Attachment_10-Updated_BLDG._886_Drawings_8_July_2019.pdf

PDF 11 MB Posted

Attached to
Renovate Bldg 886 Federal contract opportunity
Solicitation number
FA282319RA012
Issued by
Department of the Air Force Materiel Command Test Center

About this file

Attachment 10-Updated Bldg. 886 Drawings 8 July 2019

View the file

Other files for this federal contract opportunity

Other files attached to Renovate Bldg 886, newest first.
File Type Posted
Amendment_FA282319RA0120007_SF_30.pdf PDF
FTFA_17-1100_Post_Site_Visit_RFIs_Bldg_886_QA.pdf PDF
FTFA_17-1100_Pre-Award_Construction_Site_Visit_Sign-In_18_July_2019.pdf PDF
Conformed_Solicit_-_FA282319RA0120007.pdf PDF
Attachment_12-Revised_SPEC_13_34_19_Eng_Canopy_Sys_8_July_2019.pdf PDF
Conf_Solicit_-_FA282319RA0120006.pdf PDF
Amendment_FA282319RA0120006_SF_30.pdf PDF
Attachment_11-Revised_Section_28_31_64.00_10_Fire_Detection_and_Alarm_8_July_2019.pdf PDF
Bldg_886_Questions_and_Answers_part_2.docx DOCX document
Contractor_Questions_and_Answers_Bldg_886_19RA012.docx DOCX document
QandA_Bldg_886.docx DOCX document
Conf_Solicit-_FA282319RA0120005.pdf PDF
Amendment_FA282319RA0120005_SF_30.pdf PDF
50_Div_Cost.xls XLS spreadsheet
Amendment-_FA282319RA0120004_SF_30.pdf PDF
Conformed_Solicit-_FA282319RA0120004.pdf PDF
Conformed_Solit_-_FA282319RA0120003.pdf PDF
Amendment-FA282319RA0120003_SF_30.pdf PDF
Attachment_8-Financial_Responsibility_Questionnaire.pdf PDF
Solicitation_-_FA282319RA012.pdf PDF
Attachment_3-Specification.pdf PDF
Attachment_4-Wage_Determination.pdf PDF
Attachment_2-Bldg_886_Drawings.pdf PDF
Amendment-FA282319RA0120001_SF_30.pdf PDF
Attachment_1-Statement_of_Work.pdf PDF
Conformed_Solicit_-_FA282319RA012.pdf PDF
Conformed_Solicit_-FA282319RA0120002.pdf PDF
Attachment_6-Past_Performance_Questionnaire.pdf PDF
Amendment_FA282319RA0120002_SF_30.pdf PDF
Show all 29

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DORM 19

COASTAL

EAST GATE

SHOPETTE

DORM 855

ADDIE R LEWIS SCHOOL

VISITING AMN QTRS

AAFES CAR CARE

NAVY EOD DORM

SWIMMING

POOL

LAUNDRY

DINING

FACILITY

DORM 854

HOBBY SHOP

EAST GATE

GYM

TAXILANE M EAST

TAXILANE T

GENERAL AVIATION RAMP

NE U

TA

XI

LA

N

E S

WASH

RACK

HG-3

TW

U

AEROCLUB

G-1

HUNG ORD/GUN CLEARING

ORD/GUN CLEARING

338°

E G

LI

N

B

LV

D

MCCARTHY AV

W

IC

KE

R

ST

DADE RD

"D " A

V

LOUISIANA AVE

TENNESSEE AVE

CHOCTAWHATCHEE RD

DAYTONA R

D

W E

S C

A M

BI

A

R D

CHEROKEE AV

EGLIN RD

O

KE

EC

H

O

BE

E R

D

S

AN

TA

R

O S

A R

D

ORGIA

A

V

DA

YT

O

NA

R D

EIGHTH ST

W

IC

KE

R

C I R

SEVENTH ST

SUWANEE

R

IM

ETER

R

D

O

CA

LA

R

D

PERIMET

DAY

TO

NA

RD

S

EM

IN

O

LE R

D

TENTH ST

FL

O

R

ID

A A

V

W

IC

KE

R

C R

HY

M

ES

R

D

CHAPEL 1

846T

87534

891945

BUS

889 890

85T

8587172

EG

LIN

B

LV

D

EIGHTH

FTFA-17-1100

RENOVATE BUILDING 886

EGLIN AFB, FLORIDA

BASE CIVIL ENGINEER

EGLIN AIR FORCE BASE, FLORIDA

AS-BUILT

STATE

OF

FLORIDA

GENERAL NOTESGENERAL DEMOLITION NOTESGENERAL ABBREVIATIONS

DRAWING SYMBOLS LEGEND BID OPTIONS

BASE CIVIL ENGINEER

BASE CIVIL ENGINEER

1.00 GENERAL NOTES

1.01 THESE STRUCTURAL NOTES SHALL BE APPLIED WITH THE TECHNICAL SPECIFICATIONS IN THE SPECIFICATIONS MANUAL. ANY CONFLICTING REQUIREMENTS SHALL BE BROUGHT TO THE ATTENTION

OF THE CONTRACTING OFFICER FOR RESOLUTION BEFORE PROCEEDING WITH FABRICATION OR

CONSTRUCTION.

1.02 DRAWINGS SHOW TYPICAL AND CERTAIN SPECIFIC CONDITIONS ONLY. FOR DETAILS NOT

SPECIFICALLY SHOWN, PROVIDE DETAILS SIMILAR TO THOSE SHOWN.

1.03 VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS BEFORE STARTING WORK. NOTIFY

CONTRACTING OFFICER OF ANY DISCREPANCY.

1.04 THE DESIGN, ADEQUACY, AND SAFETY OF ERECTION BRACING, SHORING, TEMPORARY SUPPORTS, ETC., ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR. TAKE NECESSARY PRECAUTIONS TO PROTECT THE EXISTING STRUCTURE AND ITS FOUNDATION AND TO LIMIT, TO THE EXTENT POSSIBLE, THE EFFECTS OF CONSTRUCTION THAT THE NEW STRUCTURE HAS ON THE EXISTING STRUCTURE.

1.05 COORDINATE STRUCTURAL CONTRACT DOCUMENTS WITH ARCHITECTURAL, MECHANICAL,

ELECTRICAL, PLUMBING AND CIVIL. NOTIFY CONTRACTING OFFICER OF ANY CONFLICT AND/OR OMISSION. CONTRACTOR SHALL MAKE NO DEVIATION FROM DESIGN DRAWINGS WITHOUT WRITTEN

APPROVAL OF THE ARCHITECT. FOR ADDITIONAL OPENINGS NOT SHOWN ON THE STRUCTURAL

DRAWINGS, SEE ARCHITECTURAL, MECHANICAL, AND PLUMBING DRAWINGS.

1.06 DESIGN CRITERIA:

THE STRUCTURE HAS BEEN DESIGNED UTILIZING THE FOLLOWING REFERENCES:

A. UFC 1&200&01, GENERAL BUILDING REQUIREMENTS

B. UFC 3&301&01, STRUCTURAL ENGINEERING, WITH CHANGE 1

C. INTERNATIONAL BUILDING CODE, 2012

D. ASCE 7&10, MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES

E. ACI 302.1 R&5, CONCRETE FLOOR AND SLAB CONSTRUCTION

F. ACI 318&11, BUILDING CODE REQUIREMENTS FOR CONCRETE STRUCTURES

G. ACI 360 R&06, DESIGN OF SLAB ON GRADES

1.07 DESIGN LOADS:

A. DEAD LOADS:

1. SELF WEIGHT OF 8” SLAB: 100 PSF

2. SELF WEIGHT OF 4” SLAB: 50 PSF

B. LIVE LOADS: (MAY BE REDUCED PER CODE)

1. RAMPS: 100 PSF

2. SLAB&ON&GRADE: 100 PSF

3. HEAVY TRAFFIC AREA OR 6&TON FORKLIFT: 250 PSF

C. WIND LOADS & STRUCTURE HAS BEEN DESIGNED TO CONFORM TO THE WIND PROVISIONS OF

ASCE 7&10. SEE WIND PRESSURE DIAGRAM & CHART FOR THE FOLLOWING:

1. BASIC WIND SPEED (3&SEC GUST)

2. BUILDING RISK CATEGORY

3. WIND EXPOSURE CATEGORY

4. INTERNAL PRESSURE COEFFICIENT

5. COMPONENT & CLADDING WIND PRESSURES

1.08 SHOP DRAWING SUBMITTALS:

A. THE REVIEW OF SUBMITTALS AND/OR SHOP DRAWINGS DONE BY THE CONTRACTING OFFICER

DOES NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY TO REVIEW AND CHECK SHOP

DRAWINGS BEFORE SUBMITTAL TO THE STRUCUTRAL ENGINEER. THE REVIEW BY THE

STRUCUTRAL ENGINEER IS FOR GENERAL CONFORMANCE ONLY. IF SHOP DRAWINGS HAVE

NOT BEEN REVIEWED AND APPROVED BEFORE SUBMITTAL TO THE STRUCUTURAL ENGINEER,

THEY SHALL BE RETURNED WITHOUT APPROVAL.

B. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR ANY AND ALL ERRORS AND OMISSIONS

ASSOCIATED WITH THE PREPARATION OF ALL SHOP DRAWINGS IN RELATIONSHIP TO THE

CONSTRUCTION DOCUMENTS.

C. ALL MODIFICATIONS MADE FOR SUBMITTALS THAT ARE RE&SUBMITTED SHALL CLEARLY NOTE

ALL CHANGES.

D. REPRODUCING THE CONTRACT DOCUMENTS FOR USE AS SHOP DRAWINGS IS NOT ALLOWED,

AND SHOP DRAWINGS WILL BE RETURNED WITHOUT APPROVAL.

E. GENERAL SHOP DRAWING REQUIREMENTS:

1. SUBMIT SHOP DRAWINGS AND ANY OTHER SPECIAL INFORMATION NECCESSARY FOR

PROPER FABRICATION, ERECTION, AND PLACEMENT OF STRUCTURAL FABRICATIONS.

INCLUDE PLANS, ELEVATIONS, AND SECTIONS. CLEARLY SHOW ANCHORAGES,

CONNECTIONS, AND ACCESSORY ITEMS. THE DETAILER MUST INTERPRET THE

CONTRACT DOCUMENTS AND CLEARLY CONVEY THIS INTERPRETATION TO THE FIELD IN

THE FORM OF PLACING OR ERECTION DRAWINGS.

2. CONCRETE REINFORCING DETAILER & PROVIDE PLACING DRAWINGS FOR FABRICATION

AND PLACING OF REINFORCING STEEL. THESE DRAWINGS SHALL INCLUDE, BUT ARE NOT

LIMITED TO, THE FOLLOWING: BAR LISTS, SCHEDULES, BENDING DETAILS, PLACING

DETAILS, PLACING PLANS, AND PLACING ELEVATIONS. CLEARLY SHOW FOUNDATION

REINFORCING. INDICATE BAR LENGTHS, LOCATION AND SPLICES OF CONTINUOUS BARS,

AND BAR SUPPORTS. CLEARLY SHOW LOCATIONS OF ALL DOWELS ON PLAN.

