01 June 2023 Attachment 19
FA301023R0008
FA301023R0008 Repair Student Dorm Smith
Additional Pre-bid Questions and Answers
1) The answer to the fire alarm question was not answered: Which spec are we to follow
(Navy or Air Force)? These are two different systems with regards to rough in and device counts.
Q1 Answer: Refer to Attachment 19 – MNS_ECB for mass notification system standards.
2) After looking at the photos I noticed there are no disconnect switches on the VAV: Are we required to add switches for a disconnect means?
Q2 Answer: Yes, install disconnect switches on the VAVs.