100_Per_Cent_B448_Drawings_REVISED.pdf

PDF 23 MB Posted

Attached to
B448 Replace Air Units and Upgrade EMCS Federal contract opportunity
Solicitation number
FA303018B0004
Issued by
Department of the Air Force Air Education and Training Command

About this file

Drawings

View the file

Other files for this federal contract opportunity

Other files attached to B448 Replace Air Units and Upgrade EMCS, newest first.
File Type Posted
FA303018B000400006.pdf PDF
Record_of_Attendance.pdf PDF
FA303018B0004_-_amendment_0004.pdf PDF
Questions_and_Answers.pdf PDF
2008_Asbestos_Report.pdf PDF
1992_Asbestos_Report.pdf PDF
FA303018B00040003.pdf PDF
FA303018B00040002.pdf PDF
FA303018B00040001.pdf PDF
WD_TX180336__05_Jan_18.pdf PDF
Insurance_Requirements.pdf PDF
FA303018B0004.pdf PDF
BAL_Request.pdf PDF
Speicifications_06Jun18.pdf PDF
AF_66.pdf PDF
Show all 15

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

ELECTRICAL

MD-101 MD-101

SCALE: 3/32" = 1'-0"

HVAC DEMO PLAN

MD101MD102

MD102 MD101

MD103 MD101

MD103 MD101

X

X

X

X

X

X

X

X

MD-102 MD-101

SCALE: 1/4" = 1'-0"

ENLARGED MECH ROOM

MECHANICAL DEMOLITION

MD-102 MD-101

SCALE: 1/4" = 1'-0"

AHU-1 ENLARGED PLANS

MECHANICAL DEMOLITION

WH

MD-103 MD-101

SCALE: 1/4" = 1'-0"

AHU-2 ENLARGED PLAN

MECHANICAL DEMOLITION

MD-103 MD-101

SCALE: 1/4" = 1'-0"

AHU-3 ENLARGED PLAN

MECHANICAL DEMOLITION

MD-201 MD-201

SCALE: 3/32" = 1'-0"

HVAC DEMO ROOF PLAN

M-103 M-103

SCALE: 3/16" = 1'-0"

HVAC FLOOR PLAN C

M105 M101

CHWP-1

ZONE 3

M-104 M-104

SCALE: 3/16" = 1'-0"

HVAC FLOOR PLAN D

M101M106

M-105 M-101

SCALE: 1/4" = 1'-0"

AHU-1 ENLARGED PLAN

MECHANICAL NEW WORK

M-105 M-103

SCALE: 1/4" = 1'-0"

AHU-2 ENLARGED PLAN

MECHANICAL NEW WORK

M-105 M-101

SCALE: 1/4" = 1'-0"

AHU-1 SECTION VIEW

MECHANICAL NEW WORK

M-105 M-103

SCALE: 1/4" = 1'-0"

AHU-2 SECTION VIEW

MECHANICAL NEW WORK

KEY NOTES:

M-106 M-104

SCALE: 1/4" = 1'-0"

AHU-3 ENLARGED PLAN

MECHANICAL NEW WORK

M-106 M-104

SCALE: 1/4" = 1'-0"

AHU-3 SECTION VIEW

MECHANICAL NEW WORK

M-201 M-201

SCALE: 3/32" = 1'-0"

HVAC ROOF PLAN

X

X

X

X

X

X

X

X

ELECTRICAL

M-301 M-301

SCALE: 3/32" = 1'-0"

HYDRONIC PIPING PLAN

M-302M-301

GENERAL NOTES:

C W R

C W R

C W R

C W R

C W S

C W R C W R C W R

C W R

C W S C W S C W S

C W R

C W S

C W S

C W S

C W S

X

X

X

X

X

X

X

X

X

X

M-302 M-301

SCALE: 1/4" = 1'-0"

PARTIAL HYDRONIC PIPING PLAN

M-401 M-401

SCALE: N.T.S.