2.00 FOUNDATIONS AND SLAB&ON&GRADE

2.01 SHALLOW FOUNDATIONS HAVE BEEN DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF

1500 PSF.

2.02 AT THIS TIME NO GEOTECHNICAL REPORT HAS BEEN SUBMITTED. AN ALLOWABLE SOIL BEARING PRESSURE HAS BEEN CONSERVATIVELY ESTIMATED BASED ON SIMILAR PROJECTS OF THIS SIZE AND LOCATED IN THE SAME GENERAL AREA OF CONSTRUCTION. A QUALIFIED GEOTECHNICAL ENGINEER SHALL CHECK COMPACTION OF THE FOOTINGS. THE SOILS IMMEDIATELY BENEATH ALL FOOTINGS SHOULD BE COMPACTED FOR A MINIMUM DEPTH OF 12 INCHES TO A MINIMUM OF 95% OF THE SOIL’S MAXIMUM DENSITY AS DETERMINED BY THE MODIFIED PROCTOR TEST (ASTM D1557) USING A LARGE

TAMPER.

2.03 A QUALIFIED GEOTECHNICAL ENGINEER SHALL VERIFY CONDITION AND/OR ADEQUACY OF ALL

SUBGRADES, FILLS AND BACKFILLS BEFORE PLACEMENT OF FOUNDATIONS, FOOTINGS, SLABS,

WALLS, FILLS, BACKFILLS, ETC. SHOULD THE CONTRACTOR FIND UNDESIRABLE SOILS, HE SHALL STOP WORK AND IMMEDIATELY CONTACT CONTRACTING OFFICER . ALL FOOTINGS SHALL REST EITHER ON UNDISTURBED SOIL OR A MANUALLY OPERATED VIBRATORY SLED OR TAMPER SHOULD BE USED TO

DENSIFY ANY SOILS IN THE BOTTOM OF THE FOOTING TRENCHES LOOSENED DURING THE

EXCAVATION OPERATION.

2.04 SIDES OF FOUNDATIONS SHALL BE FORMED UNLESS CONDITIONS PERMIT EARTH FORMING.

FOUNDATIONS POURED AGAINST THE EARTH REQUIRE THE FOLLOWING PRECAUTIONS: SLOPE SIDES OF EXCAVATIONS AS APPROVED BY GEOTECHNICAL ENGINEER AND CLEAN UP SLOUGHING BEFORE

AND DURING CONCRETE PLACEMENT.

2.05 CONTRACTOR IS RESPONSIBLE FOR ADEQUATELY PROTECTING ALL EXCAVATION SLOPES.

2.06 DEWATER TO AT LEAST TWO FEET BELOW BOTTOM OF LOWEST FOUNDATION IF GROUNDWATER IS

ENCOUNTERED.

2.07 SLAB&ON&GRADE REQUIREMENTS:

A. UNLESS NOTED OTHERWISE, THE SLAB&ON&GRADE SHALL BE A MINIMUM OF 4 INCHES THICK, PLACED ON COMPACTED SUBGRADE, AND REINFORCED WITH 6 x 6 & W2.0 x W2.0 WWF IN FLAT

SHEETS (ROLLS ARE NOT PERMITTED). PROVIDE POSITIVE SUPPORT 2½” CLEAR FROM BOTTOM

OF SLAB. LAP MESH 12”.

B. PLACE CONTROL OR CONSTRUCTION JOINTS AT LOCATIONS INDICATED BY “C.J.” IF NOT

INDICATED, LOCATED JOINTS AT COLUMN CENTERLINES AND AT 20’&0” O.C MAX. SAWCUT

CONTROL JOINTS AS SOON AFTER POURING AS POSSIBLE, WHEN CONCRETE WILL NOT RAVEL;

12 HRS. MAX. CURE CONCRETE IN ACCORDANCE WITH ACI 301. BEGIN CURING IMMEDIATELY

AFTER POURING TO LIMIT CRACKING PRIOR TO SAWCUTTING CONTROL JOINTS.

C. THE TOP 12” OF THE SUBGRADE SHALL BE COMPACTED TO 95% OF THE MAXIMUM MODIFIED

PROCTOR DENSITY. DENSITY TESTS SHALL BE TAKEN AT 2500 SF INTERVALS.

D. VAPOR RETARDER IS ONLY REQUIRED OVER GEOFOAM. SEE SPECIFICATIONS FOR VAPOR

RETARDER MATERIAL. VAPOR RETARDER SHALL CONFORM TO ASTM E1745, CLASS A AND BE A

MINIMUM OF 15 MIL. THICKNESS. THE VAPOR RETARDER SHOULD BE PLACED OVER THE

GEOFOAM. VAPOR RETARDER SHOULD BE OVERLAPPED 8 IN. AND TAPED AT THE JOINTS AND

CAREFULLY FITTED AROUND SERVICE OPENINGS.

3.00 REINFORCED CONCRETE

3.01 ALL CONCRETE WORK SHALL CONFORM TO ACI 301&05, SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS. DESIGN IS BASED ON ACI 318&05, BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE. DETAIL CONCRETE REINFORCEMENT AND ACCESSORIES IN ACCORDANCE WITH ACI 315, DETAILING MANUAL. DETAIL ALL CONCRETE WALLS AND BEAMS ON THE SHOP DRAWINGS IN

ELEVATION UNLESS SPECIFICALLY APPROVED OTHERWISE. SUBMIT SHOP DRAWINGS FOR APPROVAL, SHOWING ALL FABRICATION DIMENSIONS AND LOCATIONS FOR PLACING REINFORCING STEEL AND

ACCESSORIES. DO NOT BEGIN FABRICATION UNTIL SHOP DRAWINGS ARE COMPLETED AND

REVIEWED.

3.02 UNLESS NOTED OTHERWISE, ALL CONCRETE SHALL BE NORMAL WEIGHT AND HAVE THE FOLLOWING

MINIMUM 28 DAY COMPRESSIVE STRENGTHS:

A. FOUNDATIONS 3000 PSI

B. RETAINING WALLS 4000 PSI

C. SLAB&ON&GRADE 4000 PSI

D. COLUMNS AND PIERS 4000 PSI

ALL CONCRETE SHALL HAVE ENTRAINED AIR, U.N.O. CONCRETE MAY CONTAIN A PROPERLY DESIGNED

SUPERPLASTICIZER FOR WORKABILITY.

3.03 REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60 UNLESS NOTED OTHERWISE.

3.04 THE PROPOSED MATERIALS AND MIX DESIGN SHALL BE FULLY DOCUMENTED AND REVIEWED BY THE OWNER'S TESTING LABORATORY. RESPONSIBILITY FOR OBTAINING THE REQUIRED DESIGN STRENGTH

IS THE CONTRACTOR'S.

3.05 USE OF CALCIUM CHLORIDE, CHLORIDE IONS, OR OTHER SALTS IN CONCRETE IS NOT PERMITTED.

3.06 HORIZONTAL CONSTRUCTION JOINTS ARE PERMITTED ONLY WHERE INDICATED. THE STRUCTURAL ENGINEER SHALL APPROVE THE LOCATION OF VERTICAL CONSTRUCTION JOINTS. CONSTRUCTION JOINTS SHALL BE THOROUGHLY ROUGHENED BY MECHANICAL MEANS, AND CLEANED. CONTRACTOR

SHALL SUBMIT DRAWINGS SHOWING INTENDED POURING SEQUENCE AND LOCATION OF

CONSTRUCTION JOINT TO THE ENGINEER FOR REVIEW. PROPOSED METHODS MUST BE ACCEPTABLE

TO THE ARCHITECT BEFORE USE.

3.07 UNLESS NOTED OTHERWISE, PLACE VERTICAL CONTROL JOINTS IN CONCRETE WALLS AT 10'&0" O.C.

(MAX), 3/4" DEEP, V&CHAMFERED ON BOTH FACES. CONSTRUCTION JOINTS SHALL FALL ON CONTROL JOINTS AND SHALL BE KEYED. STOP 50 PERCENT OF THE SPECIFIED LONGITUDINAL REINFORCEMENT

AT THE CONTROL JOINT.

3.08 CHAMFER OR ROUND ALL EXPOSED CORNERS A MINIMUM OF 3/4".

3.09 TIE ALL REINFORCING STEEL AND EMBEDMENTS SECURELY IN PLACE PRIOR TO PLACING CONCRETE.

PROVIDE SUFFICIENT SUPPORTS TO MAINTAIN THE POSITION OF REINFORCEMENT WITHIN SPECIFIED TOLERANCE DURING ALL CONSTRUCTION ACTIVITIES. "STICKING” DOWELS INTO WET CONCRETE IS

NOT PERMITTED.

3.10 PROVIDE CONTINUOUS REINFORCEMENT WHEREVER POSSIBLE; SPLICE ONLY AS SHOWN OR

APPROVED; STAGGER SPLICE WHERE POSSIBLE; USE FULL TENSION SPLICE (CLASS "B") UNLESS

NOTED OTHERWISE. DOWELS SHALL MATCH THE SIZE AND SPACING OF THE SPECIFIED

REINFORCEMENT AND SHALL BE LAPPED WITH FULL TENSION SPLICES (CLASS "B") UNLESS NOTED

OTHERWISE. TERMINATE BARS WITH STANDARD HOOKS.

3.11 REINFORCING STEEL SHALL HAVE THE FOLLOWING CONCRETE COVER UNLESS NOTED OTHERWISE

(PER ACI 318&05 PAR.7.7.1):

A. CONCRETE AGAINST EARTH (NOT FORMED): 3"

B. FORMED CONCRETE EXPOSED TO THE EARTH OR WEATHER:

1. #6 THROUGH #18 BARS: 2"

2. #5 BARS AND SMALLER: 1&1/2"

C. CONCRETE NOT EXPOSED TO EARTH OR WEATHER:

1. SLABS AND WALLS: 1"

2. BEAMS (STIRRUPS) AND COLUMNS (TIES): 1&1/2"

3.12 DO NOT PLACE DUCTS EXCEEDING ONE&THIRD THE SLAB OR WALL THICKNESS WITHIN THE SLAB OR

WALL UNLESS SPECIFICALLY SHOWN AND DETAILED ON STRUCTURAL DRAWINGS.

3.13 DO NOT WELD OR TACK WELD REINFORCING STEEL UNLESS APPROVED OR DIRECTED BY THE

CONTRACTING OFFICER.

3.14 ALL REINFORCING STEEL PLACEMENTS SHALL BE REVIEWED BY A REGISTERED STRUCTURAL

ENGINEER, OR BY A REPRESENTATIVE RESPONSIBLE TO HIM. (RE: ACI 318 PAR. 1.3.1)

4.00 STRUCTURAL STEEL

4.01 STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED AND ERECTED ACCORDING TO AISC

"SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS, ASD, LATEST EDITION.

4.02 SUBMIT SHOP DRAWINGS PREPARED IN ACCORDANCE WITH AISC MANUAL "DETAILING FOR STEEL CONSTRUCTION", LATEST EDITION. STEEL FABRICATOR SHALL SUPPLY ANCHOR BOLT LOCATION DRAWINGS. DO NOT BEGIN FABRICATION UNTIL SHOP DRAWINGS ARE COMPLETED AND REVIEWED.

