAINTED HOLD LINE
EXISTING ASPHALT SHOULDER
INSTALL NEW HOLD SIGN & CONCRETE FOUNDATION. SEE DETAILS, SHEET
E-15. INSTALL SIGN IN LINE WITH EXISTING PAINTED HOLD LINE. INSTALL
NEW CONCRETE PAD FROM THE EDGE OF THE EXISTING HANDHOLE TO THE
EDGE OF THE EXISTING ASPHALT TAXIWAY SHOULDER.
EXISTING HANDHOLE TO REMAIN
2 # 6 L-824 TYPE C CABLES IN ONE-WAY 2" CONCRETE
ENCASED DUCT. SEE DETAILS, SHEET E-15.
L E
C T
R I C
A L
S
I T
E
P
L A
N
A
R E
KEY PLAN - AREA 5
M A
T C
H
L I N
E
M A
T C
H
L I N
E
ELECTRICAL SITE PLAN - AREA 5
SCALE: 1" = 50'-0"
SYMBOL INDICATES EDGE LIGHT
NUMBER AND CORRELATES
BETWEEN SITE PLAN AND WIRING
DIAGRAMS (TYP.)
WORK NOTES:
1 PULL OUT EXISTING EDGE LIGHTING CIRCUITS & PULL NEW RUNWAY EDGE LIGHT
CIRCUITS A & B (4 # 6 L-824 TYPE C CABLES & 2 # 6 XHHW GROUNDS) IN EXISTING DUCT.
EXISTING DUCTS MAY CONTAIN CABLES WHICH MUST REMAIN IN PLACE.
2 PULL OUT EXISTING EDGE LIGHTING CIRCUITS & PULL NEW RUNWAY EDGE LIGHT
CIRCUITS A & B (2 # 6 L-824 TYPE C CABLES & 2 # 6 XHHW GROUNDS) IN EXISTING DUCT.
EXISTING DUCTS MAY CONTAIN CABLES WHICH MUST REMAIN IN PLACE.
PULL OUT EXISTING EDGE LIGHTING CIRCUIT & PULL NEW RUNWAY EDGE LIGHT
CIRCUIT A (2 # 6 L-824 TYPE C CABLES & 1 # 6 XHHW GROUND) IN EXISTING DUCT FROM
HANDHOLE TO LIGHT BASE.
PULL OUT EXISTING EDGE LIGHTING CIRCUIT & PULL NEW RUNWAY EDGE LIGHT
CIRCUIT B (2 # 6 L-824 TYPE C CABLES & 1 # 6 XHHW GROUND) IN EXISTING DUCT FROM
HANDHOLE TO LIGHT BASE.
E
E
E
E
E
E
E
E
E
E
E
E
E
E
L E
C T
R I C
A L
S
I T
E
P
L A
N
A
R E
KEY PLAN - AREA 6
T A
X I W
A
T C
H
L I N
E
M A
T C
H
L I N
E
ELECTRICAL SITE PLAN - AREA 6
SCALE: 1" = 50'-0"
SYMBOL INDICATES EDGE LIGHT
NUMBER AND CORRELATES
BETWEEN SITE PLAN AND WIRING
DIAGRAMS (TYP.)
WORK NOTES:
1 PULL OUT EXISTING EDGE LIGHTING CIRCUITS & PULL NEW RUNWAY EDGE LIGHT
CIRCUITS A & B (4 # 6 L-824 TYPE C CABLES & 2 # 6 XHHW GROUNDS) IN EXISTING DUCT.
EXISTING DUCTS MAY CONTAIN CABLES WHICH MUST REMAIN IN PLACE.
2 PULL OUT EXISTING EDGE LIGHTING CIRCUITS & PULL NEW RUNWAY EDGE LIGHT
CIRCUITS A & B (2 # 6 L-824 TYPE C CABLES & 2 # 6 XHHW GROUNDS) IN EXISTING DUCT.
EXISTING DUCTS MAY CONTAIN CABLES WHICH MUST REMAIN IN PLACE.
PULL OUT EXISTING EDGE LIGHTING CIRCUIT & PULL NEW RUNWAY EDGE LIGHT
CIRCUIT A (2 # 6 L-824 TYPE C CABLES & 1 # 6 XHHW GROUND) IN EXISTING DUCT FROM
HANDHOLE TO LIGHT BASE.
5 LOOP NEW EDGE LIGHT CIRCUIT B CONDUCTORS UNBROKEN THROUGH EXISTING
LIGHT BASE CAN WITH BLANK COVER.
PULL OUT EXISTING EDGE LIGHTING CIRCUIT & PULL NEW RUNWAY EDGE LIGHT
CIRCUIT B (2 # 6 L-824 TYPE C CABLES & 1 # 6 XHHW GROUND) IN EXISTING DUCT FROM
HANDHOLE TO LIGHT BASE.
E
E
E
E
B
F
E
E
E
E
E
E
E
E
L E
C T
R I C
A L
S
I T
E
P
L A
N
A
R E
KEY PLAN - AREA 7
M A
T C
H
L I N
E
M A
T C
H
L I N
E
ELECTRICAL SITE PLAN - AREA 7
SCALE: 1" = 50'-0"
SYMBOL INDICATES EDGE LIGHT
NUMBER AND CORRELATES
BETWEEN SITE PLAN AND WIRING
DIAGRAMS (TYP.)
WORK NOTES:
1 PULL OUT EXISTING EDGE LIGHTING CIRCUITS & PULL NEW RUNWAY EDGE LIGHT
CIRCUITS A & B (4 # 6 L-824 TYPE C CABLES & 2 # 6 XHHW GROUNDS) IN EXISTING DUCT.
EXISTING DUCTS MAY CONTAIN CABLES WHICH MUST REMAIN IN PLACE.
2 PULL OUT EXISTING EDGE LIGHTING CIRCUITS & PULL NEW RUNWAY EDGE LIGHT
CIRCUITS A & B (2 # 6 L-824 TYPE C CABLES & 2 # 6 XHHW GROUNDS) IN EXISTING DUCT.
EXISTING DUCTS MAY CONTAIN CABLES WHICH MUST REMAIN IN PLACE.
PULL OUT EXISTING EDGE LIGHTING CIRCUIT & PULL NEW RUNWAY EDGE LIGHT
CIRCUIT A (2 # 6 L-824 TYPE C CABLES & 1 # 6 XHHW GROUND) IN EXISTING DUCT FROM
HANDHOLE TO LIGHT BASE.
5 CONNECT EXISTING ISOLATION TRANSFORMER TO NEW EDGE LIGHT CIRCUIT B.
PULL OUT EXISTING EDGE LIGHTING CIRCUIT & PULL NEW RUNWAY EDGE LIGHT
CIRCUIT B (2 # 6 L-824 TYPE C CABLES & 1 # 6 XHHW GROUND) IN EXISTING DUCT FROM
HANDHOLE TO LIGHT BASE.
E
E
E
E
E
E
E
E
E
E
E
E
E
E
L E
C T
R I C
A L
S
I T
E
P
L A
N
A
R E
KEY PLAN - AREA 8
T
A
X
I
W
A
T C
H
L I N
E
ELECTRICAL SITE PLAN - AREA 8
SCALE: 1" = 50'-0"
SYMBOL INDICATES EDGE LIGHT
NUMBER AND CORRELATES
BETWEEN SITE PLAN AND WIRING
DIAGRAMS (TYP.)
EXISTING THRESHOLD
WORK NOTES:
1 PULL OUT EXISTING EDGE LIGHTING CIRCUITS & PULL NEW RUNWAY EDGE LIGHT
CIRCUITS A & B (4 # 6 L-824 TYPE C CABLES & 2 # 6 XHHW GROUNDS) IN EXISTING DUCT.
EXISTING DUCTS MAY CONTAIN CABLES WHICH MUST REMAIN IN PLACE.
2 PULL OUT EXISTING EDGE LIGHTING CIRCUITS & PULL NEW RUNWAY EDGE LIGHT
CIRCUITS A & B (2 # 6 L-824 TYPE C CABLES & 2 # 6 XHHW GROUNDS) IN EXISTING DUCT.
EXISTING DUCTS MAY CONTAIN CABLES WHICH MUST REMAIN IN PLACE.
PULL OUT EXISTING EDGE LIGHTING CIRCUIT & PULL NEW RUNWAY EDGE LIGHT
CIRCUIT A (2 # 6 L-824 TYPE C CABLES & 1 # 6 XHHW GROUND) IN EXISTING DUCT FROM
HANDHOLE TO LIGHT BASE.
5 CONNECT EXISTING ISOLATION TRANSFORMER TO NEW EDGE LIGHT CIRCUIT B.
PULL OUT EXISTING EDGE LIGHTING CIRCUIT & PULL NEW RUNWAY EDGE LIGHT
CIRCUIT B (2 # 6 L-824 TYPE C CABLES & 1 # 6 XHHW GROUND) IN EXISTING DUCT FROM
HANDHOLE TO LIGHT BASE.
E
E
E
E
E
E
L E
C T
R I C
A L
S
I T
E
P
L A
N
A
R E
ELECTRICAL PLAN - AIRFIELD LIGHTING VAULT
SCALE: 1/4" = 1'-0"
VESTIBULE
ELECTRICAL
EQUIPMENT
ELECTRICAL
EQUIPMENT
GENERATOR
ROOM
VAULT
OFFICE
OFFICE
TOILET
MECHANICAL
EXISTING CABLE TRENCH
EXISTING PULL BOX
EXISTING SERIES LIGHTING
CIRCUITS IN 4" CONDUITS
CONCEALED ABOVE CEILINGS.
EXISTING SERIES LIGHTING CIRCUITS IN 4" CONDUITS
CONCEALED BELOW FLOOR. PULL IN TWO (2) NEW # 6
XHHW (GREEN) GROUND CONDUCTORS.
EXISTING REGULATOR SWITCHGEAR -
SEE ELEVATION, SHEET E-10.
EXISTING AIRFIELD LIGHTING DUCTS - SEE
"ELECTRICAL SITE PLAN - AREA 1," SHEET E-1,
FOR CONTINUATION.
EXISTING AIRFIELD LIGHTING DUCTS - SEE
"ELECTRICAL SITE PLAN - AREA 1," SHEET E-1,
FOR CONTINUATION.
EXISTING SERIES LIGHTING CIRCUITS IN 4" CONDUIT
CONCEALED ABOVE CEILING. PULL IN TWO (2) NEW #
6 XHHW (GREEN) GROUND CONDUCTORS.
L E
C T
R I C
A L
P
L A
N
A
I R
F I E
I G
H T
I N
G
V
A U
KEY NOTES:
WIRING DIAGRAM - REGULATOR SWITCHGEAR 1
N.T.S.
ELEVATION - REGULATOR SWITCHGEAR 1
N.T.S.
2 1
SERIES CIRCUIT CUTOUT BAY.
INCOMING POWER BAY.
RUNWAY A REGULATOR.
RUNWAY B REGULATOR.
5 EXISTING # 6 L-824 TYPE C CABLES.
6 EXISTING SERIES CUT OUT - RUNWAY A.
7 EXISTING SERIES CUT OUT - RUNWAY B.
8 EXISTING 4" CONDUIT.
9 NEW # 6 AWG TYPE XHHW (GREEN) GROUND CONDUCTOR.
PROVIDE A MAINTENANCE LOOP AROUND THE CUTOUT BAY
ENCLOSURE.
10 TERMINATE NEW GROUND CONDUCTOR ON GROUND LUG
LOCATED ON FACE OF CONSTANT CURRENT REGULATOR.
11 ROUTE GROUND CONDUCTORS THRU GROMMETED
OPENINGS BETWEEN EQUIPMENT ENCLOSURE BAYS.
11 11
L E
V A
T I O
N
R
E G
U L A
T O
R
S
W I T
C H
G E
1234567891011121314151617181920212223242526272829303132333435363738394041424344454647
X
I S
T I N
G
S
O U
H
R
E S
H O
L D
EXISTING CONSTANT CURRENT REGULATOR A
AIRFIELD LIGHTING VAULT
EXISTING CONSTANT CURRENT REGULATOR B
WIRING DIAGRAM - RUNWAY CIRCUIT A
N.T.S.
