Warehouse Fan Bldg. 10904 -Answers 8 Jan 25.pdf

PDF 199 KB Posted

Attached to
Warehouse Fan Bldg. 10904
Solicitation number
FA301625Q0017
Issued by

About this file

This is a Questions & Answers document for solicitation FA30162Q0017 regarding the installation of an industrial ceiling fan at Building 10904 at JBSA Lackland, TX for the Department of the Air Force Air Education and Training Command. The document contains contractor questions and government responses regarding electrical conduit specifications and installation requirements.

The key clarifications provided indicate that Electric Metallic Tube Conduit or Metal Clad Conduit must be used for all exposed wiring, with Metal Clad conduit specifically confirmed as suitable. The government notes that the quantity of conduit needed cannot be predetermined as it depends on how contractors access the electrical panel, which would typically be determined during the site visit. Several questions regarding distances, panel locations, and installation specifics were unable to be answered due to scheduling conflicts and warehouse utilization issues at the time of response. The cutoff date for contractor questions was set for 12:00 pm CST, January 6, 2025.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

502 CONS/JBKAE FA30162Q0017

JBSA Lackland, TX Warehouse Fan Bldg. 10904

QUESTIONS & ANSWERS: Cutoff date for contractor questions is 12:00 pm CST, 6 Jan 2025.

Question 1: The contractor shall provide and install all metal conduit”. What type of conduit and how much?

Government Response: Electric Metallic Tube Conduit or Metal Clad Conduit is what all exposed wiring needs to be enclosed in. As far as how much, the Government cannot determine how much a Contractor will need. This is dependent on how the Contractor gains access to the electrical panel.

Typically, this information is gained by the Contractor during the Site Visit.

Question 2: The approximate distance from the panel to the future location of the Fan; Photographs showing:

Government Response: This information is gained by the Contractor during the Site Visit. Due to Program Manager’s current schedule, the deadline to provide answers, and warehouse utilization conflicts, this information cannot be provided.

Question 3: Wiring shall be in electrical conduit (no exposed wires?) What type of conduit and how much?

Government Response: Electric Metallic Tube Conduit or Metal Clad Conduit is what all exposed wiring needs to be enclosed in. As far as how much, the Government cannot determine how much a Contractor will need. This is dependent on how the Contractor gains access to the electrical panel. Typically, this information is gained by the Contractor during the Site Visit.

Question 4: The contractor shall provide and install all metal conduit; We use Metal Clad as out standard wiring.

Government Response: Metal Clad conduit is suitable.

Question 5:

Government Response:

Question 6:

Government Response:

Question 7:

o The panel.

o The location of the desired installation.

o A wide-angle view that includes both the panel location and the future

Industrial Fan location, if possible.

Government Response:

Question 8:

Question 9:

Government Response:

Question 10:

Government Response:

Question 11:

Government Response:

Question 12: