DESIGN ANALYSIS
FOR
REPAIR (SUS) VARIOUS BUILDING SYSTEMS
COMM FAC; BUILDNG 861
PROJECT NO. VDYD 15-1246
100% DESIGN SUBMITTAL
April 25, 2017
SCOTT AIR FORCE BASE, ILLINOIS
Prepared By:
Evansville, IN
A-E CONTRACT NO. FA 4407-14-D-0018
INDEX
I. ARCHITECTURAL
II. PLUMBING
III. FIRE PROTECTION
IV. HEATING, VENTILATION, AND AIR CONDITIONING
V. ELECTRICAL
APPENDIX A – EQUIPMENT CUT SHEETS
APPENDIX B – LIMITED ASBESTOS, LEAD PAINT, AND MICROBIAL SURVEY
APPENDIX C – CONFIRMATION NOTICES
I. ARCHITECTURAL
A. GENERAL PARAMETERS
1. Replace all ceiling tiles and associated grid with exception of areas denoted on plans. Replace/patch gypsum board ceilings/soffits/bulkheads as necessary to install new above ceiling MEP work. New grid and ceiling tiles are to be at the same height as the existing ceilings to retain the sprinkler head and fire alarm locations.
2. Repair/Patch walls in areas where fans, louvers, ducts and piping is removed.
3. Install new support structure beneath existing trusses to support new gypsum board ceiling at areas indicated on reflected ceiling plan. Install batt insulation above gypsum board ceiling at all locations.
4. Install new lighting at all spaces within project limits.
5. Remove gypsum board at all exterior walls within project limits. Remove any rotted or termite infested framing members and replace with like size members.
Install new gypsum board sheathing and match existing finishes including wall base, paint and/or wallcovering.
6. Remove sealant at all windows. Install new caulk/sealant at all windows.
Secure all sills beneath windows receiving new sealant.
7. Replace all downspouts for the entire building. Re-seal all gutters for the entire building.
8. Install new soffit lighting at exterior entrances and exits.
B. FUNCTIONAL AND TECHNICAL DATA
1. Design Criteria
a. Scott Air Force Base – Architectural compatibility plan. January 2000.
b. Air Mobility Command – Interior Design Guide, April 1994.
c. UBC Building Code.
d. ADAAG – Americans with disabilities guidelines.
e. Federal, state, and local code including EPA and state historic preservation office standards.
C. DESIGN OBJECTIVES
1. The West side of the Building as indicated on plans has been renovated under previous project. Existing VAV boxes are to be replaced in this area.
2. Replace all ceiling tile and grid as indicated. (Proposed product: Armstrong, “Fine Fissured" #1728)
3. Repair exterior walls at locations of removed fan coil units, louvers, ducts, pipes and fans. Repair exterior wall where framing has rotted or deteriorated due to moisture or termite infestation. Install new gypsum board at exterior walls.
Paint.
4. Replace downspouts and seal gutters around entire building.
5. Re-seal all window units.
II. PLUMBING
A. SCOPE
1. The plumbing fixtures in the renovated restroom will be first quality, vitreous china, ADA accessible, counter top mounted with floor mounted water closets, chrome plated flush valves and faucets.
2. Water closets, lavatories and urinals will be installed in the renovated men’s and ladies’ restroom.
3. Provide new sanitary, waste, vent and water to new fixtures.
4. Remove all existing cold, hot/hot water return piping with new. This includes a point from the incoming service to toilet rooms and water heater.
5. Remove existing water heater and provide new to match existing.
B. TECHNICAL REQUIREMENTS
a. The following technical manuals will be used:
- Military Handbook MIL-HDBK, “Facility
Planning and Design Guide”
- National Plumbing Code
1. Plumbing fixtures in the renovated restroom will be vitreous china. The designated fixtures will be ADA compliant.
2. Water closets will be floor mounted and flush valves.
3. The urinal will be wall mounted with floor mounted carrier and flush valve.
4. Lavatories will be counter top mounted with auto faucets.
5. Remove all existing galvanized and copper pipe in the building serving existing restrooms and water heater with new copper pipe and fittings throughout the construction area.
D. DESIGN CALCULATIONS
1. Refer to Appendix A for plumbing load calculations and equipment data.
III. FIRE PROTECTION
A. SCOPE
1. The sprinkler heads will be replaced with new in rooms indicated.
2. Sprinkler piping drops to sprinkler heads will be adjusted to new elevation of ceilings in all rooms.
B. TECHNICAL REQUIREMENTS
- Military Handbook MIL-HDBK 1008C, “Fire Protection for Facilities, Design, and
Construction”
1. Modify sprinkler head piping as required for installation of new ceilings.
2. Replace existing sprinkler heads with new.
IV. HEATING, VENTILATING AND AIR CONDITIONING
A. SCOPE
1. Remove existing fan coil units and associated piping and controls.
2. Remove existing fan power terminal units and associated hot water coils and automatic BAS controls.
3. The existing hot water boilers and air cooled chiller will be reused.
4. Provide a temperature control system (Direct Digital Control) for existing and project HVAC upgrade area. The existing heating/cooling system will have terminal units replaced and updated BMS control system.
5. Provide new pumps for chilled and hot water distribution systems.
6. Provide new supply fan motor for air handling unit, extend ductwork and fan powered VAV terminal units to serve the spaces currently served by fan coil units in the building. New grilles will be provided.
7. Ventilation for the building will be in accordance with American Society of Heating, Refrigeration, Air Conditioning Engineers (ASHRAE). Ventilation for Acceptable Indoor Air Quality, Standard 62-2016.
B. FUNCTIONAL AND TECHNICAL REQUIREMENTS
1. Design Criteria.
a. The following technical manuals will be used:
- ASHRAE Handbook “2013 Fundamentals” and “2012 HVAC Systems and Equipment”
- Unified Facilities Criteria (UFC) Heating, Ventilating, and Air Conditioning Systems, UFC 3-410-01, 1 July 2013, Change 2, October 2015
b. Design Conditions
Outside Design: Winter 9oF (99.6% ASHRAE 2013 Fundamentals Chapter 27.10)
Summer 91.4oF Dry Bulb (1% ASHRAE 2013 Fundamentals Chapter 27.11) 75.5oF Wet Bulb
Inside Design: Winter 68oF Summer 75oF
30-60% RH
c. Outdoor Air Ventilation:
Outdoor ventilation air will be provided according to (ASHRAE)
Standard 62-1999. Ventilation is listed in cubic feet per minute (CFM) per occupant.
Offices and Meeting Rooms……………………….0.06 CFM/ FT2 plus 5 CFM/person
1. Remove existing fan coil units. Remove all associated piping and temperature controls.
2. Provide increased airflow on existing air handling unit, extend supply ductwork, return ductwork and accessories. Return will utilize a ceiling return plenum, ductwork will be required for air transfers, etc.
3. Provide new supply and return ceiling grilles and diffusers.
4. Provide replacement/updated chilled water and hot water building distribution pumps. System will utilize a 4-pipe water distribution system.
5. Provide replacement/updated thermostats and temperature control wiring to control the VAV terminal units and air handling unit.
6. Provide new exhaust fans serving restrooms.
7. Reuse existing chiller.
8. Reuse existing boilers.
D. DESIGN CALCULATIONS
1. Refer to Appendix B for HVAC load calculations and equipment data.
V. ELECTRICAL
A. GENERAL PARAMETERS
1. Electrical work will include:
a. Remove and replace building lighting in wings 2, 3, 4, 7, 8 and interconnecting corridors with high efficient LED lighting.
b. Replace all exterior lighting at building exits with high efficient LED lighting.
c. Remove electric to HVAC equipment scheduled to be replaced and provide electric to new HVAC equipment.
d. Temporarily remove, support, and reinstall raceways on exterior walls where the interior wall finish is to be removed and replaced.