HOT WATER ONE LINE DIAGRAM

M-402 M-402

CHILLED WATER ONE LINE DIAGRAM

M501 M101

SCALE: N.T.S

DUCT TAKEOFF DETAIL

M501 M101

SCALE: N.T.S

CONDENSATE DRAIN TRAP DETAIL

FINISHED FLOOR DETAIL

M501 M101

SCALE: N.T.S

CONNECTION DETAIL

TYPICAL FLEXIBLE DUCT

M501 M101

SCALE: N.T.S

VANE DETAIL

TYPICAL TURNING

M501 M101

SCALE: N.T.S

PIPE PENETRATION DETAIL

THRU WALL

M501 M101

SCALE: N.T.S

AIR INSTALLATION DETAIL

GRID CEILING SUPPLY

M501 M101

SCALE: N.T.S

FOR ROUND / OVAL DUCT

ACCESS SECTION

M501 M101

SCALE: N.T.S

ADJUSTABLE SINGLE BLADE BALANCING TYPE

MANUAL DAMPER

M501 M101

SCALE: N.T.S

RECTANGULAR DUCT

ACCESS SECTION FOR

M

NC

C

M

C

NC

M501 M101

SCALE: N.T.S

FAN COIL INSTALLATION DETAIL

M502 M101

SCALE: N.T.S

VAV BOX DETAIL

SERIES FAN POWERED

M502 M101

SCALE: N.T.S

VAV BOX MOUNTING DETAIL

M502 M101

SCALE: N.T.S

DUCT ACCESS DOOR DETAIL

M502 M101

SCALE: N.T.S

CEILING ACCESS PANEL DETAIL

M502 M301

SCALE: N.T.S

PIPING DETAIL

HYDRONIC COIL

M502 M101

SCALE: N.T.S

REFRIGERANT PIPING DETAIL

DX - SPLIT SYSTEM

UNION

M503 M101

SCALE: N.T.S

BOOT INSTALLATION DETAIL

GRID CEILING RETURN AIR

M503 M101

SCALE: N.T.S

INSTALLATION DETAIL

AHU-1 DUCT

M503 M201

SCALE: N.T.S

PIPE SUPPORT DETAIL

PIPING ROOF PENETRATION

M503 M201

SCALE: N.T.S

INSTALLATION DETAIL

PENTHOUSE LOUVER

M503 M201

SCALE: N.T.S

EXHUAST FAN DETAIL

ROOF MOUNTED CENTRIFUGAL

M504 M401

SCALE: N.T.S

THERMOMETER INSTALLATION

IN INSULATED PIPE

PRESSURE REGULATOR

PRESSURE GAUGE

( 25 PSIG)

( 30 PSIG)

RPBP

DRAIN VALVE

W/HOSE CONNECTION

TO FLOOR DRAIN

1" TO FLOOR DRAIN

FUNNEL DRAIN BELOW

ISOLATION CHAMBER

3/4" BY-PASS

HOSE CONNECTION

3/4"

TO CHILLED WATER

RELIEF SETTING 35 PSI

OR BOILER MAKE-UP

VENT ALL HIGH POINTS INDICATED ABOVE.

WHERE AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE

NOTES:

1/4" (8 MM)

COPPER TUBING

1/2" (15 MM)

GATE VALVE

1/2" (15 MM) x 4" (100 MM)

REDUCER

CIRCULATING

1.

2.

NIPPLE

ELEVATION

WATER PIPING

ABOVE 2" (50 MM) DIA. PIPE

2 1/2" (65 MM) DIA.

2" (50 MM) DIA. & SMALLER

HORIZONTAL

ABOVE 2" (50 MM) DIA. PIPE

2" (50 MM) DIA. & SMALLER

VERTICAL

2 1/2" (65 MM) DIA.

TO NEAREST MECHANICAL ROOM DRAIN.

SPECS FOR TYPE AND RANGE

2 BRASS THERMOMETER WELL, SEE DETAIL 7, THIS SHEET.

3 THREADOLET WELDED TO PIPE

4 DEPTH OF WELL ONE-THIRD

OF PIPE DIAMETER

5 PIPE DIAMETER

6 PIPE INSULATION

1 THERMOMETER - SEE

M504 M401

SCALE: N.T.S

INSTALLATION OF

THERMOMETER WELLS

M504 M105

SCALE: N.T.S

MAKE-UP WATER SPOOL DETAIL

M504 M105

SCALE: N.T.S

AIR VENT DETAIL

TYPICAL AUTOMATIC

INSERT TEE HERE FOR

SYSTEM WATER

CONNECTION IF PARALLEL

TANKS ARE USED

VERTICAL

DIAPHRAGM TYPE

EXPANSION TANK

PROVIDE TANK SADDLES &

HANGER ROD SUPPORTS

SEE NOTE 2

AIR VENT

NOTES:

1. DASHED PIPING SHOWS BOTH HORIZONTAL

AND VERTICAL DIAPHRAGM TYPE EXPANSION

TANKS. PROVIDE ONLY THE TYPE OF TANK

SELECTED AND THE ASSOCIATE PIPING.

2. CONNECT TO SIDE OF MAIN TO PREVENT AIR

OR DEBRIS FROM ENTERING PIPE TO TANK,

TOP OR BOTTOM CONNECTION NOT PERMITTED.

3. PROVIDE 12" [305mm] MINIMUM DROP

ANTI-THERMOSYPHON LOOP TO PREVENT

GRAVITY HEATING OF TANK.

4. SEE EXPANSION TANK SYSTEM SCHEDULE FOR

COMPONENT SIZES.

5. RELIEF VALVE FOR CONDENSER WATER SYSTEM

IS SHOWN. OMIT WHEN RELIEF VALVE IS

SHOWN ON HEAT EXCHANGER DETAIL &

SYSTEM IS USED ONLY FOR HOT WATER

HEATING. COMBINATION HEATING & COOLING

SYSTEMS WILL REQUIRE THE RELIEF VALVE.

6. PROVIDE STRAINER IN AIR SEPARATOR WHEN

INDICATED IN EXPANSION TANK SCHEDULE.

7. SET PRESSURE REDUCING VALVE SO

PRESSURE AT HIGHEST POINT IN SYSTEM HAS

A MINIMUM OF 4 PSIG. [28kPa]

HORIZONTAL

DIAPHRAGM TYPE

EXPANSION TANK

MANUAL AIR VENT

INSERT TEE HERE FOR

SYSTEM WATER

CONNECTION IF PARALLEL

TANKS ARE USED

INTEGRAL FULL

PORT FLOAT

ACUTATE

BRASS VENT

MECHNISM

RUN DRAIN LINE TO

NEAREST FD UNLESS

INDICATED OTHERWISE

COMBINATION AIR

DIRT SEPARATOR

M504 M105

SCALE: N.T.S

FOR CHILLED WATER AND HEATING HOT WATER SYSTEMS

AIR CONTROL AND PIPING CONNECTIONS

FLUSH VALVE

M I N

FLUE VENT(REFER

ARCH. DRWGS.)

AGA APPROVED

VENT CAP

FLUE SIZE IAW

MANUF. REQMTS.)

M504 M105

SCALE: N.T.S

CHEMICAL FEEDER DETAIL

M504 M401

SCALE: N.T.S

FLUE VENT DETAIL

TYPICAL STRUCTURAL STEEL

MEMBER FOR EQUIPMENT

NUMBER OF SPRING ISOLATION

UNITS AS REQUIRED

STRUCTURAL

STEEL FRAME

SPRING

ISOLATOR

ANCHOR

BOLT

REINFORCING

BARS

SLEEVE

#6 BAR ON

8" CENTERS NOM.

BOTH WAYS

ALL WELDED

STEEL FRAMEWORK

3000 PSI

CONCRETE INFILL

SECTION "A-A"

M504 M302

SCALE: N.T.S

ISOLATION DETAIL

PUMP VIBRATION

M504 M302

SCALE: N.T.S

ISOLATION DETAIL

VIBRATION

NEOPRENE

PAD

STEEL

SPRING

VIBRATION

ISOLATOR

CONCRETE

FLOOR

5/8"∅

ANCHOR

BOLT

EQUIPMENT

NEOPRENE

PAD

PRESSURE GAGE

(0 - 150 psig)

1/4" UNION

1/4" BRASS

NIPPLES

1/4" BALL

VALVE

BUSHING

FITTING

M504 M402

SCALE: N.T.S

INSTALLATION DETAIL

PRESSURE GAUGE

1. PROVIDE REHEAT, INFARED HUMIDIFICATION, LARGE DISPLAY, WATER LEAK DETECTION

CABLE, SMOKE DETECTOR, LOCKING DISCONNECT, CONDENSATE PUMP, AND MERV 8 FILTER.

NOTES:

2.01SYS SCOP

WEIGHT (LBS)

PFH014A-PLNMODEL

LIEBERTMANUFACTURER

B A

S I S

15MOCP

9.1MCA

208/1/60VOLTS/PHASE/HERTZ

E L E

C T

R I C

105AMBIENT AIR

CU-1MARK

G E

N

O U

T D

O O

R

U

N I T

NOTES

WEIGHT (LBS)

MMD12ENXHE02MODEL

LIEBERTMANUFACTURER

B A

S I S

30MOCP

21.3MCA

277/1/60VOLTS/PHASE/HERTZ

E L E

C T

R I C

0.88

HUMIDIFER (KW)

2.5

HUMIDIFIER (LB/HR)

4.8

TOTAL HEATING (KW)

M I S

C

LEAVING AIR TEMP. DB/WB (F)

ENTERING AIR TEMP. DB/WB (F)

12.1SENSIBLE COOLING (MBH)

13.7TOTAL COOLING (MBH)

C O

O L I N

G

C

O I L

0.2MOTOR HP

600SUPPLY AIR (CFM)

57B37ASERVES

MS-2MS-1MARK

G E

N E

R A

L

I N

D O

O R

U

N I T

1.68

LIEBERT

15.4

208/1/60

CU-2

MMD24ENXHED3

LIEBERT

29.7

277/1/60

1.5

4.3

6.3

19.5

21.8

0.5

PFH027A-PHN

8.

M701 M701

SCALE: N.T.S

VARIABLE AIR VOLUME AIR HANDLING UNIT CONTROL DIAGRAM

RELIEF AIR

D-3

D-2

P R E

F I L T E R

OUTSIDE

AIR

D-1

C O I L

P R E H E A T

C O I L

C O O L I N G

LOCATE SENSOR

OUTSIDE UNDER

SHIELD

MPS

V-2

V-1

CHR

CHS

SUPPLY FAN

A F M D

SUPPLY AIR TO

TERMINAL UNITS

TT

TT

TT TT

FT

A F T E R

F I L T E R

TT

HS

CS

VFD

SD

HOT WATER

COIL

PRESSURE SWITCH HIGH

TO DISABLE FAN WHEN HIGH

PRESSURE LIMIT SETPOINT IS

REACHED

PSH

SMOKE

DETECTOR

VARIABLE

FREQUENCY DRIVE,

TYP.

ZC

ZC

ZC

DPS DPS

TT

SST

SPD

TSL

SPS

SD

SD

SEQUENCE OF OPERATION:

S/A

HWS

HWR

F I L T E R

R/A OR

RECIRCULATED

SOUND

BAFFLE

FAN

FT

T

TT

M

SST

PC

ROOM

THERMOSTAT/SENSOR

WALL MOUNTED 48"

[1200 MM] AFF.

FAN POWERED/VARIABLE AIR VOLUME,

AIR TERMINAL UNIT

V-X

M701 M701

SCALE: N.T.S

CONTROL DIAGRAM

FPB/VAV AIR TERMINAL UNIT

SEQUENCE OF OPERATION(CONT.):

GAFB

B448

B448

PUMPS

CHWP-1,2

HWP-1,2

GAFB

B448

B448

FCU-1

M702 M702

SCALE: N.T.S

FOUR PIPE FAN COIL UNIT

D-1

ZC

NOT TO SCALE

Y Z

TITLE

X

X

X

X

X

X

X

X

ED-201 ED-201

SCALE: 3/32" = 1'-0"

ELECTRICAL POWER PLAN - DEMO

ED-202ED-201

HWP-1

ACC-1

X

X

X

X

X

X

X

X

X

X

HWP-2

CHP-1 CHP-2

ED-202 ED-201

SCALE: 1/4" = 1'-0"

PARTIAL ELECTRICAL POWER PLAN - DEMO

EF-1

EF-2

EF-4

EF-5

EF-7

EF-8

EF-9

EF-3

EF-6

EF-4

EF

MAU-1

CU CU CU

ED-203 ED-203

SCALE: 3/32" = 1'-0"

ROOF POWER PLAN - DEMO

ED-301 ED-301

SCALE: NTS

PARTIAL ELECTRICAL ONE LINE DIAGRAM - "SWBD-HMP" - DEMO

ED-302 ED-302

SCALE: NTS

PARTIAL ELECTRICAL ONE LINE DIAGRAM - "SWBD-HMP" - DEMO

ED-303 ED-303

SCALE: NTS

PARTIAL ELECTRICAL ONE LINE DIAGRAM - "SWBD-LMP" - DEMO

ED-304 ED-304

SCALE: NTS

PARTIAL ELECTRICAL ONE LINE DIAGRAM - "SWBD-LMP" - DEMO

X

X

X

X

X

X

X

X

E-201 E-202

SCALE: 3/32" = 1'-0"

ELECTRICAL POWER PLAN

E-202E-201

X

X

X

X

X

X

X

X

H W S

H W S

H W S

E-202 E-201

SCALE: 1/4" = 1'-0"

PARTIAL ELECTRICAL POWER PLAN

E-203 E-203

SCALE: 3/32" = 1'-0"

ROOF POWER PLAN

E-301 E-301

SCALE: NTS

PARTIAL ELECTRICAL ONE LINE DIAGRAM - "SWBD-HMP"

E-302 E-302

SCALE: NTS

PARTIAL ELECTRICAL ONE LINE DIAGRAM - "SWBD-HMP"

E-303 E-303

SCALE: NTS

PARTIAL ELECTRICAL ONE LINE DIAGRAM - "SWBD-LMP"

E-304 E-304

SCALE: NTS

PARTIAL ELECTRICAL ONE LINE DIAGRAM - "SWBD-LMP"

E-501 E-501

FIRE STOP DETAIL

EG-101 EG-101

SCALE: 3/32" = 1'-0"

LIGHTNING PROTECTION PLAN

NON SPRINKLERED SPACE

BUTTERFLY VALVE

OUTSIDE SCREW AND YOKE VALVE

OUTSIDE SCREW AND YOKE NORMALLY CLOSED VALVE

WET PIPE SPRINKLER RISER

BACKFLOW PREVENTER FLOW TEST CONNECTION

SIAMESE FIRE DEPARTMENT CONNECTION

OS& Y

NC OS& Y

APPLICABLE CODES AND STANDARDS:

THE DESIGN AND INSTALLATION SHALL BE IN ACCORDANCE WITH THE FOLLOWING CODES AND

STANDARDS, AND REFERENCED CODES AND STANDARDS THEREIN;

NFPA 1, FIRE CODE, 2015 EDITION

NFPA 3, RECOMMENDED PRACTICE FOR COMMISSIONING OF FIRE PROTECTION AND LIFE SAFETY

SYSTEMS, 2015 EDITION

NFPA 4, STANDARD FOR INTEGRATED FIRE PROTECTION AND LIFE SAFETY SYSTEM TESTING, 2015

EDITION

NFPA 10, STANDARD FOR PORTABLE FIRE EXTINGUISHERS, 2013 EDITION

NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2013 EDITION

NFPA 25, STANDARD FOR THE INSPECTION, TESTING AND MAINTENANCE OF WATER-BASED FIRE

PROTECTION SYSTEMS, 2014 EDITION

NFPA 70, NATIONAL ELECTRIC CODE, 2014 EDITION

NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE, 2013 EDITION

NFPA 90A, STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATION SYSTEMS, 2015 EDITION

NFPA 101, LIFE SAFETY CODE, 2015 EDITION

NFPA 170, STANDARD FOR FIRE SAFETY AND EMERGENCY SYMBOLS, 2015 EDITION

NFPA 291, RECOMMENDED PRACTICE FOR FIRE FLOW TESTING AND MARKING OF HYDRANTS, 2013

EDITION

ABA ACCESSIBILITY STANDARD FOR DEPARTMENT OF DEFENSE FACILITIES AS SIGNED AND

ADOPTED BY THE DEPUTY SECRETARY OF DEFENSE MEMORANDUM DATED 0CTOVER 31, 2008

UFC 3-600-01 FIRE PROTECTION ENGINEERING FOR FACILITIES, 26 SEPTEMBER 2006 CHANGE 3, 1

MARCH 2013

UFC 3-601-2 OPERATION AND MAINTENANCE: INSPECTIONS, TESTING, AND MAINTENANCE OF FIRE

PROTECTION SYSTEMS, 2010 EDITION

ADDRESSABLE MANUAL PULL STATION

ADDRESSABLE CONTROL MODULE

HEAT DETECTOR (FIXED TEMPERATURE)

PHOTOELECTRIC SMOKE DETECTOR

DUCT DETECTOR

SMOKE DETECTOR WITH SOUNDER BASE

COMBINATION SMOKE AND CARBON MONOXIDE DETECTOR

SMOKE DETECTOR ASSOCIATED WITH CLEAN AGENT SYSTEM

FLOW SWITCH

PRESSURE SWITCH ( AP- ALARM PRESSURE; PS-PRESSUE SUPERVISORY)

TAMPER SWITCH

KITCHEN HOOD SUPPRESSION SYSTEM

KNOX BOX

STROBE LIGHT-WALL MOUNTED (CD-CANDELA RATING; C-CLEAR, A-AMBER)

STROBE LIGHT-CEILING MOUNTED (CD-CANDELA RATING; C-CLEAR, A-AMBER)

HORN (FL-FLASHING LIGHT)

SPEAKER NOTIFICATION APPLIANCE

FIRE ALARM BELL

COMBINATION SPEAKER/STROBE LIGHT APPLIANCE. (CD-CANDELA RATING; C-CLEAR, A-AMBER)

EMERGENCY TEXT MESSAGE

FIRE ALARM CONTROL PANEL

AUTONOMOUS CONTROL UNIT

LOCAL OPERATING CONSOLE

DIGITAL RADIO COMMUNICATOR / TRANSMITTER

ALPHA-NUMERIC ANNUNCIATOR

NOTIFICATION CIRCUIT POWER BOOSTER PANEL

ULTRASENSITIVE SMOKE DETECTION CONTROLLER

POWER BOOSTER SUPPLY

FIRE ALARM LEGEND

ADDRESSABLE MONITOR MODULE

FIRE SPRINKLER

1. REPLACE ALL FIRE SPRINKLERS WITH ALL NEW QUICK RESPONSE SPRINKLERS.

2. THE FOLLOWING STAKEHOLDERS SHALL BE INVITED TO ALL FIRE SUPPRESSION ACCEPTANCE

TESTING: 17 CES FIRE ALARM TECHNICIANS, 17 CES PLUMBERS, 17 CES FIRE PREVENTION OFFICE.