4.03 HEADED STUD SHEAR CONNECTORS (INDICATED AS “HS” ON PLANS): ASTM A 108, GRADES 1010 THROUGH 1020, HEADED&STUD TYPE, COLD&FINISHED CARBON STEEL; AWS D1.1, TYPE B. USE

AUTOMATIC END WELDING OF HEADED&STUD SHEAR CONNECTORS ACCORDING TO AWS D1.1 AND

MANUFACTURER’S WRITTEN INSTRUCTIONS.

4.04 STRUCTURAL STEEL SHAPES, PLATES, ANGLES, AND CHANNELS SHALL CONFORM TO ASTM A36

UNLESS NOTED OTHERWISE.

5.00 COLD FORMED METAL FRAMING SEE SEPARATE SECTION BELOW FOR METAL TRUSSES

5.01 COLD FORMED METAL STUDS: GALVANIZED STEEL PER ASTM A525, G60 COATING MEETING THE

REQUIREMENTS OF ASTM A446 GRADE A, WITH A MINIMUM YIELD STRENGTH OF 33,000 PSI.

5.02 ALL STUDS INDICATED SHALL HAVE 1&5/8” WIDE FLANGES WITH A ½” LIP.

ALL TRACK INDICATED SHALL HAVE 1&1/4” WIDE FLANGES.

5.03 STUDS SHALL BE LOCATED DIRECTLY BELOW ROOF TRUSSES.

5.04 GABLE END WALLS SHALL BE FRAMED FULL HEIGHT.

5.05 TOP AND BOTTOM TRACKS SHALL BE 18 GA. MINIMUM. TRACKS SHALL BE CONTINUOUS AND LAP SPLICED WITH A 22" PIECE OF 20 GA. TRACK AND 6 #10 SCREWS EACH SIDE OF SPLICE. LOCATE SPLICE

MIDWAY BETWEEN STUDS.

5.06 INTERIOR WALLS:

WALL STUDS TO BE 6", 18&GAUGE STUDS SPACED 16" ON CENTER.

WALL HEIGHT SHALL NOT EXCEED 14&FT. PROVIDE LATERAL BRIDGING AT 48" ON CENTER OVER FULL

HEIGHT OF WALL

a a

5 5 a a

WIND LOAD DETERMINATION ASSUMPTIONS & INTERNATIONAL BUILDING CODE 2015

ROOF SLOPE

142 C 13.8 3 ON 12 II ENCLOSED

ULTIMATE DESIGN WIND PRESSURES FOR COMPONENTS AND CLADDING (PSF)

ROOF ZONE 1

ROOF ZONE 2 ROOF ZONE 3

WALL ZONE 4 WALL ZONE 5

O&HANG O&HANG

25.3 &40.2 &70.0 44.0 &47.7 &58.8

50 20.1 &37.6 &57.0 39.4 &43.1 &49.7

17.9 &36.5 &51.4 37.4 &41.1 &45.7

&103.5

&87.9

&81.2

&137.8

&106.6

&93.1

NOTES:

1. FOR EFFECTIVE AREAS BETWEEN THOSE GIVEN ABOVE THE LOAD MAY BE INTERPOLATED,

OTHERWISE USE THE LOAD ASSOCIATED WITH THE LOWER EFFECTIVE AREA.

2. THE EDGE STRIP, a = 5.5 FT.

3. PRESSURES SHALL BE APPLIED IN ACCORDANCE WITH THE FIGURE SHOWN ON THIS SHEET.

< 10

> 100

WIND VELOCITY

(MPH)

EXPOSURE

CATEGORY

MEAN ROOF

HEIGHT (FT.)

RISK

CATEGORY

ENCLOSURE

CATEGORY

EFF.

AREA

(SQ. FT)

4. PRESSURES GIVEN ARE ULTIMATE LOADS TO BE USED WITH STRENGTH DESIGN. FOR

SERVICE LOADS TO BE USED WITH ALLOWABLE STRESS DESIGN, MULTIPLY THE PRESSURES

BY 0.60. SEE TABLES 2.3 AND 2.4 IN ASCE 7&10 FOR MORE INFORMATION ON LOAD

COMBINATIONS.

&81.9

&81.9

&81.9

25.3

20.1

17.9

25.3

20.1

17.9

44.0

39.4

37.4

REPRESENTATIVE DIAGRAM

ATFP DESIGN CRITERIA PER UFC 4&010&01 DATED 9 FEBRUARY 2012, CHANGE 1, 1 OCTOBER 2013

BUILDING LOCATION: WITHIN CONTROLLED PERIMETER

BUILDING OCCUPANCY CATEGORY: LOW OCCUPANCY

LEVEL OF PROTECTION: LOW

EXPLOSIVE WEIGHT: TYPE II

PER UFC 4&010&01 LOW OCCUPANCY BUILDING IS CLASSIFIED AS ANY BUILDING OR PORTION OF A BUILDING ROUTINELY OCCUPIED BY FEWER THAN 11 DOD PERSONNEL OR WITH A POPULATION DENSITY OF LESS THAN

ONE PERSON PER 40 GROSS SQUARE FEET (40 GROSS SQUARE METERS).

1&9.1 LOW OCCUPANCY BUILDINGS: BUILDING WHOSE OCCUPANCIES DO NOT MEET THE OCCUPANCY LEVELS OF INHABITED OR PRIMARY GATHERING BUILDINGS OR OF BILLETING ARE EXEMPT FROM ALL PROVISIONS OF THESE

STANDARDS.

BUILDING 886 WIND LOAD INFORMATION

a

5 5 a a

1 a

WIND LOAD DETERMINATION ASSUMPTIONS & INTERNATIONAL BUILDING CODE 2015

ROOF SLOPE

132 C 15.0 0.25 ON 12 I OPEN

ULTIMATE DESIGN WIND PRESSURES FOR COMPONENTS AND CLADDING (PSF)

ROOF

ZONE 1

ROOF

ZONE 2

ROOF

ZONE 3

32.4 &30.5 &46.9

>9, <36

&91.6

&46.9

&30.5

NOTES:

1. FOR EFFECTIVE AREAS BETWEEN THOSE GIVEN ABOVE THE LOAD MAY BE INTERPOLATED,

OTHERWISE USE THE LOAD ASSOCIATED WITH THE LOWER EFFECTIVE AREA.

2. THE EDGE STRIP, a = 3.0 FT.

3. PRESSURES SHALL BE APPLIED IN ACCORDANCE WITH THE FIGURE SHOWN ON THIS SHEET.

<9

>36

WIND VELOCITY

(MPH)

EXPOSURE

CATEGORY

MEAN ROOF

HEIGHT (FT.)

RISK

CATEGORY

ENCLOSURE

CATEGORY

EFF.

AREA

(SQ. FT)

4. PRESSURES GIVEN ARE ULTIMATE LOADS TO BE USED WITH STRENGTH DESIGN. FOR

SERVICE LOADS TO BE USED WITH ALLOWABLE STRESS DESIGN, MULTIPLY THE PRESSURES

BY 0.60. SEE TABLES 2.3 AND 2.4 IN ASCE 7&10 FOR MORE INFORMATION ON LOAD

COMBINATIONS.

48.8 64.8

48.8

32.4

REPRESENTATIVE DIAGRAM

CANOPY WIND LOAD INFORMATION

32.4

32.4 32.4

48.8&30.5

&30.5

&46.9

&30.5

WINDWARD

FASCIA

LEEWARD

FASCIA

48.3 &32.2

AS�BUILT

96 CEG, OFFICE FORM 002, FY2018

DATEREVISION BY APPR'D

PROGRAM MANAGER

ENVIROMENTAL

INDEX NO.

CENM

APPROVED

APPROVED

APPROVED

SIGNATURE

DATE

USING AGENCY

APPROVED

APPROVED

COMMUNICATIONS

OPERATIONS ENGINEERING

APPROVED

APPROVED

APPROVED

APPROVED

FIRE PREVENTION

SAFETY REPRESENTATIVE

DIR. BASE MED. SERVICE

PROJ. ENGR.

DRAWN BY TITLE

CONTENTS

APPROVED

SCALE

DATE

96 CEG/CEN

APPROVED

DEPUTY BASE CIVIL ENGINEER

SPEC. NO. PROJ. NO. DRAWING NO. FILE NO.

SHEET OFFTFA

DESCRIPTION

SECURITY FORCES

APPROVED

ASUS

APPROVED

CHELCO

APPROVED

D

EU

SOJ

R E

G

ISTERE

R E

E

NIGNED

EPH

ER

IL

SI

U

OL

A

DIOL

F R

STATE OF

No. 54319

E T

ACFIT

C R

E

I

301 West Cervantes St. Tel. 850.429.1951301 West Cervantes St. Tel. 850.429.1951301 West Cervantes St. Tel. 850.429.1951301 West Cervantes St. Tel. 850.429.1951 Pensacola, FL 32501 Pensacola, FL 32501 Pensacola, FL 32501 Pensacola, FL 32501

JOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLC S T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SJDA

STATE OF FLORIDA STATE OF FLORIDA STATE OF FLORIDA STATE OF FLORIDA

P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515

JULY,2019

J. SUMRALL

L. DeREUIL

Hernandez Calhoun Design International Architecture ● Interior Design

RENOVATE

BUILDING 886

EGLIN, AFB,FLORIDA

17�1100 XXXX17AP

Hernandez Calhoun Design International Architecture ● Interior Design 17AP

BASE CIVIL ENGINEER

EGLIN AIR FORCE BASE, FLORIDA

JDA Job #: 17199JDA Job #: 17199JDA Job #: 17199JDA Job #: 17199

7/12/20197/12/20197/12/20197/12/2019

S-1

GENERAL NOTES

A

A

B

B

C

C

D

D

E

E

F

F

G

G

H

H

I

I

J

J

K

K

L

L

S-3

S-3

S-3

S-3

S-3

13'&6" 15'&0" 15'&0" 15'&0" 15'&0" 15'&0" 15'&0" 15'&0" 15'&0" 15'&0" 13'&8" 6'&7 3/4"

'&0

'&4

'&0

S-5

7'&0"

6' &0

7" SLAB

4" SLAB4" SLAB

4" SLAB

4" SLAB

7" SLAB

&1'&7 1/2"

S-5

7" SLAB

S-5

Sim

S-5

Sim

S-6

S-5

S-5

Sim

S-5

Sim

7" SLAB

9' &9

S-5

S-5

S-6

S-6

A B C D E F G H I J K L S-4

13'&6" 15'&0" 15'&0" 15'&0" 15'&0" 15'&0" 15'&0" 15'&0" 15'&0" 15'&0" 13'&8" 6'&7 3/4"

S-6

7" SLAB7" SLAB9'

&6

S-5

S-5

4" SLAB

4" SLAB

LEGEND

= CONSTRUCTION JOINT; PLACE C.J. AT 15'-0" O.C. MAXIMUM SPACING. CUT 50% OF REINF. AT

JOINTS. PROVIDE VERTICAL WALL JOINTS AT HORIZONTAL JOINT LOCATIONS, TYPICAL.

C.J.

= 8" CONCRETE WALL. WALL SHALL BE REINFORCED WITH #4 VERTICAL REINFORCING AT 1'-0" ON

CENTER IN CENTER OF 8" WALL & WITH #4 HORIZONTAL REINFORCING AT 0'-8" ON CENTER.

