Water Flow Test Record Input information in non‐shaded areas only.
Hydrant # Location Date 2‐May‐19 6‐May‐20 7‐May‐21 10‐May‐22 3‐May‐18
Purpose of Test 65 65 68 65 70 Manufacturer 55 56 62 55 62
Date 2005 Size 5 1/4" 2.5 2.5 2.5 2.5 2.5
0.9 0.9 0.9 0.9 0.9
Comments 50 51 58 55 50 Min of Test 5 15 5 5 5
Outlet Size 2.5 1186 1198 1278 1244 1186 Cooefficient 0.9 2673 2858 3928 2803 3192
2979 3185 4351 3124 3522 Flow Hydrant #1 5932 17974 6389 6222 5932 Flow Hydrant #2 J.BROWN J. BROWN D.NECAISE D.NECAISE K STURGILL Flow Hydrant #3
GPM PSI GPM PSI GPM PSI GPM PSI GPM PSI
0 65 0 65 0 68 0 65 0 70
1186 55 1198 56 1278 62 1244 55 1186 62 2673 20 2858 20 3928 20 2803 20 3192 20 2979 10 3185 10 4351 10 3124 10 3522 10 3260 0 3485 0 4741 0 3419 0 3828 0
Column heading color correlates to line color on the chart
Outlet Size (inches) Coefficient
17 TURNS Pitot Pressure
Test Flow (gpm) Flow (gpm) available @ 20 psi Flow (gpm) available @ 10 psi (gpm) Consumed During Test
Tested By:
MUELLER Residual Pressure (psig)
Test Data Information 5‐47
PHANTOM ST S.E. OF 4278
FLUSH & FLOW Static Pressure (psig)
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000
Pr es su re (p si g)
Water Flow (gpm)
Water Flow Test Chart
AF Form 1027, Water Flow Test Record, Computer‐Generated (Nov 2010) Produced By:
Robert Manter
Utilities Supervisor
508 L St Keesler AFB, MS 39540 Work: (228) 377‐4390