B. FUNCTIONAL AND TECHNICAL DATA
- National Electrical Code, NFPA 70
- National Fire Protection Association – NFPA
- International Building Code
- Interior Electrical Systems – UFC 3-520-01
- “Illuminating Engineering Society”, IES
- International Energy Conservation Code IECC 2012
1. Lighting.
a. The following maintained illumination levels will be used in designing the lighting systems.
- Conference – 50 footcandles
- Restrooms – 20 footcandles
- Storage/Closets – 20 footcandles
- Mechanical and Electrical Rooms – 20 footcandles
- Open Office Area – 50 footcandles
- Offices – 50 footcandles
b. High efficient LED lighting fixtures will be provided in all spaces indicated within this scope of work. 2'x4' fixtures will be provided in the majority of the areas. Selected spaces will receive LED downlighting where 2'x4' style fixtures are not appropriate.
c. Wall mounted passive infrared (PIR) vacancy sensors will be provided in small individual offices as lighting control.
d. Ceiling mounted passive infrared and ultrasonic occupancy sensors will be provided in large offices or in open office spaces.
e. Lighting control will be set to manual ON and automatic OFF.
f. Exterior lighting control will be by photoelectric sensor for dusk-to-dawn operation.
g. Exit light and emergency egress lighting will be served from integral emergency battery packs.
2. HVAC Electric.
a. All branch circuits to HVAC equipment scheduled to be removed will be removed back to source.
b. New branch circuits will be provided to new HVAC equipment. The existing branch panelboards do not appear to have capacity to serve the
HVAC equipment. Panelboards will be added in selected locations to provide power to equipment.
c. The air handling unit feeder will be upsized to accommodate the increased motor load.
d. Pumps scheduled to be replaced will be provided with new motor controllers.
3. Temporary support of exterior wall devices.
a. Where the wall finish on the exterior walls is scheduled to be removed, the existing surface mounted devices will be temporarily removed from wall and supported during construction. Devices will be reinstalled at previous locations.
APPENDIX A – EQUIPMENT CUT SHEETS
FS Series
2FSL4
2' x 4'
LED
LED 2FSL4-2X4
Catalog Number
Notes
Type
FEATURES & SPECIFICATIONS
INTENDED USE — The FS Series recessed LED luminaire combines modern aesthetics and performance in a general lighting product that enables the transformation from fluorescent to LED. The high efficacy light engine delivers long life and excellent color to ensure a quality lighting installation. Integrated controls options provide for design flexibility and optimum energy savings.
Multiple lumen packages and driver options provide solutions for all your lighting applications.
Certain airborne contaminants can diminish integrity of acrylic. Click here for Acrylic Environmental Compatibility table for suitable uses.
CONSTRUCTION — Rugged, one-piece cold-rolled steel coated polyester, painted after fabrication. The satin white lens provides excellent shielding and wide distribution. End plates include integral T-bar clips.
Fixture may be mounted and wired in continuous rows. Total fixture height is only 4-3/8".
ELECTRICAL — Long-life LEDs, coupled with high-efficiency drivers, provide superior illumination for extended service life. 90% LED lumen maintenance at 60,000 hours (L90/60,000). The LEDs have a CRI of 82.
eldoLED driver options deliver choice of dimming range, and choices for control, while assuring flicker-free, low-current inrush, 89% efficiency and low EMI.
Optional integrated nLight® controls make each luminaire addressable - allowing it to digitally communicate with other nLight enabled controls such as dimmers, switches, occupancy sensors and photocontrols. Simply connect all the nLight enabled control devices and the FSL luminaires using standard CAT-5 cabling. Unique plug-and-play convenience allows devices and luminaires to automatically discover each other and self-commission.
Lumen Management: Unique lumen management system (option N80) provides onboard intelligence that actively manages the LED light source so that constant lumen output is maintained over the system life, preventing the energy waste created by the traditional practice of over-lighting.
Step-level dimming option allows system to be switched to 50% power for compliance with common energy codes while maintaining fixture appearance.
Driver disconnect provided where required to comply with US and Canadian codes.
INSTALLATION — Unique grid interfacing arrangement provides mounting into standard 1" and 9/16" tee bar or screw slot grids. 9/16" allows fixture trim to hang level with architectural ceiling tiles. Drywall ceiling adaptors available. Suitable for damp location.
LISTINGS — CSA certified to meet US and Canadian standards. IC rated. DesignLights Consortium® (DLC) Premium qualified product. Not all versions of this product may be DLC Premium qualified. Please check the DLC Qualified Products List at www.designlights.org/QPL to confirm which versions are qualified.
WARRANTY — 5-year limited warranty. Complete warranty terms located at www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx
Note: Actual performance may differ as a result of end-user environment and application.
All values are design or typical values, measured under laboratory conditions at 25 °C.
Specifications subject to change without notice.
Stock Configurations
2FSL4 40L EZ1 LP835
2FSL4 40L EZ1 LP840
Capable Luminaire This item is an A+ capable luminaire, which has been designed and tested to provide consistent color appearance and out-of-the-box control compatibility with simple commissioning.
• All configurations of this luminaire meet the Acuity Brands’ specification for chromatic consistency
• This luminaire is part of an A+ Certified solution for nLight® control networks when ordered with drivers marked by a shaded background*
• This luminaire is part of an A+ Certified solution for nLight control networks, providing advanced control functionality at the luminaire level, when selection includes driver and control options marked by a shaded background*
To learn more about A+, visit www.acuitybrands.com/aplus.
*See ordering tree for details http://Click here for Acrylic Environmental Compatibility table for suitable uses.
http://Click here for Acrylic Environmental Compatibility table for suitable uses.
2FSL4 LED Recessed Lighting 2'x4'
LED 2FSL4-2X4
2FSL4
Series Air function Lumens Lens Voltage Driver Color temperature Controls5 Options
2FSL4 2X4 FSL (blank) Static H Heat removal
30L 30001
40L 40001
48L 48001
60L 60001
72L 72001
(blank) Satin white
(blank) MVOLT 347 3472
EZ1 eldoLED dims to 1%, 0-10V
EZB eldoLED dims to black, 0-10V
EDB eldoLED DALI3
EXB eldoLED DMX/
RDM3
SLD Step-level dimming3,4
EXA1 Dims to 1%, XPoint wireless enabled
EXAB Dims to dark, XPoint wireless enabled
EOHN On/Off (non-dim)
LP830 3000 K
LP835 3500 K
LP840 4000 K
LP850 5000 K
(blank) No controls N80 nlight® with 80% lumen manage-ment
N80EMG nlight® with 80% lumen manage-ment. For use with generator supply EM power.
N100 nlight® without lumen manage-ment
N100EMG nlight® without lumen manage-ment. For use with generator supply EM power.
EL7L 700 lumen battery pack
EL14L 1400 lumen battery pack
CP Chicago plenum
PWS1836 6' prewire, 3/8" diameter, 18-gauge, 1-circuit
PWS1846 6' prewire, 3/8" diameter, 18-gauge, 2-circuit
RRL_ RELOC®-ready luminaire6
NPLT Narrow pallet
ORDERING INFORMATION Lead times will vary depending on options selected. Consult with your sales representative. Example: 2FSL4 40L EZ1 LP835 N100
Notes 1 Approximate lumen output.
2 Consult factory for availability. Not available with SLD, EL7L, or EL14L.
3 Not available with N80, N80EMG, N100 or N100EMG.
4 When using prewire option, use PWS1846.
5 nIO access limitations on 30L or EZB.