= SLAB DEPRESSION; SEE PLAN FOR DEPRESSION EXTENTS AND DEPRESSION DEPTH AT DOCK

LEVELER.

&X'&X"

7" MINIMUM THICKNESS SLAB-ON-GRADE REINFORCED WITH #4 BARS @ 8" O.C. BOTTOM BARS EACH WAY WITH 2" CLR. TO BOT. 7" SLABS WILL REQUIRE DOWELLED JOINTS, WHICH WILL REQUIRE (2) POURS7" SLAB =

4" MINIMUM THICKNESS SLAB-ON-GRADE REINFORCED WITH WWF 6x6 W2.0xW2.0 WITH 2" CLR.

POSITIVE SUPPORT FROM BOTTOM OF SLAB.

4" SLAB =

(2) #4x4'-0" RE-ENTRANT CRACK CONTROL REINF. W/ 1-1/2"

CLR TO TOP OF SLAB

= VERTICAL CONCRETE WALL CONTROL JOINT LOCATION (15 FT MAXIMUM SPACING); SEE TYPICAL DETAILS ON S&7

AS�BUILT

96 CEG, OFFICE FORM 002, FY2018

DATEREVISION BY APPR'D

PROGRAM MANAGER

ENVIROMENTAL

INDEX NO.

CENM

APPROVED

APPROVED

APPROVED

SIGNATURE

DATE

USING AGENCY

APPROVED

APPROVED

COMMUNICATIONS

OPERATIONS ENGINEERING

APPROVED

APPROVED

APPROVED

APPROVED

FIRE PREVENTION

SAFETY REPRESENTATIVE

DIR. BASE MED. SERVICE

PROJ. ENGR.

DRAWN BY TITLE

CONTENTS

APPROVED

SCALE

DATE

96 CEG/CEN

APPROVED

DEPUTY BASE CIVIL ENGINEER

SPEC. NO. PROJ. NO. DRAWING NO. FILE NO.

SHEET OFFTFA

DESCRIPTION

SECURITY FORCES

APPROVED

ASUS

APPROVED

CHELCO

APPROVED

D

EU

SOJ

R E

G

ISTERE

R E

E

NIGNED

EPH

ER

IL

SI

U

OL

A

DIOL

F R

STATE OF

No. 54319

E T

ACFIT

C R

E

I

301 West Cervantes St. Tel. 850.429.1951301 West Cervantes St. Tel. 850.429.1951301 West Cervantes St. Tel. 850.429.1951301 West Cervantes St. Tel. 850.429.1951 Pensacola, FL 32501 Pensacola, FL 32501 Pensacola, FL 32501 Pensacola, FL 32501

JOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLC S T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SJDA

STATE OF FLORIDA STATE OF FLORIDA STATE OF FLORIDA STATE OF FLORIDA

P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515

JULY,2019

J. SUMRALL

L. DeREUIL

Hernandez Calhoun Design International Architecture ● Interior Design

RENOVATE

BUILDING 886

EGLIN, AFB,FLORIDA

17�1100 XXXX17AP

Hernandez Calhoun Design International Architecture ● Interior Design 17AP

BASE CIVIL ENGINEER

EGLIN AIR FORCE BASE, FLORIDA

JDA Job #: 17199JDA Job #: 17199JDA Job #: 17199JDA Job #: 17199

7/12/20197/12/20197/12/20197/12/2019

S-2

OVERALL PLAN

1/8" = 1'-0"S-2

1 BLDG. 886 DOCK REPAIR - BASE BID

1/8" = 1'-0"S-2

2 BLDG. 886 DOCK REPAIR - BID OPTION

C

S-5

4" SLAB

1/4

7'&0"

6' &0

G H

4" SLAB

1/4" / 1' - 0"

7'&0"

6' &0

S-5

Sim

I J

1/4" / 1' - 0"

C.J.

DOCK

LEVELER

7" SLAB

C.J.

C.J.

C .J

C .J

10'&0" 10'&0" 10'&0"

S-5

7" SLAB

S-5

S-6

S-6

1/4" / 1' - 0"

/4

S-6

30'&0"

'&0

1'&3" 16'&4 1/2" 11'&1 1/2" 1'&3"

1' &3

'&7

/2

ALUMINUM CANOPY

COLUMN BLOCKOUT

LOCATIONS

PROVIDE 4'0"x2&6"' x 2'&0" DEEP

UNREINFORCED CONCRETE FOOTING

FOR CENTER COLUMN SUPPORT.

TYP.

A B C

/4

1/4" / 1' - 0"

1/4" / 1' - 0"

/4

1" / 1' - 0"

1/4" / 1' - 0"

1" / 1' - 0"

4" SLAB

4" SLAB

8'&0" 6'&8" 6'&8" 6'&8"

4' &0

9'

&6

C .J

C .J

C .J

C .J

C .J

C .J

C .J

C

.J

C .J

C.J.

S-6

ALUMINUM CANOPY

COLUMN BLOCKOUT

LOCATIONS

PROVIDE 4'0"x2&6"' x 2'&0" DEEP

UNREINFORCED CONCRETE FOOTING

FOR CENTER COLUMN SUPPORT.

(TYP. 5X)

5'&0"

S-6

I J K L

7" SLAB

/4

C .J

C .J

15' & 0" 15' & 0" 13' & 8" 6' & 7 3/4"

S-5

/4

LEGEND

= CONSTRUCTION JOINT; PLACE C.J. AT 15'-0" O.C. MAXIMUM SPACING. CUT 50% OF REINF. AT

JOINTS. PROVIDE VERTICAL WALL JOINTS AT HORIZONTAL JOINT LOCATIONS, TYPICAL.

C.J.

= 8" CONCRETE WALL. WALL SHALL BE REINFORCED WITH #4 VERTICAL REINFORCING AT 1'-0" ON

CENTER IN CENTER OF 8" WALL & WITH #4 HORIZONTAL REINFORCING AT 0'-8" ON CENTER.

= SLAB DEPRESSION; SEE PLAN FOR DEPRESSION EXTENTS AND DEPRESSION DEPTH AT DOCK

LEVELER.

&X'&X"

7" MINIMUM THICKNESS SLAB-ON-GRADE REINFORCED WITH #4 BARS @ 8" O.C. BOTTOM BARS EACH WAY WITH 2" CLR. TO BOT. 7" SLABS WILL REQUIRE DOWELLED JOINTS, WHICH WILL REQUIRE (2) POURS7" SLAB =

4" MINIMUM THICKNESS SLAB-ON-GRADE REINFORCED WITH WWF 6x6 W2.0xW2.0 WITH 2" CLR.

POSITIVE SUPPORT FROM BOTTOM OF SLAB.

4" SLAB =

(2) #4x4'-0" RE-ENTRANT CRACK CONTROL REINF. W/ 1-1/2"

CLR TO TOP OF SLAB

= VERTICAL CONCRETE WALL CONTROL JOINT LOCATION (15 FT MAXIMUM SPACING); SEE TYPICAL DETAILS ON S&7

AS�BUILT

96 CEG, OFFICE FORM 002, FY2018

DATEREVISION BY APPR'D

PROGRAM MANAGER

ENVIROMENTAL

INDEX NO.

CENM

APPROVED

APPROVED

APPROVED

SIGNATURE

DATE

USING AGENCY

APPROVED

APPROVED

COMMUNICATIONS

OPERATIONS ENGINEERING

APPROVED

APPROVED

APPROVED

APPROVED

FIRE PREVENTION

SAFETY REPRESENTATIVE

DIR. BASE MED. SERVICE

PROJ. ENGR.

DRAWN BY TITLE

CONTENTS

APPROVED

SCALE

DATE

96 CEG/CEN

APPROVED

DEPUTY BASE CIVIL ENGINEER

SPEC. NO. PROJ. NO. DRAWING NO. FILE NO.

SHEET OFFTFA

DESCRIPTION

SECURITY FORCES

APPROVED

ASUS

APPROVED

CHELCO

APPROVED

D

EU

SOJ

R E

G

ISTERE

R E

E

NIGNED

EPH

ER

IL

SI

U

OL

A

DIOL

F R

STATE OF

No. 54319

E T

ACFIT

C R

E

I

301 West Cervantes St. Tel. 850.429.1951301 West Cervantes St. Tel. 850.429.1951301 West Cervantes St. Tel. 850.429.1951301 West Cervantes St. Tel. 850.429.1951 Pensacola, FL 32501 Pensacola, FL 32501 Pensacola, FL 32501 Pensacola, FL 32501

JOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLC S T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SJDA

STATE OF FLORIDA STATE OF FLORIDA STATE OF FLORIDA STATE OF FLORIDA

P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515

JULY,2019

J. SUMRALL

L. DeREUIL

Hernandez Calhoun Design International Architecture ● Interior Design

RENOVATE

BUILDING 886

EGLIN, AFB,FLORIDA

17�1100 XXXX17AP

Hernandez Calhoun Design International Architecture ● Interior Design 17AP

BASE CIVIL ENGINEER

EGLIN AIR FORCE BASE, FLORIDA

JDA Job #: 17199JDA Job #: 17199JDA Job #: 17199JDA Job #: 17199

7/12/20197/12/20197/12/20197/12/2019

S-3

ENLARGED PLANS - BASE BID

1/4" = 1'-0"S-3

1 BASE BID - NORTH STAIR PAD

1/4" = 1'-0"S-3

2 BASE BID - NORTH STAIR PAD

1/4" = 1'-0"S-3

3 BASE BID - NORTH LOADING DOCK

1/4" = 1'-0"S-3

4 BASE BID - SOUTH RAMP

1/4" = 1'-0"S-3

5 BASE BID - LOADING DOCK

SHEET NOTE: COORDINATE TOP OF SLAB ELEVATIONS WITH ARCHITECTURAL DRAWINGS.

C D E F G H I J K L

8" SLAB 8" SLAB

/4

/4

/4

C .J

C .J

C .J

C .J

C .J

C .J

C .J

C .J

15' & 0" 15' & 0" 15' & 0" 15' & 0" 15' & 0" 15' & 0" 15' & 0" 15' & 0" 13' & 8"

S-5

S-5

LEGEND

= CONSTRUCTION JOINT; PLACE C.J. AT 15'-0" O.C. MAXIMUM SPACING. CUT 50% OF REINF. AT

JOINTS. PROVIDE VERTICAL WALL JOINTS AT HORIZONTAL JOINT LOCATIONS, TYPICAL.

C.J.

= 8" CONCRETE WALL. WALL SHALL BE REINFORCED WITH #4 VERTICAL REINFORCING AT 1'-0" ON

CENTER IN CENTER OF 8" WALL & WITH #4 HORIZONTAL REINFORCING AT 0'-8" ON CENTER.

= SLAB DEPRESSION; SEE PLAN FOR DEPRESSION EXTENTS AND DEPRESSION DEPTH AT DOCK

LEVELER.

&X'&X"

7" MINIMUM THICKNESS SLAB-ON-GRADE REINFORCED WITH #4 BARS @ 8" O.C. BOTTOM BARS EACH WAY WITH 2" CLR. TO BOT. 7" SLABS WILL REQUIRE DOWELLED JOINTS, WHICH WILL REQUIRE (2) POURS7" SLAB =

4" MINIMUM THICKNESS SLAB-ON-GRADE REINFORCED WITH WWF 6x6 W2.0xW2.0 WITH 2" CLR.