EXISTING CABLE TROUGH
EXISTING MANHOLE (TYPICAL)
EXISTING HANDHOLE (TYPICAL)
E X
I S
T I N
G
N
O R
R
E S
H O
L D
1 # 6 L-824 TYPE C CABLE & 1 # 6 XHHW GROUND (TYPICAL) -
PULL INTO EXISTING DUCTS. SEE ELECTRICAL SITE PLANS FOR
ADDITIONAL INFORMATION.
2 # 6 L-824 TYPE C CABLES & 1 # 6 XHHW GROUND (TYPICAL) -
PULL INTO EXISTING DUCTS. SEE ELECTRICAL SITE PLANS FOR
ADDITIONAL INFORMATION.
B
REUSE EXISTING 2 # 6 L-824 TYPE C SERIES
LIGHTING CIRCUIT CABLES FROM EXISTING
CABLE TROUGH TO EXISTING CONSTANT
CURRENT REGULATOR. PULL IN NEW # 6
AWG TYPE XHHW GROUND CONDUCTOR TO
EXISTING CONSTANT CURRENT REGULATOR.
WORK NOTES:
PROVIDE CONNECTIONS TO (2) ISOLATION TRANSFORMERS IN
LIGHT BASE FOR BI-DIRECTIONAL FIXTURE IN THRESHOLD.
W I R
I N
G
D
I A
G R
U N
W A
Y
C
I R
C U
1234567891011121314151617181920212223242526272829303132333435363738394041424344454647
X
I S
T I N
G
S
O U
R
E S
H O
L D
EXISTING CONSTANT CURRENT REGULATOR A
AIRFIELD LIGHTING VAULT
EXISTING CONSTANT CURRENT REGULATOR B
WIRING DIAGRAM - RUNWAY CIRCUIT B
N.T.S.
EXISTING CABLE TROUGH
EXISTING MANHOLE (TYPICAL)
EXISTING HANDHOLE (TYPICAL)
E X
I S
T I N
G
N
O R
R
E S
H O
L D
1 # 6 L-824 TYPE C CABLE & 1 # 6 XHHW GROUND (TYPICAL) -
PULL INTO EXISTING DUCTS. SEE ELECTRICAL SITE PLANS FOR
ADDITIONAL INFORMATION.
2 # 6 L-824 TYPE C CABLES & 1 # 6 XHHW GROUND (TYPICAL) -
PULL INTO EXISTING DUCTS. SEE ELECTRICAL SITE PLANS FOR
ADDITIONAL INFORMATION.
B
REUSE EXISTING 2 # 6 L-824 TYPE C SERIES
LIGHTING CIRCUIT CABLES FROM EXISTING
CABLE TROUGH TO EXISTING CONSTANT
CURRENT REGULATOR. PULL IN NEW # 6
AWG TYPE XHHW GROUND CONDUCTOR TO
EXISTING CONSTANT CURRENT REGULATOR.
WORK NOTES:
PROVIDE CONNECTIONS TO (2) ISOLATION TRANSFORMERS IN
LIGHT BASE FOR BI-DIRECTIONAL FIXTURE IN THRESHOLD.
W I R
I N
G
D
I A
G R
U N
W A
Y
C
I R
C U
DETAIL - RUNWAY EDGE LIGHT WITH ADJACENT HANDHOLE
EXISTING ISOLATION TRANSFORMER
EXISTING LIGHT BASE CAN
EXISTING GROUND LUG
EXISTING MEDIUM INTENSITY RUNWAY EDGE LIGHT -
ELEVATED OR FLUSH, AS INDICATED ON SITE PLANS.
PROVIDE P606 SEALANT AROUND
FIXTURE HEAD AFTER FLUSH EDGE LIGHT
IS REINSTALLED ON BASE CAN
EXISTING CONDUIT - PULL IN NEW
CONDUCTORS, AS INDICATED ON
SITE PLANS.
EXISTING HANDHOLE
PROVIDE NEW L-823 CONNECTORS
WITH HEAT SHRINK KITS
NEW # 6 L-824 TYPE C
CABLES - LEAVE MINIMUM
4'-0" SLACK IN HANDHOLE.
NEW # 6 L-824 TYPE C CABLES -
LEAVE MINIMUM 2'-0" SLACK IN
BASE CAN.
# 6 AWG TYPE XHHW (GREEN) GROUND CONDUCTORS -
LEAVE MINIMUM 4'-0" SLACK IN HANDHOLE.
# 6 AWG TYPE XHHW (GREEN)
GROUND CONDUCTORS -
LEAVE MINIMUM 2'-0" SLACK IN
BASE CAN.
DISCONNECT EXISTING GROUNDING CONNECTION
FROM EXISTING GROUND LUG ON BASE CAN.
ABANDON EXISTING GROUND
ROD IN PLACE.
DETAIL - RUNWAY EDGE LIGHT WITH REMOTE HANDHOLE
N.T.S.
EXISTING LIGHT BASE CAN
EXISTING GROUND LUG
PROVIDE P606 SEALANT AROUND
FIXTURE HEAD AFTER FLUSH EDGE LIGHT
IS REINSTALLED ON BASE CAN
EXISTING CONDUIT - PULL IN NEW
CONDUCTORS, AS INDICATED ON
SITE PLANS.
EXISTING HANDHOLE
PROVIDE NEW L-823
CONNECTORS WITH HEAT
SHRINK KITS
NEW # 6 L-824 TYPE C CABLES -
LEAVE MINIMUM 2'-0" SLACK IN
BASE CAN.
# 6 AWG TYPE XHHW (GREEN) GROUND CONDUCTORS -
LEAVE MINIMUM 4'-0" SLACK IN HANDHOLE.
# 6 AWG TYPE XHHW (GREEN)
GROUND CONDUCTORS -
LEAVE MINIMUM 2'-0" SLACK IN
BASE CAN.
DISCONNECT EXISTING GROUNDING CONNECTION
FROM EXISTING GROUND LUG ON BASE CAN.
ABANDON EXISTING GROUND
ROD IN PLACE.
EXISTING ISOLATION
TRANSFORMER
DETAIL - THRESHOLD LIGHT AND RUNWAY EDGE LIGHT WITHOUT HANDHOLE
N.T.S.
EXISTING LIGHT BASE CAN
EXISTING GROUND LUG
PROVIDE P606 SEALANT AROUND
FIXTURE HEAD AFTER FLUSH EDGE LIGHT
IS REINSTALLED ON BASE CAN
PROVIDE NEW L-823
CONNECTORS WITH HEAT
SHRINK KITS
NEW # 6 L-824 TYPE C CABLES - LEAVE
MINIMUM 2'-0" SLACK IN BASE CAN.
DISCONNECT EXISTING GROUNDING CONNECTION
FROM EXISTING GROUND LUG ON BASE CAN.
ABANDON EXISTING GROUND
ROD IN PLACE.
EXISTING ISOLATION TRANSFORMER -
BI-DIRECTIONAL THRESHOLD LIGHTS HAVE TWO
TRANSFORMERS IN EACH LIGHT BASE.
UNIDIRECTIONAL THRESHOLD LIGHTS AND
RUNWAY EDGE LIGHTS HAVE ONE
TRANSFORMER IN EACH LIGHT BASE.
EXISTING CONDUIT - PULL IN NEW
CONDUCTORS, AS INDICATED ON SITE PLANS.
EXISTING MEDIUM INTENSITY RUNWAY EDGE LIGHT -
ELEVATED OR FLUSH, AS INDICATED ON SITE PLANS.
EXISTING MEDIUM INTENSITY RUNWAY EDGE LIGHT OR
THRESHOLD LIGHT - ELEVATED OR FLUSH, AS INDICATED
ON SITE PLANS.
NEW # 6 L-824 TYPE C
CABLES - LEAVE MINIMUM
4'-0" SLACK IN HANDHOLE.
# 6 AWG TYPE XHHW (GREEN) GROUND CONDUCTORS -
LEAVE MINIMUM 2'-0" SLACK IN BASE CAN.
DETAIL - FLUSH RUNWAY EDGE LIGHT IN TAXIWAY
N.T.S.