GENERAL NOTES:

FIRE ALARM

1. SCOPE OF WORK IS TO:

1.1. DEMOLISH EXISTING FIRE ALARM SYSTEM AND PROVIDE A NEW FIRE ALARM SYSTEM:

A. DEMOLISH EXISTING HORN/LIGHTS, PULL STATIONS, AND DUCT DETECTORS

B. PROVIDE NEW FIRE ALARM CONTROL PANEL IN CONDITIONED SPACE

F. PROVIDE MANUAL PULL STATIONS NO MORE THAN 48" AFF

G. PROVIDE NEW DUCT TYPE SMOKE DETECTORS WITH REMOTE, KEYED, TEST STATIONS TO INITIATE A

SUPERVISORY ALARM

2. THE FIRE ALARM SYSTEM SHALL BE INSTALLED AND TESTED PER ALL CODES AND STANDARDS REFERENCED

HEREIN. ADDITIONAL LOCAL STANDARDS, ORDINANCES AND POLICIES WILL BE FOLLOWED.

3. REQUIRED EQUIPMENT INCLUDE MONACO MAAP PANEL, NARROWBAND COMPATIBLE WITH A MONACO D-700, OR

MONACO D-21 SYSTEM. ALL DEVICES SHOULD BE ADDRESSABLE TO TRANSMIT EXACT LOCATION AND DEVICE TO

THE MAIN CONTROL PANEL AT GOODFELLOW FIRE DEPARTMENT.

4. FIRE ALARM SYSTEM WIRING: ALL WIRING TO BE FPLR RATED. WIRING SHALL BE PROTECTED FROM PHYSICAL

DAMAGE AS REQUIRED BY UFC 3-600-01 AND NFPA 70. WIRE AND CABLE SHALL BE: POWER LIMITED CLASS "B"

STYLE C FOR THE INITIATING DEVICE AND SIGNALING LINE CIRCUITS AND POWER LIMITED CLASS "A" STYLE Z FOR

THE NOTIFICATION APPLIANCE CIRCUITS. WIRE TYPE SHALL BE LISTED FOR ITS INTENDED USE BY AN APPROVAL

AGENCY ACCEPTABLE TO THE LOCAL AUTHORITY AND SHALL BE INSTALLED IN ACCORDANCE WITH UFC 3-600-01, AND NFPA 70: NATIONAL ELECTRIC CODE. WIRING TO BE SIZED, COLOR CODED AND IN QUANTITIES AS

RECOMMENDED:

A. BY THE EQUIPMENT MANUFACTURER AND IN ACCORDANCE TO NEC 760.

B. SIGNALING LINE CIRCUIT DEVICE WIRING SHALL BE AWG#16 MINIMUM.

C. ALL WIRING TO BE SOLID COPPER, EXCEPT FOR CIRCUITS REQUIRING SHIELDING.

D. ALARM NOTIFICATION DEVICE WIRING SHALL BE AWG#16 MINIMUM.

E. ALL WIRING TO BE SUPERVISED PER ALL APPLICABLE CODES AND STANDARDS.

F. ALL CONDUIT TO BE METALLIC, 152 MM (3/4") MINIMUM.

G. ALL TERMINATIONS MUST BE AT A TERMINAL STRIP USING SCREW TERMINALS. ALL DEVICES TO HAVE SCREW

TERMINALS.

H. PULL ALL CONDUCTORS SPLICE FREE. MAKE ALL TURNS AT 90 DEGREE ANGLES AND TIGHTLY BUNDLE AND

WRAP ALL WIRE.

I. ALL WIRING TO CONTROL PANELS SHALL BE RUN IN THE VERTICAL OR HORIZONTAL PLANE.

5. ALL STROBE LIGHTS SHALL BE SYNCHRONIZED.

6. ALL DEVICES AND APPLIANCES SHALL BE COMPATIBLE WITH THE CONTROL PANEL. ALL DEVICES AND APPLIANCES

WILL BE MOUNTED AND SPACED PER ALL APPLICABLE CODES AND STANDARDS AS WELL AS MANUFACTURER'S

SPECIFICATIONS.

7. THE ACCEPTANCE TESTING OF THE FIRE ALARM SYSTEM AND COMPONENTS SHALL CONSIST OF ALL APPLICABLE

ITEMS IN NFPA 72, UFC 4-021-01, AND UFC 3-601-02. SEE NFPA 72, CHAPTER 14 FOR DETAILS ON THE APPLICABLE

TESTS. UPON ACCEPTANCE, A COMPLETE SET OF RECORD DRAWINGS SHALL BE SUBMITTED.

8. CONTRACTOR SHALL TAKE EFFECTIVE MEASURES TO REDUCE FALSE ALARMS INCLUDING COORDINATING WITH 17

CE ALARM SHOP AND 17 CEFP OFFICES, MINIMIZE DUST, AS WELL AS COVERING AND PROTECTING FIRE

DETECTION SYSTEMS SUCH AS SMOKE AND HEAT DETECTORS.