POSITIVE SUPPORT FROM BOTTOM OF SLAB.

4" SLAB =

(2) #4x4'-0" RE-ENTRANT CRACK CONTROL REINF. W/ 1-1/2"

CLR TO TOP OF SLAB

= VERTICAL CONCRETE WALL CONTROL JOINT LOCATION (15 FT MAXIMUM SPACING); SEE TYPICAL DETAILS ON S&7

AS�BUILT

96 CEG, OFFICE FORM 002, FY2018

DATEREVISION BY APPR'D

PROGRAM MANAGER

ENVIROMENTAL

INDEX NO.

CENM

APPROVED

APPROVED

APPROVED

SIGNATURE

DATE

USING AGENCY

APPROVED

APPROVED

COMMUNICATIONS

OPERATIONS ENGINEERING

APPROVED

APPROVED

APPROVED

APPROVED

FIRE PREVENTION

SAFETY REPRESENTATIVE

DIR. BASE MED. SERVICE

PROJ. ENGR.

DRAWN BY TITLE

CONTENTS

APPROVED

SCALE

DATE

96 CEG/CEN

APPROVED

DEPUTY BASE CIVIL ENGINEER

SPEC. NO. PROJ. NO. DRAWING NO. FILE NO.

SHEET OFFTFA

DESCRIPTION

SECURITY FORCES

APPROVED

ASUS

APPROVED

CHELCO

APPROVED

D

EU

SOJ

R E

G

ISTERE

R E

E

NIGNED

EPH

ER

IL

SI

U

OL

A

DIOL

F R

STATE OF

No. 54319

E T

ACFIT

C R

E

I

301 West Cervantes St. Tel. 850.429.1951301 West Cervantes St. Tel. 850.429.1951301 West Cervantes St. Tel. 850.429.1951301 West Cervantes St. Tel. 850.429.1951 Pensacola, FL 32501 Pensacola, FL 32501 Pensacola, FL 32501 Pensacola, FL 32501

JOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLC S T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SJDA

STATE OF FLORIDA STATE OF FLORIDA STATE OF FLORIDA STATE OF FLORIDA

P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515

JULY,2019

J. SUMRALL

L. DeREUIL

Hernandez Calhoun Design International Architecture ● Interior Design

RENOVATE

BUILDING 886

EGLIN, AFB,FLORIDA

17�1100 XXXX17AP

Hernandez Calhoun Design International Architecture ● Interior Design 17AP

BASE CIVIL ENGINEER

EGLIN AIR FORCE BASE, FLORIDA

JDA Job #: 17199JDA Job #: 17199JDA Job #: 17199JDA Job #: 17199

7/12/20197/12/20197/12/20197/12/2019

S-4

ENLARGED PLANS - BID OPTION

1/4" = 1'-0"S-4

1 BID OPTION - SOUTH LOADING DOCK

SHEET NOTE: COORDINATE TOP OF SLAB ELEVATIONS WITH ARCHITECTURAL DRAWINGS.

EXISTING SLAB

7" SLAB

EXISTING FOUNDATIONS

EXISTING WALL

1/2" PREMOLDED

JOINT FILLER

REFER TO DETAIL ON 1/S&7

FOR TYPICAL DETAIL AT NEW

SLAB TO EXISTING SLAB

COMPACTED

SUBGRADE

EXISTING SLAB 7" SLAB (SEE PLAN

FOR REINFORCING)

EXISTING FOUNDATIONS

EXISTING WALL

REFER TO DETAIL 1/S&5

FOR CONCRETE REPAIR

IN EXISTING NOTCH

6" 8" 1'&6"

4" SLAB, (SEE PLAN

FOR REINFORCING)

8" CONCRETE WALL; (SEE

PLAN FOR REINFORCING)

REFER TO DETAIL ON 1/S&7

FOR TYPICAL DETAIL AT NEW

SLAB TO EXISTING SLAB

1' &0

PROVIDE 3/4" CHAMFER;

TYPICAL

PROVIDE RAILINGS TO

MEET THE REQUIREMENTS

OF THE IBC AND ARCHITECTURAL

DRAWINGS AND SPECIFICATIONS.

1/2" PREMOLDED

JOINT FILLER

COMPACTED

SOIL

4"

#4 EDGE BAR 1&1/2" CLR,

TYP. AT ALL EDGES

#3 @ 12" O.C.

24"

24"

8" M

IN

B A

S E

D O

N G

R A

D E

V A

R

IE

S

'&2

T O

'&1

0"

#4 @ 8" CONT.

#4 @ 12"

(6) # 4 CONT.

BARS

GEOFOAM EPS 22 FILL

(OR EQUIVALENT)

COMPACTED

SUBGRADE

MEMBRANE TO PROTECT

FORM FROM PETROLEUM

PRODUCTS

I

7" SLAB (SEE PLAN

FOR REINFORCING)

6" 8" 1'&6"

7" SLAB, (SEE PLAN

FOR REINFORCING)

8" CONCRETE WALL; (SEE

PLAN FOR REINFORCING)

1' &0

"1/2" PREMOLDED

JOINT FILLER

GALV L3x3x1/4 W/ 1/2" DIA. x 6" HS @ 12" O.C.

#3 @ 12" O.C.

24"

24"

PROVIDE 3/4" CHAMFER;

TYPICAL

WEEP HOLES @ WALL

CONTROL JOINTS. #4 @ 8" CONT.

#4 @ 12"

(6) # 4 CONT.

BARS

GEOFOAM EPS 22 FILL

(OR EQUIVALENT)

MEMBRANE TO PROTECT

FORM FROM PETROLEUM

PRODUCTS

COMPACTED

SUBGRADE

6" 8" 1'&6"

7" SLAB, (SEE PLAN

FOR REINFORCING)

8" CONCRETE WALL;

(SEE PLAN FOR

REINFORCING)

1' &0

GALV L3x3x1/4 W/ 1/2" DIA. x 6" HS @ 12" O.C.

#3 @ 12" O.C.

24"

PROVIDE 3/4" CHAMFER;

TYPICAL

24"

EXISTING FOUNDATIONS

EXISTING WALL

REMOVE CRACKED CONCRETE

FROM NOTCH SEE PHOTO, CUT

CLEAN EDGE & PROVIDE 1/2"

RADIUS EDGE AT DOOR.

WHERE APPLICABLE, REPAIR SPALLED

CONCRETE W/ HORIZONTAL CUT, BONDING

AGENT & PATCHING MORTAR. ASSUME 20

LINEAR FT. FOR BIDDING PURPOSES.

BOND BREAKER

(LAYER OF 30# FELT)

1/2" PREMOLDED

JOINT FILLER

B A

S E

D O

N G

R A

D E

V A

R

IE

S

'&2

T O

'&1

0"

FIN. FLOOR1/

2"

S T

E P

#4 @ 8" CONT.

#4 @ 12"

(6) # 4 CONT.

BARS

GEOFOAM EPS 22

FILL (OR

EQUIVALENT)

MEMBRANE TO PROTECT

FORM FROM PETROLEUM

PRODUCTS

COMPACTED

SUBGRADE

EXISTING SLAB

REFER TO DETAIL ON

1/S&7 FOR TYPICAL

DETAIL AT NEW SLAB

TO EXISTING SLAB

1/2" P.J.F.

EXISTING WALL

REMOVE CRACKED CONCRETE

FROM NOTCH SEE PHOTO, CUT

CLEAN EDGE & PROVIDE 1/2"

RADIUS EDGE AT DOOR.

BOND BREAKER

(LAYER OF 30# FELT)

REPAIR SPALLED CONCRETE W/

HORIZONTAL CUT, BONDING

AGENT & PATCHING MORTAR.

1/2" PREMOLDED

JOINT FILLER

7" SLAB, (SEE PLAN

FOR REINFORCING)

GEOFOAM EPS

22 FILL (OR

EQUIVALENT)

MEMBRANE TO

PROTECT FORM FROM

PETROLEUM PRODUCTS

AS�BUILT

96 CEG, OFFICE FORM 002, FY2018

DATEREVISION BY APPR'D

PROGRAM MANAGER

ENVIROMENTAL

INDEX NO.

CENM

APPROVED

APPROVED

APPROVED

SIGNATURE

DATE

USING AGENCY

APPROVED

APPROVED

COMMUNICATIONS

OPERATIONS ENGINEERING

APPROVED

APPROVED

APPROVED

APPROVED

FIRE PREVENTION

SAFETY REPRESENTATIVE

DIR. BASE MED. SERVICE

PROJ. ENGR.

DRAWN BY TITLE

CONTENTS

APPROVED

SCALE

DATE

96 CEG/CEN

APPROVED

DEPUTY BASE CIVIL ENGINEER

SPEC. NO. PROJ. NO. DRAWING NO. FILE NO.

SHEET OFFTFA

DESCRIPTION

SECURITY FORCES

APPROVED

ASUS

APPROVED

CHELCO

APPROVED

D

EU

SOJ

R E

G

ISTERE

R E

E

NIGNED

EPH

ER

IL

SI

U

OL

A

DIOL

F R

STATE OF

No. 54319

E T

ACFIT

C R

E

I

301 West Cervantes St. Tel. 850.429.1951301 West Cervantes St. Tel. 850.429.1951301 West Cervantes St. Tel. 850.429.1951301 West Cervantes St. Tel. 850.429.1951 Pensacola, FL 32501 Pensacola, FL 32501 Pensacola, FL 32501 Pensacola, FL 32501

JOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLC S T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SJDA

STATE OF FLORIDA STATE OF FLORIDA STATE OF FLORIDA STATE OF FLORIDA

P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515

JULY,2019

J. SUMRALL

L. DeREUIL

Hernandez Calhoun Design International Architecture ● Interior Design

RENOVATE

BUILDING 886

EGLIN, AFB,FLORIDA

17�1100 XXXX17AP

Hernandez Calhoun Design International Architecture ● Interior Design 17AP

BASE CIVIL ENGINEER

EGLIN AIR FORCE BASE, FLORIDA

JDA Job #: 17199JDA Job #: 17199JDA Job #: 17199JDA Job #: 17199

7/12/20197/12/20197/12/20197/12/2019

S-5

SECTIONS AND DETAILS

3/4" = 1'-0"S-5

2 NEW SLAB ON GRADE DETAIL

3/4" = 1'-0"S-5

4 CONCRETE WALL AT STAIR

3/4" = 1'-0"S-5

5 LOADING BAY SECTION

3/4" = 1'-0"S-5

1 TYPICAL LOADING DOCK SECTION

IMAGE AT EXISTING DOOR

3/4" = 1'-0"S-5

3 LOADING BAY SECTION

PROVIDE 3/4" CHAMFER;

TYPICAL

PROVIDE RAILINGS TO

MEET THE REQUIREMENTS

OF THE IBC AND ARCHITECTURAL

DRAWINGS AND SPECIFICATIONS.