EXISTING LIGHT BASE CAN
EXISTING GROUND LUG
PROVIDE P606 SEALANT AROUND
FIXTURE HEAD AFTER EDGE LIGHT IS
REINSTALLED ON BASE CAN
PROVIDE NEW L-823
CONNECTORS WITH HEAT
SHRINK KITS
NEW # 6 L-824 TYPE C CABLES - LEAVE
MINIMUM 2'-0" SLACK IN BASE CAN.
DISCONNECT EXISTING GROUNDING CONNECTION
FROM EXISTING GROUND LUG ON BASE CAN.
ABANDON EXISTING GROUND
ROD IN PLACE.
EXISTING ISOLATION
TRANSFORMER
EXISTING CONDUIT - PULL IN NEW
CONDUCTORS, AS INDICATED ON SITE PLANS.
EXISTING FLUSH MEDIUM INTENSITY
RUNWAY EDGE LIGHT
# 6 AWG TYPE XHHW (GREEN) GROUND CONDUCTORS -
LEAVE MINIMUM 2'-0" SLACK IN BASE CAN.
DRILL OUT ANY BROKEN BOLTS AND RE-TAP ALL
BOLT HOLES ON LIGHT BASE CANS. REPLACE ALL
BOLTS W/ NEW STAINLESS STEEL BOLTS AND APPLY
ANTI-SIEZE COMPOUND TO BOLTS.
NOTE:
E
T A
I
U N
W A
Y
E
D G
E
L I G
H
DETAIL - DISTANCE REMAINING MARKER INSTALLATION
FINISHED GRADE7
48"
48"
6"
12"
40"
STAINLESS STEEL BIRD SPIKES -
ATTACH TO SIGN W/ TWO PART
EPOXY. DO NOT ATTACH BIRD
SPIKES TO SIGN W/ SCREWS, OR
PENETRATE THE TOP OF THE
SIGN ENCLOSURE.
EXISTING GROUND ROD
EXISTING LIGHT BASE CAN
EXISTING GROUND LUG
NEW L-823 CONNECTORS WITH
HEAT SHRINK KITS
NEW 45 W., 6.6/6.6 A.
ISOLATION TRANSFORMER
EXISTING SERIES LIGHTING
CIRCUIT CONDUIT
NEW DISTANCE REMAINING MARKER
PROVIDE NEW FRANGIBLE COUPLINGS
PROVIDE NEW FLOOR FLANGE. DRILL EXISTING CONCRETE AS REQUIRED
FOR NEW INSTALLATION. ATTACH FLANGE TO CONCRETE FOUNDATION
WITH STAINLESS STEEL EXPANSION BOLTS.
CONNECT JUMPER CABLES TO NEW DISTANCE REMAINING MARKER
HOUSING W/ 1 1/2" LIQUID-TIGHT FLEXIBLE METALLIC CONDUIT.
INSTALL NEW NYLON COMPOSITE BASE
PLATE ON EXISTING L-867 LIGHT BASE.
CONNECT FLEXIBLE CONDUIT FITTING TO
BASE PLATE. DRILL OUT ANY BROKEN BOLTS
AND RE-TAP ALL BOLT HOLES. REPLACE ALL
BOLTS W/ NEW STAINLESS STEEL BOLTS AND
APPLY ANTI-SIEZE COMPOUND TO BOLTS.
DISTANCE REMAINING MARKER DEMOLITION NOTE:
REMOVE EXISTING DISTANCE REMAINING MARKER. REMOVE EXISTING PLEXIGLASS BASE CAN LID.
REMOVE EXISTING FLEXIBLE CONDUIT & WIRING CONNECTION FROM BASE CAN TO MARKER. REMOVE
EXISTING ISOLATION TRANSFORMER & ASSOCIATED CONNECTORS. REMOVE EXISTING FRANGIBLE
COUPLINGS AND FLOOR FLANGES.
