Field Service Report

Service Date: 04/06/2021 Phone: 800-247-3973 Fax: 516-932-0014

TO: SITE #: 21297-001 FOR:

F3L350-721 CES

1 NORAD RD STE 12104

CHEYENNE MOUNTAIN

AF CO 80914

CHEYENNE MOUNTAIN

AIRFORCE STATION

1 NORAD RD

CHEYENNE MOUNTAIN AF CO

80914

ANALYSIS

Call Slip: 3740500 Limit Equip # 1 – 8/10 Constituent MIN MAX Cooling Tower (CT )

Equipment 1 Remarks: System not operating during service visit.

Call Slip: 3740501 Limit Equip # 2 – 6/7 Constituent MIN MAX Cooling Tower (CT )

Equipment 2 Remarks: System not operating during service visit.

Call Slip: 3740502 Make Up Limit Equip # 3 – AUX TOWER Constituent MIN MAX Cooling Tower (CT )

Conductivity 99 500 2000 821 pH 7.7 6.0 9.0 8.7 Chloride 30 0 500 90 Total Alkalinity 30 100 500 220 Phenol Alkalinity 0 0 100 30 Calcium Hardness 40 0 500 270 Phosphonate 7.0 14.0 7.0

Equipment 3 Remarks: Satisfactory

Call Slip: 3740503 Make Up Limit Equip # 4 – MER Constituent MIN MAX Closed Condens.Loop (CCL )

Conductivity 223 500 2000 1082 pH 7.7 7.0 9.0 8.7 Chloride 40 0 500 110 Total Alkalinity 50 0 500 240 Phenol Alkalinity 0 0 100 40 Calcium Hardness 60 0 500 280 Phosphonate 5.6 14.0 8.4

Equipment 4 Remarks: Satisfactory

Analyses, except items marked *, in mg/l (milligrams per liter) ppm (parts per million)

Site Remarks: Towers that are running are in good condition and running great. I did have to manually blow down tower 7. Conductivity was at 1500 plus. Had to replace the blow down valve on the aux tower.

Representative: Ian Powers Contact #: (303) 993-9461