4" SLAB&ON&GRADE

RAMP; TYPICAL

#4 CONT.;

TYPICAL

CENTERLINE OF

RAILINGS

CENTERLINE OF RAILING

SLAB EDGE

SLAB EDGE

EXISTING

FOUNDATIONS

EXISTING WALL

4" SLAB&ON&GRADE

RAMP; TYPICAL

4"

4"4"

4'-6"FIN. FLOOR1/

2"

S T

E P

EXISTING

SLAB

REPLACE DEMOLISHED

PAVEMENT

COMPACTED

SUBGRADE COMPACTED

FILL

LINE OF

EXCAVATION

8" M

IN

#3 @ 12" O.C.

24"

24"

#3 @ 12" O.C.

24"

24"

REFER TO DETAIL 1/S&5

FOR CONCRETE REPAIR

IN EXISTING NOTCH

#4 @ 8" CONT.

#4 @ 12"

(6) # 4 CONT.

BARS

#4 @ 8" CONT.

#4 @ 12"

(5) # 4 CONT.

BARS

#4 @ 8" CONT.

#4 @ 12"

(4) # 4 CONT.

BARS

CENTER ALL WALL

REINFORCING IN FOOTER

1/2" P.J.F.

(TYP.)

1'&0" 8" 1'&0"8" 8" 8"5" 8" 5"

GEOFOAM EPS 22 FILL

(OR EQUIVALENT)

MEMBRANE TO PROTECT

FORM FROM PETROLEUM

PRODUCTS

4' & 0" 4' & 0" 5' & 6"

1/2" P.J.F.

GEOFOAM

FILL

GALV L3x3x1/4 W/ 1/2" DIA. x 6" HS @ 12" O.C.

7" SLAB (SEE PLAN

FOR REINFORCING)

#3 @ 12" O.C.16"

16"

7" SLAB (SEE PLAN

FOR REINFORCING)

PROVIDE 3/4"

CHAMFER; TYPICAL

S-6

6'&0"

OPTIONAL COLD

JOINT

GEOFOAM

FILL

I

S-6

GALV L3x3x1/4 W/ 1/2" DIA. x 6" HS @ 12" O.C.

7" SLAB (SEE PLAN

FOR REINFORCING)

#3 @ 12" O.C. 16"

16"

7" SLAB (SEE PLAN

FOR REINFORCING)

PROVIDE 3/4"

CHAMFER; TYPICAL

GALV L3x3x1/4 W/ 1/2" DIA. x 6" HS @ 12" O.C.

#3 @ 12" O.C.24"

24"

1' &7" + /& 1 /8 "

1' &8

1/

8"

DOCK LEVELER

WALL BEYOND

7" SLAB (SEE PLAN

FOR REINFORCING)

EXISTING SLAB

REFER TO DETAIL ON 1/S&6

FOR TYPICAL DETAIL AT NEW

SLAB TO EXISTING SLAB

6" 8" 1'&6"

#4 @ 8" CONT.

#4 @ 12"

(6) # 4 CONT.

BARS

8'&0"

PROVIDE MITERED

CORNER PIECES (TYP.)

COMPACTED FILL

GEOFOAM EPS 22 FILL

(OR EQUIVALENT)

MEMBRANE TO PROTECT

FORM FROM PETROLEUM

PRODUCTS

1/2" P.J.F.

7" SLAB, (SEE PLAN

FOR REINFORCING)

8" CONCRETE WALL; (SEE

PLAN FOR REINFORCING)

GALV L3x3x1/4 W/ 1/2" DIA. x 6"

HS @ 12" O.C. AT LOADING

DOCK LOCATIONS

#3 @ 12" O.C.

24"

24"

PROVIDE 3/4" CHAMFER;

TYPICAL

GEOFOAM EPS 22 FILL

(OR EQUIVALENT)

#4 @ 6" O.C.

18"

(3) #4 TIES

PROVIDE SLEEVE PER CANOPY DESIGNER'S

RECOMMENDATIONS. EMBED COLUMN INTO

CONCRETE PER CANOPY DESIGNER'S

RECOMMENDATIONS.

PRE&ENGINEERED ALUMINUM

COLUMN; BY CANOPY DESIGNER

8" 1' & 2" 5"

10"

18"

1' &2

6"

#4 @ 8" CONT.

PROVIDE SLEEVE PER CANOPY DESIGNER'S

RECOMMENDATIONS. EMBED COLUMN INTO

CONCRETE PER CANOPY DESIGNER'S

RECOMMENDATIONS.

PRE&ENGINEERED

ALUMINUM COLUMN; BY

CANOPY DESIGNER

5'&6"

(5) #5 BARS EACH

WAY, TOP & BOTTOM

2'&0"

A A

SECTION AA

(8) #5 VERTICAL

BARS

#3 TIES @ 12" O.C.

5'&6" x 5'&6" x 12"

THICK FOOTER

C O

V E

R

M

IN

.1 8"

#4 @ 6" O.C.

18"

16"

18"

2'&0"

7" 10" 7"

5" 1'&2" 5"

1' &2

2'

&1 0"

3/4" CHAMFER;

TYP.

(3) #4

ADDITIONAL

TIES

3/4" CHAMFER;

TYP.

4' &4

1'&9" 2'&0" 1'&9"

3" M

IN

TO TIES

2" TYP.

AS�BUILT

96 CEG, OFFICE FORM 002, FY2018

DATEREVISION BY APPR'D

PROGRAM MANAGER

ENVIROMENTAL

INDEX NO.

CENM

APPROVED

APPROVED

APPROVED

SIGNATURE

DATE

USING AGENCY

APPROVED

APPROVED

COMMUNICATIONS

OPERATIONS ENGINEERING

APPROVED

APPROVED

APPROVED

APPROVED

FIRE PREVENTION

SAFETY REPRESENTATIVE

DIR. BASE MED. SERVICE

PROJ. ENGR.

DRAWN BY TITLE

CONTENTS

APPROVED

SCALE

DATE

96 CEG/CEN

APPROVED

DEPUTY BASE CIVIL ENGINEER

SPEC. NO. PROJ. NO. DRAWING NO. FILE NO.

SHEET OFFTFA

DESCRIPTION

SECURITY FORCES

APPROVED

ASUS

APPROVED

CHELCO

APPROVED

D

EU

SOJ

R E

G

ISTERE

R E

E

NIGNED

EPH

ER

IL

SI

U

OL

A

DIOL

F R

STATE OF

No. 54319

E T

ACFIT

C R

E

I

301 West Cervantes St. Tel. 850.429.1951301 West Cervantes St. Tel. 850.429.1951301 West Cervantes St. Tel. 850.429.1951301 West Cervantes St. Tel. 850.429.1951 Pensacola, FL 32501 Pensacola, FL 32501 Pensacola, FL 32501 Pensacola, FL 32501

JOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLC S T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SJDA

STATE OF FLORIDA STATE OF FLORIDA STATE OF FLORIDA STATE OF FLORIDA

P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515

JULY,2019

J. SUMRALL

L. DeREUIL

Hernandez Calhoun Design International Architecture ● Interior Design

RENOVATE

BUILDING 886

EGLIN, AFB,FLORIDA

17�1100 XXXX17AP

Hernandez Calhoun Design International Architecture ● Interior Design 17AP

BASE CIVIL ENGINEER

EGLIN AIR FORCE BASE, FLORIDA

JDA Job #: 17199JDA Job #: 17199JDA Job #: 17199JDA Job #: 17199

7/12/20197/12/20197/12/20197/12/2019

S-6

SECTIONS AND DETAILS

3/4" = 1'-0"S-6

2 CONCRETE RAMP SECTION

3/4" = 1'-0"S-6

1 DOCK LEVELER SECTION

3/4" = 1'-0"S-6

3 DOCK LEVELER SECTION

3/4" = 1'-0"S-6

4 TYPICAL ALUMINUM CANOPY COLUMN SLEEVE

3/4" = 1'-0"S-6

5 TYPICAL ALUMINUM CANOPY COLUMN

6"

1'&6 O.C.

2" C

LR

7"

3"

CLR.

1 2 T

1 2 T

P

N A

C o n s tr u c tio n T e c h n o lo g ie s , I n c

. A ll ri g h ts r e s e rv e d . D ia m o n d D o w e l®

, A rm o r-

E d g e

, L o a d P la te

B a s k e t® a n d P

D

B a s k e t® a re r e g is te re d tr a d e m a rk s a n d

H y d ra

C u re a n d S q u a re

D o w e l C lip a re tr a d e m a rk s o f P N

A C o n s tr u c tio n

T e c h n o lo g ie s

, I n c . P ro d u c ts s h o w n m a y b e c o v e re d b y o n e o r m o re o f U .S

. p a te n ts

,7

,9

,3

,7

; G re a t B ri ta in p a te n t #

; M e x ic o p a te n t #

; N e w

Z e a la n d p a te n t #

; I n d ia p a te n t # a n d o th e r p e n d in g p a te n ts

SLOTS CUT USING COVEX

CV&9000 SAW FOR PLATES UP

TO 3/4" (20 MM) TO ENSURE

SAFE AND ACCURATE

INSTALLATION IN THE FIELD.

EXISTING SLAB

COVEX 3/8" DOWELS MANUFACTURED

FROM HOT&ROLLED STEEL CERTIFIED TO

MEET ASTM A36, CUT FULL&DEPTH AND

DEBURRED PER INDUSTRY GUIDELINES.

COVES DOWEL SYSTEM AS

MANUFACTURED BY PNA CONSTRUCTION

TECHNOLOGIES, INC. MARSHA MOORE

HARDING / SE TERRITORY MANAGER /

PNA / 678&576&1223.

SELECT OPTION BASED

ON AVAILABILITY OF

SAW AND DOWELS

OPTION 1

COVEX DOWEL

SPACED AS INDICATED

EXISTING SLAB

APPLY BOND BREAK

AGENT TO EXISTING SLAB

NEW SLAB

REINF. (SEE PLAN)

OPTION 2

2" C

LR

7"

3"

CLR.

7/8" Ø x 14" LONG SMOOTH

DOWEL @ 12" O.C.

EXISTING SLAB

APPLY BOND BREAK

AGENT TO EXISTING SLAB

NEW SLAB

REINF. (SEE PLAN)

E Q

E Q

DRILL & EPOXY

COAT TO

PREVENT BOND

1/2" x 1&1/2" PLASTIC OR

HARDBOARD PREFORMED STRIP

FIRST SLAB

PLACEMENT

SECOND SLAB

PLACEMENT

DIAMOND

DOWEL SYSTEM

1' &6

1'

&6

2" C

LR

8"

3"

CLR.

REINF.(SEE PLAN)

APPLY BOND BREAK

AGENT TO FIRST SLAB

REINF. (SEE PLAN)

3/4" x 4 1/2" SQUARE DIAMOND DOWEL

SYSTEM AS MANUFACTURED BY PNA

CONSTRUCTION TECHNOLOGIES, INC.

MARSHA MOORE HARDING / SE

TERRITORY MANAGER / PNA /

678&576&1223.

3/4" CHAMFER EACH FACE

CUT OR TERMINATE 50% OF

HORIZONTAL REINF. AT JOINT

CRACK INDUCED BY

CONTROL JOINT

3/4" CHAMFER EACH FACE

CUT OR TERMINATE 50% OF

HORIZONTAL REINF. AT JOINT

CRACK INDUCED BY

CONTROL JOINT

TYPICAL WALL CONTROL JOINT DETAIL

TYPICAL WALL CONSTRUCTION JOINT DETAIL

TYPICAL WALL REINF.