6 For ordering logic consult: RRL_2013.
Accessories: Order as separate catalog number.
2FS4 F916 Trim to adjust fixture mounting flush with 9/16" T-bar; for 2x4 fixture
DGA24 FS/VT Drywall ceiling adaptor , unit installation
A+ Capable options indicated by this color background.
2FSL4 48L LP835, test no. LTL24699P9, tested in accordance to IESNA LM-79
2FSL4 LED Recessed Lighting 2'x4'
PHOTOMETRICS
2FSL4 40L LP835, test no. LTL24699P5, tested in accordance to IESNA LM-79
0° 20°
40°
60°
80°
90°
0°0°0° 90°
180°
Coefficients of Utilization pf 20% pc 80% 70% 50% pw 70%50%30% 50%30%10% 50%30%10%
R C
R
Zonal Lumen Summary Zone Lumens % Lamp % Fixture 0° - 30° 0° - 40° 0° - 60° 0° - 90° 90° - 180° 0° - 180°
26.9 43.9 77.5
100.0 0.0
100.0
26.9 43.9 77.5
100.0 0.0
100.0
CP Summary 0° 90
0° 5° 15° 25° 35° 45° 55° 65° 75° 85°
0° 20°
40°
60°
80°
90°
0°0°0° 90°
180°
Coefficients of Utilization pf 20% pc 80% 70% 50% pw 70%50%30% 50%30%10% 50%30%10%
R C
R
Zonal Lumen Summary Zone Lumens % Lamp % Fixture 0° - 30° 0° - 40° 0° - 60° 0° - 90° 90° - 180° 0° - 180°
26.9 43.9 77.5
100.0 0.0
100.0
26.9 43.9 77.5
100.0 0.0
100.0
CP Summary 0° 90
0° 5° 15° 25° 35° 45° 55° 65° 75° 85°
Performance Data Lumen package Input watts 1 Lumens LPW
30L LP830 30.7 3170 103
30L LP835 30.8 3341 108
30L LP840 30.9 3430 111
30L LP850 31.0 3664 118
40L LP830 39.2 3994 102
40L LP835 39.4 4247 108
40L LP840 39.5 4368 111
40L LP850 39.6 4637 117
48L LP830 46.2 4596 100
48L LP835 46.4 4856 105
48L LP840 46.6 4995 107
48L LP850 46.7 5347 115
60L LP830 52.0 5071 98
60L LP835 52.2 5373 103
60L LP840 52.4 5531 106
60L LP850 52.5 5867 112
72L LP830 69.5 6758 97
72L LP835 70.0 6847 98
72L LP840 70.2 7433 106
72L LP850 70.3 7823 111
LED 2FSL4-2X4
2FSL4-2X4
LED: One Lithonia Way Conyers, GA 30012 Phone: 800-858-7763 Fax: 770-929-8789 www.lithonia.com © 2014-2016 Acuity Brands Lighting, Inc. All rights reserved. Rev. 09/22/16
2FSL4 LED Recessed Lighting 2'x4'
Specifications
Length: 48 (122.0)
Width: 24 (61.0)
Depth: 4-3/8 (11.1)
Notes
With nlight 80% lumen management input watts start at 37 and gradually increasing to 46 at 50,000 hrs when using 48L system.
15-3/4 (40)
(61)
4-3/8 (11.1)
Constant Lumen Management Enabled by the embedded nLight control, the FSL actively tracks its run-time and manages its light source such that constant lumen output is maintained over the system life. Referred to as lumen management, this feature eliminates the energy waste created by the traditional practice of over-lighting.
0 10 20 30 40 50
THOUSAND OPERATING HOURS
0 10 20 30 40 50
THOUSAND OPERATING HOURS
POWER INPUT
LIGHT
OUTPUT
100%
80%
100%
80% 37W37W
LI
G
H T
O U
TP
U
T
LI
G
H T
O U
TP
U
T
PO
W
ER
IN
PU
T
PO
W
ER
IN
PU
T
Without Lumen Management Energy is wasted and light level is inconsistent.
POWER
INPUT
LIGHT OUTPUT
With Lumen Management Energy is saved and light level remains consistent.
Wasted Energy
Saved Energy
46W 46W
9/16 with accessory 2FS4 F916
9/16 15/16
SS
nLight® Control Accessories:
Order as separate catalog number. Visit www.sensorswitch.com/nLight for complete listing of nLight controls.
WallPod stations Model number Occupancy sensors Model number On/Off nPODM [color] Small motion 360°, ceiling (PIR / dual tech) nCM 9 / nCM PDT 9 On/Off & Raise/Lower nPODM DX [color] Large motion 360°, ceiling (PIR / dual tech) nCM 10 / nCM PDT 10 Graphic Touchscreen nPOD GFX [color] Wide view (PIR / dual tech) nWV 16 / nWV PDT 16 Photocell controls Model number Wall Switch w/ Raise/Lower (PIR / dual tech) nWSX LV DX / nWSX PDT LV DX On/Off & Dimming nCM ADCX Cat-5 cables (plenum rated) Model number
10', CAT5 10FT CAT5 10FT J1
15', CAT5 15FT CAT5 15FT J1
MOUNTING DATA DIMENSIONS
All dimensions are inches (centimeters) unless otherwise specified.
Luminaire Type:
Catalog Number (autopopulated):
GOTHAM ARCHITECTURAL DOWNLIGHTING | P 800.315.4982 | gothamlighting.com
© 2010-2016 Acuity Brands Lighting, Inc. All Rights Reserved. Rev. 10/12/16. Specifications subject to change without notice.PAGE 1 OF 4
EVO-6-OPEN
Gotham Architectural Downlighting LED Downlights
6” Evo®
Downlight
Solid-State Lighting
OPTICAL SYSTEM
• Self-flanged or flangeless semi-specular, matte-diffuse or specular finishing trim
• Patented Bounding Ray™ optical design (U.S. Patent No. 5,800,050)
• 45° cutoff to source and source image
• Top-down flash characteristic
• Polycarbonate lens integral to light engine
MECHANICAL SYSTEM
• 16-gauge galvanized steel construction; maximum 1-1/2” ceiling thickness
• Telescopic mounting bars maximum of 32” and minimum of 15”, preinstalled, 4” vertical adjustment
• Toolless adjustments post installation
• Junction box capacity: 8 (4 in, 4 out ) 12AWG rated for 90°C
• Light engine and driver accessible through aperture
• Injection molded mud ring includedwith flangeless trims. Ships separately.
Installs independently of the mounting frame to reduce cracks in plaster due to vibration.
ELECTRICAL SYSTEM
• Fully serviceable and upgradeable lensed LED light engine
• 70% lumen maintenance at 60,000 hours
• Tested according to LM-79 and LM-80 standards
• Overload and short circuit protected
• 2.5 SDCM; 85 CRI typical, 90+ CRI optional
LISTINGS
• Fixtures are CSA certified to meet US and Canadian standards; wet location, covered ceiling
WARRANTY
• 5-year limited warranty. Complete warranty terms located at:
www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx
Note: Actual performance may differ as a result of end user environment and application.
All values are design or typical values, measured under laboratory conditions at
25 °C.