EXISTING CONCRETE FOUNDATION
NEW L-858B DISTANCE REMAINING MARKER W/
WHITE GRAPHIC ON BLACK BACKGROUND. DISTANCE
REMAINING MARKER SHALL BE MANUFACTURED BY
LUMACURVE. NO SUBSTITUTIONS WILL BE
PERMITTED. MARKER SHALL BE SIZE 4, STYLE 2, 1
MODULE WITH LED LAMPS, AND SHALL HAVE
GRAPHIC NUMERALS AS INDICATED ON THE
ELECTRICAL SITE PLANS.
E
T A
I
I S
T A
N C
E
R
E M
A I N
I N
G
M
A R
K E
SECTION
FRANGIBLE COUPLING
CABLE CLAMP
JUMPER CABLE
PLUG (FURN. W/ SIGN)
FLOOR FLANGE
TOP OF 2" CONDUIT - EVEN W/
TOP SURFACE OF CONCRETE PAD.
CONNECTOR (STYLE 7, TYPE 2, CLASS A)
N.T.S.
ELECTRICAL CONNECTION DETAIL
GRADE 60 REBAR - # 4
3500 PSI CONCRETE PAD
FRONT
2" PVC CONDUIT
6"
6"
6"
A
SEE "ELECTRICAL CONNECTION
DETAIL," THIS SHEET.
GRADE
DETAIL - HOLD SIGN ASSEMBLY
NOT TO SCALE
C
6"
12" Ø L-867 TRANSFORMER BASE
CONCRETE PAD
(APPROX. DIMENSIONS)
62"±
10'-8"
PLAN - CONCRETE PAD
NOT TO SCALE
FAA L-830 45 W. 6.6/6.6 AMP
ISOLATING TRANSFORMER
24"24"
1" MAX.
NOT TO SCALE
AT 12" O.C., EACH WAY.
INSTALL REBAR W/ 3"
MIN. COVER.
FACTORY MOLDED L-823
PLUGS & RECEPTACLES.
6"
12"
10 '-0" FROM
EDGE OF
TAXIWAY
# 4 BSDC COUNTERPOISE - CONNECT
TO EXISTING COUNTERPOISE. STOP
COUNTERPOISE 12" AWAY FROM SIGN
FOUNDATION.
36 - 18
NEW FAA L-858L/L-858R HOLD SIGN, SIZE 1, STYLE 2
W/ LED LAMPS, FIBERGLASS HOUSING & GRAPHICS,
AS DETAILED. SIGN SHALL BE MANUFACTURED BY
LUMACURVE. NO SUBSTITUTIONS WILL BE
PERMITTED. REAR OF SIGN SHALL HAVE BLANK
(BLACK) PANELS.
WHITE GRAPHIC W/ BLACK
OUTLINE ON RED BACKGROUND
YELLOW GRAPHIC ON
BLACK BACKGROUND
3"
3000 P.S.I. CONCRETE
N.T.S.
3"
3"
2" PVC CONDUIT (TYP.)
3"
4" MIN.
12"
24"
WARNING TAPE
COUNTERPOISE CONDUCTOR
FINISHED GRADE
DETAIL - ONE WAY 2" CONCRETE
ENCASED DUCT
ASPHALT CUT & PATCH DETAIL
APPROVED BACKFILL TAMPED
IN 6" LIFTS - SEE SPECS.
EXISTING BASE
6" - 3500 P.S.I. CONCRETE
N.T.S.
PAVEMENT
SAW CUT EXISTING
WIDTH AS REQD.
24" (MIN.)
EXISTING ASPHALT PAVING
NEW ASPHALT CEMENT - SEE
SPECIFICATION SECTION 02556.
GROUND LUG
3/4" X 10'-0" COPPERCLAD GROUND
ROD. BOND W/ EXOTHERMIC WELD.
# 6 BARE COPPER GROUND
CONDUCTOR.
L-867 BASE W/ BLANK
COVER. APPLY ANTI-
SEIZE COMPOUND TO
STAINLESS STEEL BOLTS.
STAINLESS STEEL BIRD SPIKES -
ATTACH TO SIGN W/ TWO PART
EPOXY. DO NOT ATTACH BIRD
SPIKES TO SIGN W/ SCREWS, OR
PENETRATE THE TOP OF THE
SIGN ENCLOSURE.
E
T A
I
O
G
N