TYPICAL WALL REINF.

2" CLR. TYP.

2" CLR. TYP.

SINGLE LAYER OF REINF.

AS�BUILT

96 CEG, OFFICE FORM 002, FY2018

DATEREVISION BY APPR'D

PROGRAM MANAGER

ENVIROMENTAL

INDEX NO.

CENM

APPROVED

APPROVED

APPROVED

SIGNATURE

DATE

USING AGENCY

APPROVED

APPROVED

COMMUNICATIONS

OPERATIONS ENGINEERING

APPROVED

APPROVED

APPROVED

APPROVED

FIRE PREVENTION

SAFETY REPRESENTATIVE

DIR. BASE MED. SERVICE

PROJ. ENGR.

DRAWN BY TITLE

CONTENTS

APPROVED

SCALE

DATE

96 CEG/CEN

APPROVED

DEPUTY BASE CIVIL ENGINEER

SPEC. NO. PROJ. NO. DRAWING NO. FILE NO.

SHEET OFFTFA

DESCRIPTION

SECURITY FORCES

APPROVED

ASUS

APPROVED

CHELCO

APPROVED

D

EU

SOJ

R E

G

ISTERE

R E

E

NIGNED

EPH

ER

IL

SI

U

OL

A

DIOL

F R

STATE OF

No. 54319

E T

ACFIT

C R

E

I

301 West Cervantes St. Tel. 850.429.1951301 West Cervantes St. Tel. 850.429.1951301 West Cervantes St. Tel. 850.429.1951301 West Cervantes St. Tel. 850.429.1951 Pensacola, FL 32501 Pensacola, FL 32501 Pensacola, FL 32501 Pensacola, FL 32501

JOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLC S T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SJDA

STATE OF FLORIDA STATE OF FLORIDA STATE OF FLORIDA STATE OF FLORIDA

P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515

JULY,2019

J. SUMRALL

L. DeREUIL

Hernandez Calhoun Design International Architecture ● Interior Design

RENOVATE

BUILDING 886

EGLIN, AFB,FLORIDA

17�1100 XXXX17AP

Hernandez Calhoun Design International Architecture ● Interior Design 17AP

BASE CIVIL ENGINEER

EGLIN AIR FORCE BASE, FLORIDA

JDA Job #: 17199JDA Job #: 17199JDA Job #: 17199JDA Job #: 17199

7/12/20197/12/20197/12/20197/12/2019

S-7

TYPICAL DETAILS

3/4" = 1'-0"S-7

1 TYPICAL DETAIL AT NEW SLABS TO EXISTING SLABS

3/4" = 1'-0"S-7

2 TYPICAL CONSTRUCTION JOINT DETAIL

3/4" = 1'-0"S-7

3 TYPICAL VERTICAL WALL CONTROL JONT DETAILS

07/27/2018

Door Schedule

Mark Space

Door Frame Hardware

Remarks

Size Door Material

Door Type Glazing

Frame Material

Frame Type

Details Set Number

Keyside SpaceWidth Height Thick. Head Jamb Sill

Window/Louver Schedule

Mark

Window/Louver Frame

Remarks

Size Glazing Type Material

Details

Width Height Head Jamb Sill

BASE CIVIL ENGINEER

ROOM FINISH SCHEDULE

ROOM

No. ROOM NAME

FLOOR BASE WALLS CEILING

REMARKS

MATERIAL COLOR MATERIAL COLOR

NORTH EAST SOUTH WEST

MATERIAL COLOR

MATERIAL COLOR MATERIAL COLOR MATERIAL COLOR MATERIAL COLOR

SIGNAGE SCHEDULE

# TYPE SIGN

SIZE

TEXT/

DESCRIPTION NOTES

BASE CIVIL ENGINEER

EGLIN AIR FORCE BASE, FLORIDA

AS-BUILT

RENOVATIONS TO

BUILDING 886

EGLIN AFB, FLORIDA

FACU

DISPLAY

MONACO

TRANSMISSION

SUPERVISING

STATION (SS)

EVAC

AU

D

IO

/V

IS

U

AL

T

R O

U

BL

E

IN

D

IC

AT

IO

N B

Y D

EV

IC

E

XM

IT

A

LA

R M

S

IG

N

AL

PU

LL

ST

AT

IO

N T

O S

S

XM

IT

T R

O U

BL

E

SI

G

N

AL

T O

S S

FI

R

E

AL

AR

M

S

TR

O

BE

S

TH

R O

U G

H O

U T

G

EN

. E

VA

C M

ES

SA

G E

TH

R

O U

G H

O U

T

MANUAL PULL STATION X

FIRE ALARM AC POWER FAILURE

FIRE ALARM SYSTEM LOW/MISSING BATTERY

ALARM SIGNALS

TROUBLE SIGNALS

SHORT CIRCUIT

OPEN CIRCUIT

GROUND FAULT

AU

D

IO

/V

IS

U

AL

A

LA

R

M

IN

D

IC

AT

IO

N B

Y D

EV

IC

E

X XX

X X X X X

X X X X X

XM

IT

A

LA

R M

S

IG

N

AL

W

AT

ER

FL

O

W T

O S

S

XM

IT

A

LA

R M

S

IG

N

AL

-S M

O

KE

D

ET

EC

TO

R T

O S

S

SUPERVISED COMPONENT FAILURE

SUPERVISING STATION CONNECTION FAULT

X X

X

X X XXSMOKE DETECTOR - FACP

SPRINKLER SYSTEM WATERFLOW SWITCH X X X X

CARBON MONOXIDE DETECTOR X

XM

IT

A

LA

R M

S

IG

N

AL

C

AR

BO

N M

O N

O

XI

D E

TO

S

S

X XX

SUPERVISORY SIGNALS

SPRINKLER SYSTEM TAMPER SWITCH

XM

IT

T

AM

PE

R

S W

IT

C

H

SU

PE

R

VI

SO

R Y

S

IG

N

AL

T O

S S

AU

D

IO

/V

IS

U

AL

S

U

PE

R

VI

SO

R

Y

IN

D

IC

AT

IO

N B

Y D

EV

IC

E

X X

BASE CIVIL ENGINEER

EGLIN AIR FORCE BASE, FLORIDA

AS-BUILT

RENOVATIONS TO

AS-BUILT

RENOVATIONS TO

D P R O J E C T

R e n o v a t e

B u i l d i n g

D W G M e c h M d w g

P M j o i n e r

D P R O J E C T

R e n o v a t e

B u i l d i n g

D W G P l u m b i n g P d w g

P M j o i n e r

AS-BUILT

RENOVATIONS TO

AS-BUILT

RENOVATIONS TO

AS-BUILT

RENOVATIONS TO

AS-BUILT

RENOVATIONS TO

AS-BUILT

RENOVATIONS TO

AS-BUILT

RENOVATIONS TO

AS-BUILT

RENOVATIONS TO

AS-BUILT

RENOVATIONS TO

TELECOMMUNICATIONS & ELECTRONIC SECURITY SYSTEM LEGEND

DEVICE

SYMBOL

SYMBOL

SUBSCRIPT -

TYPE 'x'

DESCRIPTION CAT 6 UTP (QTY) RG-6 COAX

(QTY)

FIBER MODULE

(DUPLEX QTY)

JACK/MODULE

TYPE

JACK/MODULE

COLOR

MOUNTING HEIGHT AFF

(UNO)

BUILDING SUPPORT SYSTEM DEVICES

DDC DIRECT DIGITAL CONTROLS NETWORK OUTLET (2) - - RJ-45 VIOLET 48"; COORD. W/ VENDOR;

SEE DETAIL

UNCLASSIFIED NETWORK DEVICES

- NIPRNET/VOICE OUTLET (2) - - RJ-45 WHITE 18"; SEE DETAIL

UNCLASSIFIED WALL MOUNT VOICE DEVICES

- WALL MOUNT VOICE OUTLET (1) - - RJ-45 WHITE 48"

UNCLASSIFIED RACEWAY & SUPPORTING INFRASTRUCTURE

- ABOVEGROUND CONDUIT - - - - - SEE PLAN

PBB PRIMARY BONDING BUSBAR - - - - - SEE PLAN; DETAILS

UNCLASSIFIED RACEWAY & SUPPORTING INFRASTRUCTURE - SITE

- UNDERGROUND CONDUIT - - - - - SEE PLAN

AUDIO VISUAL SYSTEMS - ROUGH-IN ONLY

- FLAT PANEL DISPLAY ROUGH-IN - (1) - F-CONN MATCH

FACEPLATE SEE DETAILS

- AV ROUGH-IN - - - - - SEE DETAILS

ACCESS CONTROL SYSTEM (ACS)

- CARD READER - INTERIOR SEE ACS DIAGRAM 48"; SEE DETAILS

EXT CARD READER - EXTERIOR SEE ACS DIAGRAM 48"; SEE DETAILS

- ACS INTERFACE UNIT SEE ACS DIAGRAM SEE PLAN

x

ABOVE FINISH FLOOR

ACCREDITING OFFICIAL

AMERICANS WITH DISABILITIES ACT

AMERICAN NATIONAL STANDARDS INSTITUTE

AMERICAN WIRE GAUGE

APPROVING AUTHORITY

ARCHITECTURAL

AUTHORITY HAVING JURISDICTION

BONDING BACKBONE CONDUCTOR

BUILDING AUTOMATION SYSTEM

CABLE TRAY

CATEGORY 3

CATEGORY 5 ENHANCED

CATEGORY 6

CATEGORY 6 AUGMENTED

COMMUNICATIONS OUTLET

COMMUNITY ANTENNA TELEVISION

CONDUIT

CONSOLIDATION POINT

CONTRACTOR FURNISHED, CONTRACTOR INSTALLED

CONTRACTOR FURNISHED, GOVERNMENT INSTALLED

CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE

DEMARCATION

ELECTRICAL

ELECTROMAGNETIC INTERFERENCE

ENERGY MANAGEMENT CONTROL SYSTEM

ELECTRICAL METALLIC TUBING

FEDERAL COMMUNICATIONS COMMISSION

FIBER OPTIC

GOVERNMENT FURNISHED, CONTRACTOR INSTALLED

GOVERNMENT FURNISHED, GOVERNMENT INSTALLED

HANDHOLE

LOCAL AREA NETWORK

LIGHT INTERCONNECT UNIT

MAIN TELECOMMUNICATIONS ROOM

MAINTENANCE HOLE

MAXIMUM

MICRON / MICROMETER

MINIMUM

MULTI-USER TELECOMMUNICATIONS OUTLET ASSEMBLY

MULTIMODE

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL SAFETY CODE

NATIONAL FIRE PROTECTION ASSOCIATION

UNCLASSIFIED INTERNET PROTOCOL ROUTER NETWORK

NOT APPLICABLE

NOT IN CONTRACT

OUTSIDE PLANT

PAIR

PATCH PANEL

POLYVINYL CHLORIDE

PULL BOX

PRIMARY BONDING BUSBAR

PRIVATE BRANCH EXCHANGE

RACK MOUNTED UNIT

ROOM

ROUGH-IN

SCREENED TWISTED-PAIR

SECONDARY BONDING BUSBAR

SECURED VIDEO TELECONFERENCE

SHIELDED TWISTED-PAIR

SINGLEMODE

SURFACE MOUNT

STRANDS

TELECOMMUNICATIONS BONDING BACKBONE

TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR

TELECOMMUNICATIONS BONDING CONDUCTOR

TELECOMMUNICATIONS EQUIPMENT ROOM

TELECOMMUNICATIONS ROOM

TELECOMMUNICATIONS INDUSTRY ASSOCIATION

UNDERWRITERS LABORATORIES INC

UNINTERRUPTIBLE POWER SUPPLY

UNSHIELDED TWISTED-PAIR

TYPICAL

UNLESS NOTED OTHERWISE

VIDEO TELECONFERENCE

VOICE OVER INTERNET PROTOCOL

AFF

A.O.