FEATU
RES
ORDERIN
G IN
FORM
ATION
EXAMPLE: EVO 35/10 6AR MWD LSS MVOLT EZ1
Series Color temperature Nominal lumen values Aperture/Trim color Trim Style Distribution Finish Voltage
EVO 27/ 2700 K
30/ 3000 K 35/ 3500 K 40/ 4000 K
10 1000 lumens 15 1500 lumens 20 2000 lumens 25 2500 lumens 30 3000 lumens 35 3500 lumens 40 4000 lumens 45 4500 lumens
6AR Clear 6PR Pewter 6WTR Wheat 6GR Gold 6WR1 White 6BR1 Black 6WRAMF1 White anti-microbial
(blank) Self-flanged FL Flangeless
VND Very narrow (0.5 s/mh)
ND Narrow (0.7 s/mh)
MD Medium (0.9 s/mh)
MWD Medium wide (1.0 s/mh)
WD Wide (1.2 s/ mh)
LSS Semi-specular LD Matte-diffuse LS Specular
MVOLT
Driver3 Options
EZ10 eldoLED 0-10V ECOdrive. Linear dimming to 10% min.
EZ1 eldoLED 0-10V ECOdrive. Linear dimming to 1% min.
EZB eldoLED 0-10V SOLOdrive. Logarithmic dimming to <1%.
EDAB eldoLED SOLOdrive DALI. Logarithmic dimming to <1%.
EDXB eldoLED POWERdrive DMX with RDM (remote device management).
Square Law dimming to <1%. Includes termination resistor. Refer to DMXR Manual.
EXA1 XPoint Wireless, eldoLED 0-10V ECOdrive. Linear dimming to 1%. Refer to XPoint tech sheet.
EXAB XPoint Wireless, eldoLED 0-10V SOLOdrive. Logarithmic dimming to <1%. Refer to XPoint tech sheet.
ECOS24,5 Lutron® Hi-Lume® 2-wire forward-phase driver. Minimum dimming level 1%. Minimum lumen 1000/Maximum lumen 3000.
ECOS34,5 Lutron® Hi-Lume® 3-wire or EcoSystem® dimming driver. Minimum dimming level 1%. Minimum lumen 1000/Maximum lumen 4500.
SF Single fuse. Specify 120V or 277V.
TRW6 White painted flange TRBL7 Black painted flange EL8 Emergency battery pack with integral test switch ELR8 Emergency battery pack with remote test switch NPS80EZ5 nLight® dimming pack controls
0-10V eldoLED drivers.
NPS80EZER5,9 nLight® dimming pack controls
0-10V eldoLED drivers. ER controls fixtures on emergency circuit.
BGTD Bodine generator transfer device.
Specify 120V or 277V.
CRI90 High CRI (90+) CP10 Chicago plenum. Specify 120V or 277V.
RRL__ RELOC®-ready luminaire connec-tors enable a simple and consis-tent factory installed option across all ABL luminaire brands. Refer to RRL for complete nomenclature.
A+ Capable options indicated by this color background.
http://www.gothamlighting.com http://www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx http://www.acuitybrands.com/-/media/products/Reloc/248102/document/RRL_pdf.pdf
GOTHAM ARCHITECTURAL DOWNLIGHTING | P 800.315.4982 | gothamlighting.com
© 2010-2016 Acuity Brands Lighting, Inc. All Rights Reserved. Rev. 10/12/16. Specifications subject to change without notice. PAGE 2 OF 4
EVO-6-OPEN
6” EVO
Downlight Solid-State Lighting
PH
OTOM
ETRY
All dimensions are inches (centimeters) unless otherwise noted.
ORDERING NOTES
1. Not available with finishes.
2. Not available with EL or ELR options.
3. Refer to TECH-240 for compatible dimmers.
4. Not available with nLight® and XPoint options.
5. Specify voltage. ECOS2 not available in 277V.
6. Not available with white reflector. Not applicable with FL option.
7. Not available with black reflector. Not applicable with FL option.
8. For dimensional changes, refer to TECH-140. Not available with 347V.
9. For use with generator supply EM power. Will require an emergency hot feed and normal hot feed.
10. ELR not available. CP & ECOS2 - 3000 lumen max. CP & ECOS3 - 4000 lumen max. CP, ECOS2/ECOS3 & EL - 2000 lumen max.
14 9 16 [37.0]
16 [55.4]
9 7 16 [24.0]
DIMENSIONS FOR CHICAGO PLENUM
ACCESSORIES order as separate catalog numbers (shipped separately)
SCA6 Sloped ceiling adapter. Degree of slope must be specified (5D, 10D, 15D, 20D, 25D, 30D). Ex: SCA6 10D. Refer to TECH-190.
CTA4-8 YK Ceiling thickness adapter (extends mounting frame to accommodate ceiling thickness up to 5”). Adds ~4” to fixture height.
GVRT Vandal-resistant trim accessory. Refer to TECH-200.
ISD BC 0-10V wallbox dimmer. Refer to ISD-BC.
DIM
EN
SION
AL DATA
ELECTRICAL
ACCESSORIES
N
OTES
WATTAGE CONSUMPTION MATRIX
LUMENS LM ACTUAL WATTAGE LUMENS per WATT
1000 1,059 11.8 90.1
1500 1,572 18.5 85.0
2000 2,058 23.2 88.9
2500 2,612 29.5 88.5
3000 3,077 36.6 84.1
3500 3,591 42.1 85.3
4000 4,046 48.1 84.2
4500 4,555 46.9 97.1
EMERGENCY LUMEN OUTPUT
LUMENS WATTAGE INITIAL OUTPUT
1000 9.6 1000
1500 9.6 1000
2000 9.6 1000
2500 9.6 1000
3000 9.6 1000
3500 9.6 1000
4000 9.6 1000
4500 9.6 1000
13 3 16 [33.5]
8 [40.3]
7 9 16 [19.2]
Aperture: 6-1/4” (15.9) Ceiling Opening: 7-1/8” (18.1) self-flanged 7-1/4” (18.4) flangeless Overlap trim: 7-1/2” (19.1) http://gothamlighting.com http://www.acuitybrandslighting.com/library/GAL/documents/OtherDocuments/TECH-240.pdf http://www.acuitybrandslighting.com/library/GAL/documents/OtherDocuments/TECH-140.pdf http://www.acuitybrandslighting.com/library/GAL/documents/OtherDocuments/TECH-190.pdf http://www.acuitybrandslighting.com/Library/GAL/documents/SpecSheets/TECH-200.pdf http://www.acuitybrandslighting.com/library/SYN/documents/SpecSheets/ISD_BC.pdf
© 2010-2016 Acuity Brands Lighting, Inc. All Rights Reserved. Rev. 10/12/16. Specifications subject to change without notice.PAGE 3 OF 4
EVO-6-OPEN
PH
OTOM
ETRY
6” EVO
Downlight
Solid-State Lighting
PHOTOMETRY NOTES
• Tested in accordance with IESNA LM-79-08.
• Tested to current IES and NEMA standards under stabilized laboratory conditions.
• CRI: 85 typical.