9. THE FOLLOWING STAKEHOLDERS SHALL BE INVITED TO ALL FIRE ALARM ACCEPTANCE TESTING: 17 CES FIRE

ALARM TECHNICIANS AND 17 CES FIRE PREVENTION OFFICE.

10. PROVIDE A CAD DRAWN FLOOR PLAN SHOWING LOCATION OF THE DEVICES IN THE ROOMS, AND THEIR

CORRESPONDING ADDRESS. LOCATE A SINGLE FRAMED DRAWING OF THE LOCATIONS OF THE SMOKE

DETECTORS OUTSIDE OF THE SPACE AND ADJACENT TO THE MAIN ENTRANCE PER UFC 3-600-1.

CARBON MONOXIDE DETECTOR

FIRE ALARM GRAPHIC PLAN

FL

D

D D

F L

F L

F L

F L

F L

F L

F L

S

S

S

S

S

S

ELECTRICAL

GENERAL NOTES:

1. REMOVE ALL EXISTING FIRE ALARM DEVICES.

2. CONTRACTOR MAY REUSE EXISTING

CONDUIT AND JUNCTION BOXES

3. ALL NEW DEVICES SHALL BE MOUNTED AT

HEIGHTS REQUIRED BY NFPA 72 AND ABA. IF

NECESSARY THE CONTRACTOR SHALL

RELOCATE JUNCTION BOXES OR BACK

BOXES NOT CURRENTLY AT CORRECT

HEIGHT.

4. ANY JUNCTION BOXES OR BACK BOXES NOT

REUSED SHALL BE PROVIDED WITH A COVER

PLATE. BOXES IN FINISHED AREAS SHALL BE

BRUSHED ALUMINUM. ALL OTHER COVER

PLATES MAY BE EMT OR SIMILAR GAUGE.

FP-002 FP-002

SCALE

F L

FL

D

D

D

D

D

D

D

D

F L

F L

F L

F L

F L

FL

X

X

X

X

X

X

X

X

X

X

ELECTRICAL

GENERAL NOTES:

1. REMOVE ALL EXISTING FIRE ALARM DEVICES.

2. CONTRACTOR MAY REUSE EXISTING

CONDUIT AND JUNCTION BOXES

3. ALL NEW DEVICES SHALL BE MOUNTED AT

HEIGHTS REQUIRED BY NFPA 72 AND ABA. IF

NECESSARY THE CONTRACTOR SHALL

RELOCATE JUNCTION BOXES OR BACK

BOXES NOT CURRENTLY AT CORRECT

HEIGHT.

4. ANY JUNCTION BOXES OR BACK BOXES NOT

REUSED SHALL BE PROVIDED WITH A COVER

PLATE. BOXES IN FINISHED AREAS SHALL BE

BRUSHED ALUMINUM. ALL OTHER COVER

PLATES MAY BE EMT OR SIMILAR GAUGE.

FP-003 FP-003

SCALE

60 CD; C

60 CD; C

60 CD; C60 CD; C

60 CD; C

15 CD; C

60 CD; C

60 CD; C

60 CD; C

C

D

C

C

D

C

C

D

C

C

D

C

60 CD; C

30 CD; C

60 CD; C

15 CD; C

15 CD; C

60 CD; C

C

D

C

C

D

C

15 CD; C

15 CD; C

30 CD; C

60 CD; C

C

D

C

15 CD; C

60 CD; C

60 CD; C

60 CD; C

60 CD; C

60 CD; C

60 CD; C

60 CD; C

60 CD; C

15 CD; C 15 CD; C 15 CD; C 15 CD; C

15 CD; C

15 CD; C15 CD; C

15 CD; C

15 CD; C15 CD; C

15 CD; C

D

D

60 CD; C

60 CD; C

C

D

C

C

D

C

75 CD; C

75 CD; C

C

D

C

C

D

C

X

X

X

X

X

X

X

X

X

X

ELECTRICAL

FP-005 FP-005

SCALE

GENERAL NOTES:

1. MOUNT ALL NEW MANUAL FIRE ALARM

STATIONS SO THAT OPERATING MECHANISM IS

NO MORE THAN 48" AFF.

2. SMOKE DUCT DETECTORS MOUNTED ABOVE 6

FEET AND THOSE MOUNTED BELOW 6 FEET

THAT CANNOT BE EASILY ACCESSED WHILE

STANDING ON THE FLOOR, SHALL BE PROVIDED

WITH A REMOTE DETECTOR INDICATOR PANEL

CONTAINING TEST AND RESET SWITCHES.

3. ALL JUNCTION BOX COVERS AND NEW

RACEWAYS ASSOCIATED WITH THE FIRE ALARM

SYSTEM SHALL BE PAINTED RED. REFER TO

SPECIFICATION 26 20 00 ADDITIONAL

REQUIREMENTS.

1. REPLACE THE EXISTING STANDARD RESPONSE SPRINKLERS

WITH NEW QUICK RESPONSE SPRINKLERS THROUGHOUT

THE ENTIRE ADMINISTRATIVE SPACE, INCLUDING HALLWAYS

AND OFFICES. ENSURE THAT K-FACTOR, TEMPERATURE

RATING, LOCATION, ORIENTATION, AND WATER DISTRIBUTION

CHARACTERISTICS REMAIN THE SAME. INSTALL SPRINKLER

SYSTEM COMPONENTS PER UFC 3-600-01, NFPA 13, AND

MANUFACTURER'S INSTRUCTIONS. THE EXISTING SPRINKLER

SYSTEM (INCLUDING CONTROL VALVES, SYSTEM PIPING,

FITTINGS, HANGARS, PRESSURE GAUGES, ETC.) SHALL

REMAIN.

2. HYDROSTATICALLY TEST THE REPAIRED FIRE SPRINKLER

SYSTEM IN ACCORDANCE WITH NFPA 13 SECTION 25.2. THE

USE OF RECONDITIONED SPRINKLERS IS NOT PERMITTED

PER NFPA 13. THEREFORE, IF SPRINKLERS ARE LEAKING OR

DAMAGED DURING TESTING THEN THEY SHALL BE REPLACED

WITH NEW SPRINKLERS.

FP-006 FP-006

SCALE: 3/32"=1'-0"

X

X

X

X

X

X

X

X

ELECTRICAL

FP-007 FP-007

SCALE: 3/32"=1'-0"

1. REPLACE THE EXISTING STANDARD RESPONSE SPRINKLERS

WITH NEW QUICK RESPONSE SPRINKLERS THROUGHOUT

THE ENTIRE ADMINISTRATIVE SPACE, INCLUDING HALLWAYS

AND OFFICES. ENSURE THAT K-FACTOR, TEMPERATURE

RATING, LOCATION, ORIENTATION, AND WATER DISTRIBUTION

CHARACTERISTICS REMAIN THE SAME. INSTALL SPRINKLER

SYSTEM COMPONENTS PER UFC 3-600-01, NFPA 13, AND

MANUFACTURER'S INSTRUCTIONS. THE EXISTING SPRINKLER

SYSTEM (INCLUDING CONTROL VALVES, SYSTEM PIPING,

FITTINGS, HANGARS, PRESSURE GAUGES, ETC.) SHALL

REMAIN.

2. HYDROSTATICALLY TEST THE REPAIRED FIRE SPRINKLER

SYSTEM IN ACCORDANCE WITH NFPA 13 SECTION 25.2. THE

USE OF RECONDITIONED SPRINKLERS IS NOT PERMITTED

PER NFPA 13. THEREFORE, IF SPRINKLERS ARE LEAKING OR

DAMAGED DURING TESTING THEN THEY SHALL BE REPLACED

WITH NEW SPRINKLERS.

8766-1008-CS-001-R000
8766-1008-CS-002-R000
8766-1008-CS-003-R000
GOODFELLOW B448 - ARCH 100%
8766-1008-M-000-M-000
8766-1008-MD-101-24X36
8766-1008-MD-102&MD103 ENLARGED PLANS - -MD102
8766-1008-MD-102&MD103 ENLARGED PLANS - -MD103
8766-1008-MD-201-24X36
8766-1008-M-101-A
8766-1008-M-101-B
8766-1008-M-101-C
8766-1008-M-101-D
8766-1008-M105&M106 - ENLARGED PLANS-M105
8766-1008-M105&M106 - ENLARGED PLANS-M106
8766-1008-M-201-24X36
8766-1008-M-301
8766-1008-M-302-M-302
8766-1008-M-401-M-401
8766-1008-M-402-M-402
8766-1008-M-501-24X36
8766-1008-M-502-24X36
8766-1008-M-503-24X36
8766-1008-M-504-24X36
8766-1008-M-505-24X36
8766-1008-M-601-24X36
8766-1008-M-602-24X36
8766-1008-M-701-M-701
8766-1008-M-701-M-702
E-000-E-000
ED-101-ED-101
ED-201-ED-201
ED-202-ED-202
ED-203-ED-203
ED-301-ED-301
ED-302-ED-302
ED-303-ED-303
ED-304-ED-304
E-101-E-101
E-201-E-201
E-202-E-202
E-203-E-203
E-301-E-301
E-302-E-302
E-303-E-303
E-304-E-304
E-501-E-501
E-601-E-601
E-602-E-602
E-603-E-603
EG-101-EG-101
FP-001
FP-002
FP-003
FP-004
FP-005
FP-006
FP-007