ADA

ANSI

AWG

AA

ARCH

AHJ

BBC

BAS

CT

CAT 3

CAT 5E

CAT 6

CAT 6A

CO

CATV

C

CP

CFCI

CFGI

COTR

DEMARC

ELEC

EMI

EMCS

EMT

FCC

FO

GFCI

GFGI

HH

LAN

LIU

MTR

MH

MAX

um

MIN

MUTOA

MM

NEMA

NEC

NESC

NFPA

NIPRNET

N/A

NIC

OSP

PR

PP

PVC

PB

PBB

PBX

RMU

RM

R/I

ScTP

SBB

SVTC

STP

SM

SF

STR

TBB

TEBC

TBC

TER

TR

TIA

UL

UPS

UTP

TYP

UNO

VTC

VoIP

TELECOM ABBREVIATIONS:

FP

CR

ACS

x

AV

BASE CIVIL ENGINEER

EGLIN AIR FORCE BASE, FLORIDA

AS-BUILT

RENOVATIONS TO

BUILDING 886

EGLIN AFB, FLORIDA

TELECOM & SECURITY LEGEND & ABBREVIATIONS

T001

TELECOMMUNICATIONS GENERAL NOTES - FACILITY INFRASTRUCTURE:

THE TELECOMMUNICATIONS DRAWINGS PROVIDED ARE DIAGRAMMATIC AND SHOW THE GENERAL

LOCATION OF ALL REQUIRED DEVICES; SUCH AS OUTLETS, RACEWAYS, EQUIPMENT, AND

APPURTENANCES. THEY DO NOT SHOW ALL NECESSARY OFFSETS, JUNCTION BOXES,

CABLE/LADDER TRAY TRANSITIONS, CONDUIT SLEEVES/PENETRATIONS, AND ADJUSTMENTS

NECESSARY BY COORDINATION WITH OTHER TRADES IN THE FIELD.

TELECOMMUNICATION CONTRACTOR'S SCOPE OF WORK: TELECOMMUNICATION'S CONTRACTOR

SHALL BE RESPONSIBLE FOR ENTIRE STRUCTURED CABLING SYSTEM ELEMENTS DEFINED IN THIS SCOPE OF WORK. THIS INCLUDES A COMPLETE INSTALLATION OF ALL PASSIVE INFRASTRUCTURE ELEMENTS SUCH AS OUTLETS, JACKS, CABLING, CABINETS, BACKBOARDS, TELECOM EQUIPMENT ROOM/CABINET BONDING, TERMINATIONS, TESTING, LABELING, WARRANTIES, AND ALL REQUIRED

CLOSE-OUT DOCUMENTS. THE TELECOMMUNICATIONS CONTRACTOR SHALL UNDERSTAND THE

FULL INTENT OF THE DRAWINGS AND SPECIFICATIONS PRIOR TO BID, AND WILL INCLUDE IN SCOPE

OF WORK ALL REQUIREMENTS NECESSARY TO ENSURE A FULLY FUNCTIONAL SYSTEM.

COORDINATION: WITH OTHER TRADES EXAMINE AND REVIEW THE DOCUMENTS OF ALL DIVISIONS IN ORDER TO COORDINATE THE INSTALLATION OF WORK. USE DIMENSIONED DRAWINGS TO VERIFY

THE SPACE NECESSARY FOR LOCATING OUTLETS, RACEWAYS, AND EQUIPMENT. USE FIELD

MEASUREMENTS TO VERIFY DIMENSIONS WHERE AREAS ARE CONGESTED, AND EXACT LOCATION

IS CRITICAL TO ENSURE PROPER INSTALLATION. COORDINATION SHALL INCLUDE, BUT NOT BE LIMITED TO; VERIFYING THE LOCATION AND SIZE OF OPENINGS/PENETRATIONS IN FLOORS, WALLS, PARTITIONS, CEILINGS, AND ROOFS WITH THE INSTALLING TRADES; ALLOCATION OF SPACE WITH OTHER TRADES, INSTALLING WORK IN CHASES, SHAFTS, CEILING INTERSTITIAL SPACES, AND EQUIPMENT SPACES; AND THE PHASING OF INSTALLATION WORK WITH THAT OF OTHER TRADES.

INSTALLATION SHALL CONFORM WITH NFPA 70 "NATIONAL ELECTRICAL CODE," ANSI/TIA, UFC 3-580-01, UFC 4-010-06, AND EGLIN AFB WIRE/CABLE SPECS - 96 CS DATED 11 AUG 2014 (UNO).

CABLING INSTALLATION: ALL CABLING ROUTED IN SLAB, BELOW VAPOR BARRIER OR BELOW

GRADE, SHALL BE U.L. LISTED FOR WET LOCATIONS THAT COMPLIES WITH UFC 3-580-01 AND NFPA

70. DO NOT USE PLENUM OR RISER RATED CABLE, GEL-FILLED OSP, AND UNLISTED CABLES IN SUCH

AN ENVIRONMENT.

USE A FILL RATIO OF 40 PERCENT FOR CONDUIT SIZING. DO NOT INSTALL MORE THAN FOUR, FOUR-PAIR CABLES IN A 1 INCH (27 MM) CONDUIT.

LABEL ALL CABLES WITHIN 4 INCHES OF EACH TERMINATION. PROVIDE 12 INCHES SERVICE LOOP AT

THE WORK AREA END OF EACH HORIZONTAL CABLE.

INSTALL VELCRO CABLE TIES TO ALL CABLE BUNDLES IN RACK WIRE MANAGEMENT, D-RINGS AND

OTHER SUPPORT MEANS.

BALANCED TWISTED-PAIR CABLING SHALL BE SEPARATED FROM FLUORESCENT LAMPS AND

ASSOCIATED FIXTURES BY A MINIMUM OF 5 IN.

THE MAXIMUM FILL OF ANY EXISTING CABLE TRAY SHALL NOT EXCEED 50%. THE MAXIMUM FILL

DEPTH OF ANY CABLE TRAY SHALL NOT EXCEED 6 IN.

TELECOMMUNICATIONS FACEPLATES SHALL MATCH ELECTRICAL SWITCH AND RECEPTACLE PLATE

FINISHES.

PROVIDE COVER PLATES FOR ALL UNUSED J-BOX LOCATIONS.

PROVIDE PULL STRING IN ALL EMPTY CONDUIT AND INNERDUCT. PULL STRING TO BE RATED FOR 200lbs. IN ALL CONDUIT.

MAIN TELECOM CABINET (MTC):

INSTALL BACKBOARDS IN ACCORDANCE WITH TIA-569-C. BACKBOARDS MUST BE FIRE-RETARDANT TREATED WOOD, BEARING THE MANUFACTURER’S STAMP. IF PAINTED, THE MANUFACTURES FIRE

RATED STAMP MUST REMAIN VISIBLE.

INSTALL WALL MOUNTED CABINETS MAINTAINING A MINIMUM OF 36 INCHES SPACE IN FRONT OF

CABINET. PROVIDE 25% SPARE CAPACITY WITHIN EACH UTILIZED RACK.

FURNITURE/MILLWORK:

ENSURE THAT THE CABLE IS PROTECTED AT ALL TRANSITION POINTS, AND THAT METALLIC

SEPARATION IS PROVIDED BETWEEN TELECOMMUNICATION AND POWER WIRING IN THE UTILITY

COLUMNS AND SYSTEMS FURNITURE TRACK IN ACCORDANCE WITH TIA-569-C AND NFPA 70.

ELECTRICAL GENERAL NOTES - FACILITY INFRASTRUCTURE:

ELECTRICAL CONTRACTOR'S SCOPE OF WORK:

ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE ENTIRE INTERIOR ROUGH-IN AND

SUPPORT SYSTEM NECESSARY FOR THE COMPLETE STRUCTURED CABLING SYSTEM DEFINED IN

THIS SCOPE OF WORK. THIS INCLUDES A COMPLETE INSTALLATION OF ALL REQUIRED PATHWAYS

INCLUDING: CONDUIT, BACK BOXES, JUNCTION BOXES, FLOOR BOXES, BLOCKING, GROUNDING

CONDUCTORS AND BUSBARS, FIRESTOPPING, POWER, AND ANY OTHER NECESSARY

APPURTENANCES.

THE ELECTRICAL CONTRACTOR SHALL UNDERSTAND THE FULL INTENT OF THE DRAWINGS AND

SPECIFICATIONS PRIOR TO BID, AND WILL INCLUDE IN SCOPE OF WORK ALL REQUIREMENTS

NECESSARY TO SUPPORT THE TELECOMMUNICATIONS SYSTEM TO COORDINATE AND ENSURE A

FULLY FUNCTIONAL SYSTEM.

COORDINATION WITH OTHER TRADES:

EXAMINE AND REVIEW THE DOCUMENTS OF ALL DIVISIONS IN ORDER TO COORDINATE THE

INSTALLATION OF WORK. USE DIMENSIONED DRAWINGS TO VERIFY THE SPACE NECESSARY FOR

LOCATING OUTLETS, RACEWAYS, AND EQUIPMENT. USE FIELD MEASUREMENTS TO VERIFY

DIMENSIONS WHERE AREAS ARE CONGESTED, AND EXACT LOCATION IS CRITICAL TO ENSURE

PROPER INSTALLATION. COORDINATION SHALL INCLUDE, BUT NOT BE LIMITED TO, VERIFYING THE LOCATION AND SIZE OF OPENINGS/PENETRATIONS IN FLOORS, WALLS, PARTITIONS, CEILINGS, AND ROOFS WITH THE INSTALLING TRADES; ALLOCATION OF SPACE WITH OTHER TRADES, INSTALLING WORK IN CHASES, SHAFTS, CEILING INTERSTITIAL SPACES, AND EQUIPMENT SPACES; AND THE

PHASING OF INSTALLATION WORK WITH THAT OF OTHER TRADES.

INSTALLATION SHALL CONFORM WITH NFPA 70 "NATIONAL ELECTRICAL CODE," ANSI/TIA, UFC 3-580-01, ELECTRICAL SPECIFICATIONS, AND EGLIN AFB WIRE/CABLE SPECS - 96 CS DATED 11 AUG 2014 (UNO).

CONDUIT:

INSTALL ELECTRICAL METALLIC TUBING (EMT) CONDUIT FROM THE CABLE BACKBONE…

This is the start of the file's text. The full file is on GovTribe.