LUMEN OUTPUT MULTIPLIER - CRI
CRI FACTOR
80 CRI 1
90 CRI 0.79
LUMEN OUTPUT MULTIPLIER - CCT
CRI FACTOR
4000 K 1.035
3500 K 1
3000 K 0.973
2700 K 0.938
LUMEN OUTPUT MULTIPLIER - TRIM FINISH
FINISH
CLEAR
(AR)
PEWTER
(PR)
WHEAT
(WTR)
GOLD
(GR)
WHITE
(WR/WRAMF)
BLACK
(BR)
Specular (LS) 1.00 0.88 0.83 0.95 N/A N/A
Semi-specular (LSS) 0.95 0.84 0.79 0.90 N/A N/A
Matte-diffuse (LD) 0.85 0.73 0.69 0.80 N/A N/A
Paint N/A N/A N/A N/A 0.87 0.73
Distribution Curve Distribution Data Output Data Coefficient of Utilization Illuminance: Single Luminaire 30” Above Floor
EVO 35/20 6AR LS INPUT WATTS: 23.2, DELIVERED LUMENS: 2058, LM/W=88.7, 1.02 S/MH, TEST NO. LTL27777
0° 20°
40°
60°
80°
Ave Lumens
Zone Lumens % Lamp 0° - 30° 0° - 40° 0° - 60° 0° - 90°
90° - 180° 0° - 180°
1498.5 1958.0 2056.6 2058.3
0.0 2058.3
72.8 95.1 99.9 100.0 0.0
*100.0 *Efficiency
%02fp pc 80% 70% 50% pw 50% 30% 10% 50% 30% 10% 50% 30% 10%
R C
R
50% beam - 54.2°
10% beam - 77.3°
Mounting Height
Inital FC Center Beam Diameter FC Diameter FC
8.0 10.0 12.0 14.0 16.0
66.7 35.9 22.4 15.3 11.1
5.6 7.7 9.7 11.8 13.8
33.4 17.9 11.2 7.6 5.5
8.8 12.0 15.2 18.4 21.6
6.7 3.6 2.2 1.5 1.1
EVO 35/40 6AR LS INPUT WATTS: 48.1, DELIVERED LUMENS: 4046, LM/W=84.1 , 1.03 S/MH, TEST NO. LTL27768
EVO 35/35 6AR LS INPUT WATTS: 42.1, DELIVERED LUMENS: 3591, LM/W=85.3, 1.05 S/MH, TEST NO. LTL27767
0° 20°
40°
60°
80°
Ave Lumens
Zone Lumens % Lamp 0° - 30° 0° - 40° 0° - 60° 0° - 90°
90° - 180° 0° - 180°
2904.3 3830.0 4043.4 4046.3
0.0 4046.3
71.8 94.7 99.9 100.0 0.0
*100.0 *Efficiency
%02fp pc 80% 70% 50% pw 50% 30% 10% 50% 30% 10% 50% 30% 10%
R C
R
50% beam - 54.4°
10% beam - 78.1°
Mounting Height
Inital FC Center Beam Diameter FC Diameter FC
8.0 10.0 12.0 14.0 16.0
130.1 70.0 43.6 29.8 21.6
5.7 7.7 9.8 11.8 13.9
65.1 35.0 21.8 14.9 10.8
8.9 12.2 15.4 18.7 21.9
13.0 7.0 4.4 3.0 2.2
0° 20°
40°
60°
80°
Ave Lumens
Zone Lumens % Lamp 0° - 30° 0° - 40° 0° - 60° 0° - 90°
90° - 180° 0° - 180°
2579.3 3399.8 3586.3 3590.5
0.0 3590.5
71.8 94.7 99.9 100.0 0.0
*100.0 *Efficiency
%02fp pc 80% 70% 50% pw 50% 30% 10% 50% 30% 10% 50% 30% 10%
R C
R
50% beam - 55.2°
10% beam - 78.2°
Mounting Height
Inital FC Center Beam Diameter FC Diameter FC
8.0 10.0 12.0 14.0 16.0
112.4 60.4 37.7 25.7 18.7
5.7 7.8 9.9 12.0 14.1
56.2 30.2 18.8 12.9 9.3
8.9 12.2 15.4 18.7 21.9
11.2 6.0 3.8 2.6 1.9 http://www.gothamlighting.com
© 2010-2016 Acuity Brands Lighting, Inc. All Rights Reserved. Rev. 10/12/16. Specifications subject to change without notice. PAGE 4 OF 4
EVO-6-OPEN
CON
TROLS
6” EVO
Downlight Solid-State Lighting
A
A
B
B
A nPS 80 EZ nCM PDT 9 nCM ADCX nPS 80 EZ
EXAMPLE
Group Fixture Control* *Application diagram applies for �xtures with eldoLED drivers only.
nPS 80 EZ Dimming/Control Pack (qty 2 required) nPODM 2P DX Dual On/O�/Dim Push-Button WallPod nCM ADCX Daylight Sensor with Automatic Dimming Control nCM PDT 9 Dual Technology Occupancy Sensor
Description: This design provides a dual on/o�/dim wall station that enables manual control of the �xtures in Row A and Row B separately.
Additionally, a daylight harvesting sensor is provided so the lights in row B can be con�gured to dim automatically when daylight is available. An occupancy sensor turns o� all lights when the space is vacant.
nPODM 2P DX
B
C
C
A
OPTIONAL
WIRING KEY
BA C
CAT-5e Cable Line Power Low Voltage Dimming Wires nLight® Control Accessories:
Order as separate catalog number. Visit www.sensorswitch.com/nLight for complete listing of nLight controls.
WallPod stations Model number Occupancy sensors Model number On/Off nPODM [color] Small motion 360°, ceiling (PIR / dual tech) nCM 9 / nCM PDT 9 On/Off & Raise/Lower nPODM DX [color] Large motion 360°, ceiling (PIR / dual tech) nCM 10 / nCM PDT 10 Graphic Touchscreen nPOD GFX [color] Wide view (PIR / dual tech) nWV 16 / nWV PDT 16 Photocell controls Model number Wall Switch w/ Raise/Lower (PIR / dual tech) nWSX LV DX / nWSX PDT LV DX Dimming nCM ADCX Cat-5 cables (plenum rated) Model number
10', CAT5 10FT CAT5 10FT J1
15', CAT5 15FT CAT5 15FT J1
Choose Wall Controls.
nLIGHT o�ers multiple styles of wall controls – each with varying features and user experience.
Push-Button WallPod Traditional tactile buttons and LED user feedback
Graphic WallPod Full color touch screen provides a sophisticated look and feel
A
A
B
B
A nPS 80 EZ nCM ADCX nCM PDT 9 nPS 80 EZ nPODM 2P DX
B
C
C
A
OPTIONAL
WIRING KEY
BA C
CAT-5e Cable Line Power Low Voltage Dimming Wires
Capable Luminaire This item is an A+ capable luminaire, which has been designed and tested to provide consistent color appearance and out-of-the-box control compatibility with simple commissioning.
• All configurations of this luminaire meet the Acuity Brands’ specification for chromatic consistency
• This luminaire is part of an A+ Certified solution for nLight® control networks when ordered with drivers marked by a shaded background*
• This luminaire is part of an A+ Certified solution for nLight control networks, providing advanced control functionality at the luminaire level, when selection includes driver and control options marked by a shaded background*
To learn more about A+, visit www.acuitybrands.com/aplus.
*See ordering tree for details http://gothamlighting.com http://www.sensorswitch.com/nLight http://www.acuitybrands.com/aplus
WSTM LED
Series LEDs Color temperature Voltage Mounting Control options Other options Finish (required)
WSTM LED 1A One engine 2A Two engines
30K 3000K 40K 4000K
277 1
Shipped included (blank) Surface mount Shipped separately 2
UT5 Uptilt 5 degrees
Shipped installed PE Photoelectric cell, button type
Shipped installed (blank) Diffusing glass lens CGL Clear glass lens Shipped separately 2
WG Wire guard 3
DDBXD Dark bronze DBLXD Black DNAXD Natural aluminum DWHXD White DDBTXD Textured dark bronze DBLBXD Textured black DNATXD Textured natural aluminum DWHGXD Textured white DSSTXD Textured sandstone
WSTM LED
LED Mini Wall Sconce
Ordering Information EXAMPLE: WSTM LED 2A 40K 120 DDBTXD
Catalog Number
Notes
Type
Introduction
The Architectural WSTM Mini-Wall Sconce is now available with the latest in LED technology. The result is a long-life, maintenance-free product with typical energy savings of 87% over metal halide versions. The diffuse lens eliminates harsh glare while producing comfortable illumination.
The WSTM LED is ideal for replacing existing 50-100W metal halide or 26-42W compact fluorescent wall-mounted products and can be mounted in either lens up or lens down orientation. The expected service life is over 10 years of nighttime use.
One Lithonia Way • Conyers, Georgia 30012 • Phone: 800.279.8041 • Fax: 770.918.1209 • www.lithonia.com © 2011-2015 Acuity Brands Lighting, Inc. All rights reserved.
Hit the Tab key or mouse over the page to see all interactive elements.
Luminaire
Height: 5-3/4” (14.6 cm)
Width: 12-1/2” (31.8 cm)
Depth: 7-1/2” (19.1 cm)
Weight: 6 lbs.
(2.7 kg)
W
H
D
Specifications
NOTES
1. Includes step-down transformer; see page 2 for more information.
2. Also available as a separate accessory; see Accessories information at left.
3. Not for inverted mounting.
Accessories Ordered and shipped separately.
WSTMUT5 DDBXD U 5 degree uptilt accessory (specify finish)
WSTMWG U Wire guard accessory
Stock configurations are offered for shorter lead times:
Stock Part Number
WSTM LED 1A 40K 120 DDBTXD
WSTM LED 2A 40K 120 DDBTXD
http://www.lithonia.com/Micro_Webs/NightTimeFriendly/ http://www.lithonia.com/commercial/WSTM-LED.html http://www.lithonia.com/Micro_Webs/ArchitecturalColors/ http://www.lightingfacts.com/ http://www.designlights.org/ http://www.lithonia.com
Lumen values are from photometric tests performed in accordance with IESNA LM-79-08. Data is considered to be representative of the configurations shown, within the tolerances allowed by Lighting Facts.
LEDs Performance
Package System Watts1
30K
(3000K, 80 CRI)
40K
(4000K, 80 CRI)
Nominal Lumens
B U G LPW
Nominal Lumens
B U G LPW
1A 1A --K 9 673 0 0 0 75 733 0 0 1 81
2A 2A --K 17 1,308 1 0 0 77 1,277 1 0 0 75
Use these factors to determine relative lumen output for average ambient temperatures from 0-40°C (32-104°F).
Lumen Ambient Temperature (LAT) Multipliers
Ambient Lumen Multiplier 0°C 32°F 1.05
10°C 50°F 1.03
20°C 68°F 1.01
25°C 77°F 1.00 30°C 86°F 0.99
40°C 104°F 0.97
To see complete photometric reports or download .ies files for this product, visit Lithonia Lighting’s WSTM LED homepage. Photometric Diagrams
FEATURES & SPECIFICATIONS
INTENDED USE
The classic architectural shape of the WSTM LED was designed for applications such as hospitals, schools, malls, restaurants, and commercial buildings. The long-life LEDs make this luminaire nearly maintenance-free.
CONSTRUCTION
The single-piece die-cast aluminum housing integrates a heat sink to optimize thermal transfer from the internal light engine and promote long life. The die-cast door frame is fully gasketed with a one-piece solid silicone gasket to keep out moisture and dust, providing an IP65 rating for the luminaire.
FINISH
Exterior parts are protected by a zinc-infused Super Durable TGIC thermoset powder-coat finish that provides superior resistance to corrosion and weathering. A tightly controlled multi-stage process ensures a minimum 3 mils thickness for a finish that can withstand extreme climate changes without cracking or peeling. Standard Super Durable colors include dark bronze, black, natural aluminum, sandstone and white. Available in textured and non-textured finishes.
OPTICS
Light engines are 3000K (>80 CRI) or 4000K (>80 CRI). The WSTM LED has zero uplight and qualifies as a Nighttime Friendly™ product, meaning it is consistent with the LEED® and Green Globes™ criteria for eliminating wasteful uplight.
ELECTRICAL
Light engine(s) consist of 42 high-efficacy LEDs mounted to a circuit board and integral aluminum heat sink to maximize heat dissipation and promote long life (50,000 hrs at 25°C, L74).
INSTALLATION
Easily installed using provided mounting strap. Mount to any non-combustible vertical surface, over a 4” round or square recessed outlet box (by others). Back access through slotted gasket.
LISTINGS
CSA certified to U.S. standards. Luminaire is IP65 rated and suitable for wet locations when mounted with the lens down. Rated for -30°C minimum ambient.
DesignLights Consortium® (DLC) qualified product. Not all versions of this product may be DLC qualified. Please check the DLC Qualified Products List at www.designlights.org to confirm which versions are qualified.
WARRANTY
Five-year limited warranty. Complete warranty terms located at www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx.
Actual performance may differ as a result of end-user environment and application.
All values are design or typical values, measured under laboratory conditions at 25 °C.
Note: Specifications subject to change without notice.
Isofootcandle plots for the WSTM LED 40K. Distances are in units of mounting height (8’).
Te st
N o
. L
TL
t es te d in a cc o rd an ce w ith
IE
SN
A
L M
-7 9-
Te st
N o
LT
L5 te st ed in a cc o rd
IE
SN
A
L M
-7 9-
Te st
N o
. L
TL
t es te d in a cc o rd
IE
SN
A
L M
-7 9-
-4
-3
-2
-1
4 3 2 1 0 4321
Te st
N o
. L
TL
t es te d in a cc o rd
IE
SN
A
L M
-7 9-
1A 40K CLEAR1A 40K DIFFUSE
LEGEND
0.1 fc
0.5 fc
1.0 fc
2A 40K CLEAR2A 40K DIFFUSE
-4
-3
-2
-1
4 3 2 1 0 4321
-4
-3
-2
-1
4 3 2 1 0 4321
-4
-3
-2
-1
4 3 2 1 0 4321
1 See electrical load chart for 277V system watts.
Performance Data
One Lithonia Way • Conyers, Georgia 30012 • Phone: 800.279.8041 • Fax: 770.918.1209 • www.lithonia.com © 2011-2015 Acuity Brands Lighting, Inc. All rights reserved.
Lumen Output
WSTM-LED
Rev. 05/19/15
Current (A)
LEDs System Watts 120 277
1A 9W 0.08 –
13W1 – 0.06
2A 17W 0.15 –
22W1 – 0.09
Electrical Load
Projected LED Lumen Maintenance Data references the extrapolated performance projections for the WSTM LED platform in a 25°C ambient, based on 10,000 hours of LED testing (tested per IESNA LM-80-08 and projected per IESNA TM-21-11).
To calculate LLF, use the lumen maintenance factor that corresponds to the desired number of operating hours below. For other lumen maintenance values, contact factory.
Operating Hours Lumen Maintenance
Factor
0 25,000 50,000 100,000
1.0 0.86 0.74 0.54
1 Higher wattage is due to electrical losses from step-down transformer.
http://www.lithonia.com http://www.lithonia.com/commercial/WSTM-LED.html?pt=Outdoor
EMERGENCY LQM
Catalog Number
Notes
Type
ORDERING INFORMATION Example: LQM S W 3 R 120/277 EL N
LQM
Family Face type Housing color Number of faces Letter color Input voltage2 Operation Options
LQM S Stencil P Panel1
(blank) Black W White
3 Single face with extra faceplate and color panel
R Red G Green
120/277 Dual voltage
(blank) AC only X2 Primary and secondary AC inputs provided 3
EL N Nickel cadmium battery
(blank) None NOM NOM certified for Mexico4
SD Self-diagnostics5
SDFIFA Self-diagnostics, fire alarm flashing interface and flashing emergency operation and intermittent audible alarm (one flash/one second)5
7-5/8 (19.3)
11-3/4 (29.8)
(5.1)
All dimensions are inches (centimeters) unless otherwise specified.
