This document contains questions and answers regarding a fire alarm upgrade project for Building 122 and Building 1525 at Edwards Air Force Base. The questions and answers provide device counts for smoke detectors, heat detectors, water flows, tampers, pull stations, modules, duct detectors, and horn/strobe units for Building 1525. For Building 122, the response indicates the building is mainly a fire suppression system rather than detection, and will require evaluation by a contractor to bring it up to fire protection code for suppression.
The related federal contract opportunity lists the solicitation number and provides the name and location for the Bldg 122 & 1525 Edwards Fire Alarm Upgrade project being conducted by the Department of the Air Force Space Command.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BLDG 122 & BLDG 1525 FIRE ALARM UPGRADE: QUESTIONS AND ANSWERS
Question #1: In the solicitation it is called out to provide a one for one device replacement. Will the device counts be provided? For the smoke/heat detectors and monitor modules?
Answer #1:
B1525:
Smokes: 19
Heats: 29
Water Flows: 2
Tampers: 4
Pull Stations: 8
Modules: 73
Ducts: 2
Horn/Strobe Units: 8
B122 : This Building is mainly Fire Suppression rather than fire detection. Meaning, the contractor will need to see this building in order to bring it up to Fire Protection Code. Fire protection code for suppression, not detection.
Smokes: 0
Heats: 2
Water Flows: 4
Tampers: 4
Pull Stations: 10
Modules: 40
Ducts: 8
Horn/Strobe Units: 12