FA3099-18-R-0020, Questions and Answers
· Provide clarification on the SOW as there is a references to soffit and did not appear to be any during the site visit.
· SOW mentions soffits as an example only; this roof has no soffits.
· Provide clarification on the SOW as there is a reference to replacing wall panels
· No wall panels are to be replaced.
· In lieu of removal of the existing PBR metal roofing, can we suggest the option to install a retrofit roofing system using roof huggers and new the SSHM system?
· No.
· What exactly are the roofing specifications for this project? Preferred Manufacturer, panel profile and gauge of materials?
· Please see UFC 3-110-03 (Attachment 2), Chapter 5.
· Replacement insulation type and desired R-value?
· Vinyl “Bag and Sag” with minimum R-30 value
· What are the requirements and specifications for the lighting suppression system?
· Assumption: “lighting suppression” is supposed to be “lightning protection”
· Answer: Current lightning protection system can be re-installed.
· Are you wanting a weather tightness warranty? Period of coverage and type?
· Please see SOW section 7.