Specifications
Length: 11-3/4 (29.8)
Depth: 2 (5.1)
Height: 7-5/8 (19.3)
Weight: 2.6 lbs (1.2 kgs)
Accessories: Order as separate item.
ELA WG1 Back-mount wireguard6 ELA WGEXE End-mount wireguard6
ELA WGEXT Top-mount wireguard6 ELA LQMUS12 12” stem kit7
FEATURES & SPECIFICATIONS
INTENDED USE — Ideal for applications requiring attractive, quick-installation exit signs and low energy consumption.
CONSTRUCTION — Engineering-grade thermoplastic housing is impact-resistant, scratch-resistant, and corro-sion-proof. UL94V-0 flame rating. UV-stable resin resists discoloration from natural and man-made light sources.
Rugged unibody housing snaps together with no additional mechanical fasteners. Faceplate and back cover are inter-changeable on housing. Positive snap-fit tabs hold faceplate securely, yet easily removable for lamp compartment access.
Universal directional Chevron inserts are easily removed and reinserted. Uniform illumination without shadows or hot spots. Reinforced, impact-resistant color panels. Letters 6” high with 3/4” stroke, with 100
ft. viewing distance rating, based upon UL924 standards.
U.S. Patent No. 5,526,251; 5,611,163; 5,739,639; 5,954,423; 5,988,825; 6,152,581; D383,501 ;
D495,751 and 6,502,044. Other patents pending.
OPTICS — LEDs mounted on printed circuit boards. Low energy consumption – less than one watt. LED lamp operates in normal (AC input) and emergency (DC input) modes.
The typical life of the exit LED lamp is 10 years.
ELECTRICAL — Low-voltage disconnect prevents excessively deep discharge that can permanently damage battery. Conveniently located test switch and LED provide visual and manual means of monitoring system.
Constant-current series charger minimizes energy consumption and provides low operating costs. Printed circuit boards are 100% quality tested during manufacturing. Current-limiting charger circuitry protects printed circuit boards from shorts.
AC/LV reset (line latch) allows battery connection before AC power is applied and aids in preventing battery damage from deep discharge.
Crystal oscillator timing system with watchdog protection for precision accuracy.
Brownout protection is automatically switched to emergency mode when supply voltage drops below 80% of nominal.
Battery: Sealed, maintenance-free nickel-cadmium battery delivers 90-minutes capacity to emergency lamps.
Two-state constant-current charge maximizes battery life and automatically recharges after battery discharge.
Diagnostics: Single-point microcomputer control for all electronic features.
Single multi-chromatic LED indicator to display two-state charging, test activation and three-state diag-nostic status.
Test switch provides manual activation of 30-second diagnostic testing for on-demand visual inspection.
Self-diagnostic testing for five minutes every 30 days and 30 minutes every six months and 90 mins an-nually with WRS.
Diagnostic evaluation of LED light source, AC to DC transfer, charging and battery condition. Continuously monitors AC functionality.
INSTALLATION — Universal (top-, end-, or back-) mounting. Easily removed mounting knockouts. J-box pattern on back panel. Housing snaps to canopy with four positive-locking tabs. Cam-locking pin tightly secures housing to canopy.
Ships standard with additional face plate.
LISTINGS — UL damp location listed 50°-104°F (10°-40°C) standard. NOM Certified (see options). Meets UL924, NFPA 101 (current Life Safety Code), NEC and OSHA illumination standards. NEMA Premium certified.
Meets all applicable FCC requirements.
Notes
1 Only available in custom signage. See spec sheet, Custom-Signage.
2 Some special voltages available. Consult factory.
3 Must specify input voltage 120 or 277. Not available with other options.
4 Available with stencil or panel faces in white housing.
5 Only available with EL N operation.
6 See spec sheet ELA-WG.
7 See spec sheet ELA-Stemkits.
Thermoplastic Exits
LQM
LED LAMPS
For shortest lead times, configure product using bolded options.
WARRANTY — 5-year limited warranty. (Battery is prorated.) Complete warranty terms located at www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx
Actual performance may differ as a result of end-user environment and application.
Note: Specifications subject to change without notice.
http://www.acuitybrandslighting.com/library/LL/documents/SpecSheets/CUSTOM-SIGNAGE.pdf http://www.acuitybrandslighting.com/library/LL/documents/SpecSheets/ela-wg.pdf http://www.acuitybrandslighting.com/library/ll/documents/specsheets/ela-stemkits.pdf
LQM
EMERGENCY: One Lithonia Way Conyers, GA 30012 Phone: 800.334.8694 Fax: 770.981.8141 www.lithonia.com ©1993-2015 Acuity Brands Lighting, Inc. All rights reserved. Rev. 06/30/15
LQM LED, Quantum®
MOUNTING
All dimensions are inches (centimeters) unless otherwise specified.
Shipping weight: 2.6 lbs. (1.2 kgs.)
SPECIFICATIONS
5-5/8 (14.7)
7-5/8 (19.3)
7-5/8 (19.3)
3-7/8 (9.6)
8-3/8 (21.3)
11-3/4 (29.8)
11-3/4 (29.8)
5-7/8 (14.9)
4-1/2 (11.4)
(5.1)
Top Mounting
End Mounting
Back Mounting
ELECTRICAL
Primary Circuit
Type1 Typical LED life2
Supply voltage
Input watts
Max.
amps
Red LED AC Only 10 years 120 .62 .05 277 .69 .06
Green LED AC Only 10 years 120 .62 .05 277 .74 .06
Red LED Emergency 10 years 120 .71 .05 277 .92 .06
Green LED Emergency 10 years 120 .66 .05 277 .70 .06
BATTERY
Nickel Cadmium
Voltage Shelf life3
Typical life3 Maintenance4
Optimum temperature5
1.2 3 years 7-9 years none 50°F - 104°F (10°C - 40°C)
Notes
1 LED lamps operate in normal (AC input) and emergency (DC input) modes.
2 Based on continuous operation. The typical life of the exit LED lamp is 10 years.
3 At 77°F (25°C).
4 All life safety equipment, including emergency lighting for path of egress must be maintained, serviced and tested in accordance with all National Fire Protection Association (NFPA) and local codes. Failure to perform the required maintenance, service, or testing could jeopardize the safety of occupants and will void all warranties.
5 Optimum ambient temperature range where unit will provide capacity for 90 minutes. Higher and lower tempera-tures affect life and capacity. Consult factory for detailed information.
