Field Service Report

Service Date: 03/02/2021 Phone: 800-247-3973 Fax: 516-932-0014

TO: SITE #: 21297-001 FOR:

F3L350-721 CES

1 NORAD RD STE 12104

CHEYENNE MOUNTAIN

AF CO 80914

CHEYENNE MOUNTAIN

AIRFORCE STATION

1 NORAD RD

CHEYENNE MOUNTAIN AF CO

80914

ANALYSIS

Call Slip: 3725409 Limit Equip # 1 – 8/10 Constituent MIN MAX Cooling Tower (CT )

Equipment 1 Remarks: System not operating during service visit.

Call Slip: 3725410 Limit Equip # 2 – 6/7 Constituent MIN MAX Cooling Tower (CT )

Equipment 2 Remarks: System not operating during service visit.

Call Slip: 3725411 Make Up Limit Equip # 3 – AUX TOWER Constituent MIN MAX Cooling Tower (CT )

Conductivity 109 500 2000 1092 pH 7.7 6.0 9.0 8.7 Chloride 40 0 500 90 Total Alkalinity 50 100 500 250 Phenol Alkalinity 0 0 100 50 Calcium Hardness 50 0 500 310 Phosphonate 7.0 14.0 8.4

Equipment 3 Remarks: Satisfactory

Call Slip: 3725412 Limit Equip # 4 – MER Constituent MIN MAX Closed Condens.Loop (CCL )

Equipment 4 Remarks: System not operating during service visit.

Analyses, except items marked *, in mg/l (milligrams per liter) ppm (parts per million)

Site Remarks: Main towers are still off at the moment. I was still able to check the conductivity and the are not being used per sand filter install.

Representative: Ian Powers Contact #: (303) 993-9461

Customer: TIFFANY

Signature:

File details come from the government source that posted it. Updated .