The contract requires the installation of a metal canopy to connect to an existing canopy. The government provided details on the current canopy materials, stated the project must be completed within 30 business days, and confirmed that engineer-sealed drawings are not required. The government also clarified that the new canopy must tie into the existing concrete slab and will need to be grounded. Contractors are asked to match the color of the existing sheet metal as closely as possible, and the government will clear the proposed construction area of materials. This is a 100% Small Business Set-Aside contract with a NAICS code of 236220 - Commercial and Institutional Building Construction.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

21 August 2024

Lackland Building 210 Metal Canopy

1. Is there a manufacturer for the existing sheet metal? Different companies have different brown colors.

Government Answer: The existing material was erected in house by the Government. The organization for purchase is no longer available. Please do the best to match the existing sheet metal color.

2. What is the date the canopy is to be completed?

Government Answer: 30 Business days.

3. Are engineer sealed drawings of the new canopy required?

Government Answer: NO.

4. What materials are used on the current canopy?

Government Answer: 2x2x10 steal square tubing, 2x6x10 steal joist, and 22-gauge metal roofing.

5. Are you requiring 100% stamped drawings? If so, all or partial?

Government Answer: NO.

6. Will the new metal canopy have to be grounded?

Government Answer: YES.

Added Questions:

7. The picture on page 5 shows a partial concrete slab, is the intent to leave floor as is, tie into existing slab, or replace with new?

Government Answer: The canopy must tie into the existing slab.

21 August 2024

8. Will there be a civil plan drawn up showing boundary lines? I was curious if we need to stay away from the chain link fence or build right up to it?

Government Answer: The new dimensions are in the amendment that allow the contractor to avoid the fence altogether.

9. Is there a proposed laydown area for materials, storage container, or location for the propane tanks to be moved to during the proposed construction?

Government Answer: Government POC is going to move all materials shown in the photos so the contractor can set up their construction area next to the canopy.