PEAK COOLING LOADS
MAIN SYSTEM
By BCCLT
SPACE COIL
SpaceSpaceRoom Supply Space OA
CoilSupply
CoilCoil
Floor Peak LatentSensibleAir Peak Condition Sensible Latent
Area Time LoadLoadBulb Bulb Flow Time DB AirflowDry Bulb Load Load
System ft² Mo/Hr Btu/hBtu/h°F °F cfm Mo/Hr °F Btu/hBtu/hcfm°F
WB
°F
OA
°F °F
WBDB
Condition Dry Dry
Zone Room
Alternative 1 270 21 72 1,831 0 54.0 80 75.0 7 72 54.0 5427 / 80 80 80/21PeakHall - 100 2,396
748 10 68 23,820 0 54.0 1,035 75.0 7 73 54.0 1,3956 / 78 954 84/11PeakHall - 110 23,949
527 21 72 2,135 0 54.0 93 75.0 7 72 54.0 1,0597 / 80 93 80/21PeakHall - 250 3,052
911 20 73 4,161 0 54.0 181 75.0 7 73 54.0 1,8307 / 82 167 82/20PeakHall - 350 5,411
479 21 72 1,941 0 54.0 84 75.0 7 72 54.0 9627 / 80 84 80/21PeakHall - 400 2,617
62 16 77 401 0 54.0 17 75.0 7 77 54.0 1517 / 91 17 91/16PeakHall - 400 - ent 566
563 20 73 2,550 0 54.0 111 75.0 7 73 54.0 1,1317 / 82 103 82/20PeakHall - 410 3,316
1,320 21 72 5,348 0 54.0 232 75.0 7 72 54.0 2,6527 / 80 232 80/21PeakHall - East 7,379
25 10 71 4,623 0 54.0 201 75.0 7 73 54.0 477 / 80 193 84/11PeakHall - East - Ent 4,632
197 18 74 4,572 276 54.0 199 75.0 7 74 54.0 8757 / 88 199 88/18PeakRoom - 100 5,374
405 18 74 14,897 566 54.0 647 75.0 7 76 54.0 1,9477 / 88 636 90/17PeakRoom - 101 16,274
211 18 74 6,854 295 54.0 298 75.0 7 76 54.0 1,0147 / 88 292 90/17PeakRoom - 102 7,579
145 10 71 3,769 203 54.0 164 75.0 7 71 54.0 5917 / 80 164 80/10PeakRoom - 103 4,094
559 20 73 6,058 782 54.0 263 75.0 7 78 54.0 3,0977 / 82 253 91/14PeakRoom - 104 7,670
378 21 72 5,085 1,000 54.0 221 75.0 7 78 54.0 3,0797 / 80 213 92/15PeakRoom - 250 6,049
897 17 76 21,283 1,255 54.0 925 75.0 7 76 54.0 4,3137 / 90 925 90/17PeakRoom - 251 24,298
141 18 74 5,438 0 54.0 236 75.0 7 76 54.0 3047 / 88 233 90/17PeakRoom - 251A 5,775
332 14 68 9,502 464 54.0 413 75.0 7 78 54.0 1,8399 / 82 329 91/14PeakRoom - 254 8,586
202 16 77 3,167 283 54.0 138 75.0 7 78 54.0 1,1197 / 91 135 92/15PeakRoom - 255 3,930
255 15 78 3,093 357 54.0 134 75.0 7 78 54.0 1,4137 / 92 134 92/15PeakRoom - 256 3,877
212 10 68 5,688 297 54.0 247 75.0 7 73 54.0 9226 / 78 229 84/11PeakRoom - 257 5,702
337 10 68 8,722 471 54.0 379 75.0 7 73 54.0 1,4666 / 78 352 84/11PeakRoom - 258 8,776
353 14 78 4,651 494 54.0 202 75.0 7 78 54.0 1,9567 / 91 202 91/14PeakRoom - 259 5,680
388 21 72 2,912 543 54.0 127 75.0 7 72 54.0 1,7767 / 80 127 80/21PeakRoom - 260 3,499
728 16 73 9,686 1,018 54.0 421 75.0 7 78 54.0 4,0338 / 90 412 92/15PeakRoom - 261 11,712
157 14 50 5,951 220 54.0 259 75.0 9 68 54.0 47811 / 60 238 82/14PeakRoom - 261A 5,842
119 21 72 1,151 166 54.0 50 75.0 7 72 54.0 5457 / 80 50 80/21PeakRoom - 262 1,348
1,230 19 70 10,751 1,720 54.0 467 75.0 7 78 54.0 6,8156 / 82 456 92/15PeakRoom - 300 13,596
25 19 73 496 0 54.0 22 75.0 7 73 54.0 477 / 85 22 85/19PeakRoom - 300 Ent 687
191 17 76 6,164 267 54.0 268 75.0 7 76 54.0 9187 / 90 268 90/17PeakRoom - 300A 6,866
144 21 72 1,757 201 54.0 76 75.0 7 78 54.0 7987 / 80 73 92/15PeakRoom - 300B 2,031
165 21 72 1,879 231 54.0 82 75.0 7 78 54.0 9147 / 80 78 92/15PeakRoom - 300C 2,222
313 21 72 2,349 438 54.0 102 75.0 7 72 54.0 1,4337 / 80 102 80/21PeakRoom - 300D 2,806
273 15 78 3,682 382 54.0 160 75.0 7 78 54.0 1,5137 / 92 160 92/15PeakRoom - 300E 4,430
Project Name: TRACE® 700 v6.3.3 calculated at 01:05 PM on 11/09/201604892 SAFB Building 861
Dataset Name: 04892-BLDG861-LOADS-revised.trc Peak Clg Loads Main System Report Page 1 of 4
SPACE COIL
SpaceSpaceRoom Supply Space OA
CoilSupply
CoilCoil
Floor Peak LatentSensibleAir Peak Condition Sensible Latent
Area Time LoadLoadBulb Bulb Flow Time DB AirflowDry Bulb Load Load
System ft² Mo/Hr Btu/hBtu/h°F °F cfm Mo/Hr °F Btu/hBtu/hcfm°F
WB
°F
OA
°F °F
WBDB
Condition Dry Dry
Zone Room
140 15 78 2,192 196 54.0 95 75.0 7 78 54.0 7767 / 92 95 92/15PeakRoom - 300F 2,652
112 15 78 2,022 157 54.0 88 75.0 7 78 54.0 6217 / 92 88 92/15PeakRoom - 300G 2,403
128 10 68 4,355 179 54.0 189 75.0 7 73 54.0 5576 / 78 176 84/11PeakRoom - 300H 4,344
126 10 68 4,335 176 54.0 188 75.0 7 73 54.0 5486 / 78 175 84/11PeakRoom - 300I 4,319
467 14 78 13,421 3,736 54.0 583 75.0 7 78 54.0 9,0317 / 91 583 91/14PeakRoom - 300J 16,124
884 17 76 21,071 1,236 54.0 915 75.0 7 76 54.0 4,2507 / 90 915 90/17PeakRoom - 300L 23,306
320 15 78 6,197 1,250 54.0 269 75.0 7 78 54.0 9,2027 / 92 182 92/15PeakRoom - 301 7,489
195 15 78 2,938 500 54.0 128 75.0 7 78 54.0 5,3727 / 92 128 92/15PeakRoom - 302 5,280
41 21 72 166 0 54.0 7 75.0 7 72 54.0 827 / 80 7 80/21PeakRoom - 302 - JC 234
377 21 72 2,830 527 54.0 123 75.0 7 72 54.0 1,7267 / 80 123 80/21PeakRoom - 350 3,442
322 14 68 4,451 450 54.0 193 75.0 7 78 54.0 1,7849 / 82 175 91/14PeakRoom - 351 4,830
313 17 76 9,144 438 54.0 397 75.0 7 76 54.0 1,5057 / 90 397 90/17PeakRoom - 352 10,215
120 17 76 4,555 168 54.0 198 75.0 7 76 54.0 5777 / 90 198 90/17PeakRoom - 355A 4,992
137 17 76 4,685 192 54.0 204 75.0 7 76 54.0 6597 / 90 204 90/17PeakRoom - 355B 5,182
322 17 76 4,429 450 54.0 192 75.0 7 77 54.0 1,6967 / 90 190 91/16PeakRoom - 355C 5,627
282 14 68 9,402 394 54.0 408 75.0 7 78 54.0 1,5629 / 82 326 91/14PeakRoom - 355D 8,566
263 10 68 8,229 368 54.0 357 75.0 7 73 54.0 1,1446 / 78 331 84/11PeakRoom - 355E 8,188
307 10 68 11,739 2,379 54.0 510 75.0 7 73 54.0 5,3376 / 78 483 84/11PeakRoom - 356 12,262
119…